Generator Protection
Generator Protection
Electrical Problems
• Generator Internal Faults
• Rotor Ground Faults
• Excitation System Faults
Other Abnormal Conditions
(System Induced Faults)
Excessive Stator • Over heating of stator windings
Currents
Objectives of Classification:
• Damage is minimum
• Auxiliaries if possible are kept energized and time to restart the
unit is minimum
• Over speeding of Turbo Generator due to sudden load throw off is
avoided
Classification of Generator Protections
Class A Class B Class C
Trip Trip Trip
• All Electrical • All Mechanical • Protection for
Protection Trips Trips in which faults in the
within the Turbine will trip system, unit will be
Generator first, following this on House Load
• ~90% of Total Generator will be • 220kV bus bar
Generator Trips tripped on Low protection
• It Includes: Forward or Reverse
• Frequency
Power
• 52C Trip • Over voltages
• 41E Trip
• 52/UAT Trip
• Turbine Trip
Hand Reset Lockout Relay
ANSI CODE
86
10 NO Contacts
6 NC Contacts
Hand Reset Lockout Relay
ANSI CODE Multi Contact Aux Relay
Functions
1. trip the main circuit breaker of a system
2. trip station auxiliary breakers
3. trip field breakers
4. trip and lock out all breakers on a bus
High Speed Tripping Relay
ANSI CODE
auxiliary relay which can be used where
94 a scheme demands several contacts
Functions
1.Event recording
2. Alarm initiation
3. Contact logic arrangements
Protection Against Internal Faults
(Differential Protection)
ANSI CODE
Cause
Effect
Gives rise to large amount of currents that can
damage the stator windings
Protection Scheme
Differential protection with CTs on each side of
generator (Unit Protection)
Differential Relay Working Principle
Turbine Trip