Design Arrangement and Construction
Design Arrangement and Construction
and Construction
SECTION 10.2.8.1 OCCUPANT LOAD
5. Every room constituting a place of assembly and not having fixed seats
shall have the occupant load of the room posted in a conspicuous place
near the main exit from the room. Approved signs shall be maintained in
legible manner. Signs shall be durable and shall indicate the number of
occupants permitted for each room.
6. In theaters and similar places of assembly where person are admitted to
the building at times when seats are not available for them and are allowed
to wait in a lobby or similar space until seats are available, such use of
lobby or similar spaces shall not encroach upon the required clear width of
exits. Such waiting spaces shall be restricted to areas other than the
required means of egress. Exits shall be provided for such waiting spaces on
the basis of one person for each one-fourth (0.25) square meters of waiting
space area. Such exits shall be in addition to the exits specified for the main
auditorium area and shall conform in construction and arrangement to the
general rules for exits given in this division.
7. In areas not in excess of nine hundred thirty square meters (930 m2), the
occupant load shall not exceed one person in forty-six tenths square meters
(0.46 m2); in areas in excess of nine hundred thirty square meters (930
m2), the occupant load shall not exceed one person in sixty-five tenths
square meters (0.65 m2).
SECTION 10.2.8.2 EXIT DETAILS
A. Capacity of Exits
C. Location of Exits
1. Main Exit
Every assembly occupancy shall be provided with a
main exit. The main exit shall be of sufficient width to
accommodate one-half (1/2) of the total occupant
load, but shall be not less than the total required
width of all aisles, exit passageways and stairways
leading thereto, and shall connect to a stairway or
ramp leading to a street.
2. Other Exits
Each level of an assembly occupancy shall have
access to the main exit and an addition shall be
provided with exits of sufficient width to
accommodate two-thirds (2/3) of the total occupant
load served by that level. Such exits shall open
directly to a street or into an exit court, enclosed
stairway, outside stairway, or exit passageway leading
to a street. Such exits shall be located as far apart
and as far from the main exits as practicable. Such
exits shall be accessible from a cross aisle or a side
aisle.
2. Turnstiles
No turnstiles or other devices to restrict the movement
of persons shall be installed in any place of assembly in
such a manner as to interfere in any way with required
exit facilities. (See Division 5 of this Chapter for further
requirements for turnstiles).
G. Panic Hardware
An exit door from an assembly occupancy shall not be
provided with a
latch or lock unless it is panic hardware.
1. No point within any auxiliary space shall be more than fifteen and
onefourth meters (15.25 m) from a door providing access to an exit.
2. There shall be at least two (2) exits available from every auxiliary stage
space, one of which shall be available within a travel distance of twenty
three meters (23 m). A common path of travel of six meters (6m) to the
two (2) exits shall be permitted.
H. Each stage shall be equipped with a one and a half inch (38.1
millimeters) wet-standpipe equipped with at least 30 meters hose on -each
side of the stage.
SECTION 10.2.8.4 PROJECTION BOOTH
A. No decorative material, which will ignite and allow flame to spread over
the surface when exposed to a flame test shall be allowed to be used in
places of assembly.
B. The method of test shall be as follows: the piece shall be exposed to the
flame from a common match and held in horizontal position twelve and
seven-tenths (12.7) millimeters underneath the piece, and a constant
location for a minimum of fifteen (15 ) seconds.
B. Interior Finish
1. The interior finish requirements of this Section shall be in accordance
with Section 10.2.6.3 of this IRR and subject to modifications specified
therein.
2. Interior finish in all means of egress in all places of assembly shall be
Class A.
3. Interior finish in general assembly areas shall be Class A.
4. Screen on which pictures are projected shall comply with requirements
of Class A or Class B interior finish, as the case maybe.
C. Protection from Hazards
Rooms or spaces used for hazardous equipment, operations and process,
such as but not limited to rooms containing high –pressure vessels,
refrigerating machineries, large transformers, or other service equipment;
rooms or spaces used for the storage, processing or use of boilers or
furnaces, combustible supplies, hazardous materials or flammable or
combustible liquids; laundries; and maintenance shops including
woodworking and painting areas; shall not be directly located under or
abutting required exits and shall be separated from other parts of the
building by fire barriers by construction of not less than 1 hour fire
resistance rating.
D. Fire Detection and Alarm System
2. The required fire alarm system shall activate an audible and visible
alarm in a constantly attended receiving station within the building when
occupied for purposes of initiating emergency action.
E. Extinguishing Requirement
3. The provisions of para “E” (1) and (2) above shall not apply to
assembly occupancies consisting of single multipurpose room of less than
1115 square meters that are not used for exhibition or display and are
not part of a mixed occupancy, all assembly occupancy with all sides
open and places of worship at the level of exit discharge with sufficient
means of egress.
SECTION 10.2.8.9 BUILDING SERVICE EQUIPMENT
A. Elevators
Elevators shall not constitute required means of exit. When places of
assembly are more than three (3) storeys above ground level and
equipped with automatic elevators, at least one elevator shall be
designed and equipped for fire emergency use by members of the BFP,
or as may be determined by the City/Municipal Fire Marshal. Key
operation shall transfer automatic elevator operation to manual and
bring elevator to ground or first floor use by said members. The elevator
shall be situated so as to be readily accessible.
B. Air Conditioning
All air conditioning, heating, and ventilation installations shall comply
with the provisions of Division 7 of this Chapter.
C. Special Provisions for Food Service Establishments
A. A plan showing the capacity and location of the exit ways and aisles
thereto shall be submitted for approval by the City/Municipal Fire Marshal,
and approved copy of such plan shall be kept prominently on display in
the premises.
B. The said firemen shall be in uniform and remain on duty during the
time such places are open to the public, or when the activity is being
conducted. Before each performance or the start of the activity, the said
firemen shall inspect the required fire appliances provided, to see that
they are in proper place and in good working order, and shall keep diligent
watch for fires during the time such place is open to the public or such
activity is being conducted and take prompt measures for the
extinguishment of fire that may occur.
SECTION 10.2.8.13 OUTDOOR ASSEMBLY
A. Capacity Limitations
In existing places of assembly, the Chief, BFP or his duly authorized
representative may permit occupancy by number of persons not to
exceed that for which the existing exits are adequate provided that
measures are established satisfactory to the Chief, BFP or his duly
authorized representative to prevent occupancy by any greater number
of persons based on the calculated occupant load of the building.
B. INTERIOR FINISH
Provisions of Section 10.2.6.3 of this IRR shall apply in existing places of
assembly where interior finish does not conform to the requirements for
new assembly buildings.
SECTION 10.2.8.17 PROJECTION ROOMS FOR SAFETY FILM
A. Every projection room shall be of permanent construction consistent with
the construction requirements for the Type of building in which the
projection room is located. The room shall have a floor area of not less than
seven and four-tenths square meters (7.4 m2) for a single machine and at
least three and three-fourths square meters (3.75 m2) for each additional
machine. Each motion picture projector, floodlight, spotlight, or similar piece
of equipment shall have a clear working space not less than two and one-
fourth square meters (2.25 m2).
C. The aggregate of ports and openings for projection equipment shall not
exceed twenty-five percent (25%) of the area of the wall between the
projection room and the auditorium. All opening shall be provided with glass
or other approved materials, so as to completely close the opening.
PROJECTION ROOMS
D. Projection booth room ventilation shall be not less than the following:
1. Supply Air
Each projection room shall be provided with two or more separate fresh
air inlet ducts with screened openings terminating within thirty
centimeters (30 cm) of the floor, and located at opposite ends of the
room. Such air inlets shall be of sufficient size to permit an air change
every three minutes. Fresh air may be supplied from the general building
air conditioning system, providing it is so arranged that the projection
booth will continue to receive one change of air every three (3) minutes,
when no other air is supplied by the general air conditioning system.
2. Exhaust Air
Each projection room shall be provided with one or more exhaust air
outlets which may be manifold into a single duct outside the booth. Such
outlets shall be so located as to ensure circulation throughout the room.
Projection room exhaust air system shall be independent of any other air
systems in the buildings. Exhaust air ducts shall terminate at the exterior
of the building in such a location that the exhaust system shall be
mechanically operated and of such a capacity as to provide a minimum of
one change of air every three minutes. The blower motor shall be outside
the duct system. The projection room ventilation system may also
appurtenant rooms, such as the generator room and the rewind room.
E. Each projection machine shall be provided with an exhaust duct which will
draw air from each lamp and exhaust it directly to the outside of the building
in such a fashion that it will not be picked up by supply inlets. Such a duct
shall be of rigid materials, except for a continuous flexible connector
approved for the purpose. The lamp exhaust systems shall not be
interconnected with any other system.
F. Each projection room shall be provided with rewind and film storage facilities.
G. A maximum of four (4) containers for flammable liquids not greater than
one-half liter (0.5ℓ) capacity and of a non-breakable type may be permitted in
each projection booth.
H. Appurtenant electrical equipment such as rheostats, transformers, and
generators may be located within the booth or in a separate room of equivalent
fire resistance construction.
SECTION 10.2.8.18 OPEN FLAME