FIKE INSTALLATION

6.3 INSTALL TRANSFORMER AND WIRE AC TO TRANSFORMER

Complete wiring with AC power off


and locked-out

The AC line power must originate from a AC


XFMR +
Battery
Input -

dedicated circuit at the main building power


Secondary

G F2 F1
EARTH P1
Battery Fuse 10A AC Fuse
GROUND
distribution center. The circuit breaker shall be
10A

equipped with a lockout mechanism and be clearly BATTERIES

labeled as a "Fire Protection Control Circuit".


Route the power to the system through the H

TRANSFORMER
dedicated grounded metallic conduit.
the
N
Ensure the power is compatible with
transformer assembly (120VAC or 240VAC).
Route AC ground (chassis) and connect the
to
open press stud in the enclosure back-box,
securing with a hex-nut and washer. Install the OR
transformer(s) into the back-box, onto the four
press-studs. Secure in place with four 6-32 hex
nuts and washers. Route the AC hot and neutral AC XFMR Battery

and ground (chassis) wires into the enclosure and


Secondary + Input -

P21

connect to the transformer Primary as shown. AC XFMR


Secondary + Input -
Battery
P19

G F2 F1

EARTH TO SECONDARY DISPLAY


P1
BATTERIES IF NEEDED
GROUND
Battery Fuse 10A AC Fuse 10A

TO PRIMARY
BATTERIES

CAUTION: AC power Neutral and Hot


connect to the primary side of the H

TRANSFORMER
TRANSFORMER
transformer, H1 and H2, respectively.
The step-down, or secondary, side of N

the transformer, X1 and X2, connect to


the AC XFMR Secondary terminals of
the panel’s P1 jack. Damage WILL
occur if the H1/H2 and X1/X2 sides
are reversed.
Exhibit 6-6 AC to Transformer Wiring

UL S2203 Cheetah Xi™ Product Manual Page 69 of 146


FM 3020297 Manual P/N: 06-356 Rev. 4, 03/10