EEL - LIEBERT - HPAC Nuevas Tecnologias Vs Comfort
EEL - LIEBERT - HPAC Nuevas Tecnologias Vs Comfort
Nuevas Tecnologias vs
Sistemas de Comfort
Jorge Murillo
Gerente Regional, America Latina
Division Logo
Types of Heat Loads
Comfort Precision
•24 x 365
•Summer •Temperature &
•Temperature Only •Humidity
Emerson Confidential
Latent and Sensible Cooling
Latent Sensible
Total
Emerson Confidential
Electronic Machines Generate Only
Sensible Heat
100%
TOTAL
Emerson Confidential
Typical Loads Watts/Square Meter
Comfort Precision
++ People 10 2
++ Light 20 20
++ Equipment 30 600
++ Perimeter (Walls) 25 15
++ Infiltration (Outside Air) 15 3
Emerson Confidential
Sensible Heat Ratio
Comfort Precision
Typical room SHR 0.65 0.95
Emerson Confidential
Sensible Heat Ratio (SHR)
Occupied areas have loads Telecom equipment rooms have 90-
which are 60-70% sensible 100% sensible loads
(SHR=0.6-0.7) (SHR=0.9-1.0)
Therefore, Comfort AC is Therefore, Precision AC is designed
designed with low SHR with high SHR
Comfort Precision
1.0 Total 1.0
0.9
Latent
0.6
Sensible
Emerson Confidential
Air Movement
Precision A/C
600
Comfort A/C
400
200
CFM / Ton
Air Flow
Emerson Confidential
Assumed 35 Ton Sensible Load
Emerson Confidential
Energy Costs
Assumptions
SHR 0.9 Precision
0.6 Comfort
0.75 KW / Ton
US $ 0.10 / KW - HR
Emerson Confidential
Energy Costs
Precision
0.75 KW / Ton X 8760 Hrs X $0.10 / KWHR = $ 730 / Ton
0.9 SHR
Emerson Confidential
Temperature Considerations
People Critical Systems
6
o
2o
21o 27o
22o 24o
Emerson Confidential
Temperature & Battery Life
120
100
% Rated Life
80
60
40
20
0
25 30 35 40 45
Temperature (C)
Emerson Confidential
LIFETIME:Operating Conditions
It is known that an increase in temperature of 10°C halves the lifetime of
equipment for Telecommunications
Lifetime
10
[years]
0
25 35 45 55 Temperature [°C]
Emerson Confidential
Temperature Rate of Change
Comfort Precision
5°F/min 0.15°F/min
Emerson Confidential
MTBF:Operating Conditions
A high operating temperature gradient reduces significantly the MTBF of
electronic components
G) rate of change of
temperature (NOTE 1) °C /min 0,5 0,5 0,5
Emerson Confidential
The ETSI Norm
Electronic equipment is very sensitive to temperature
ETSI norms for Telecommunications:
Temperature [°C] Functional reliability and
60 life cycle requirements
guaranteed
50
40
Functional
30 requirements
assured
20
10 Main functions
jeopardized
0
-10 Relative
0 20 40 60 80 100 Humidity [%]
Emerson Confidential
Humidity Considerations
People Critical Systems
50%
50%
35% 65% 45% 55%
Emerson Confidential
Relative Humidity Limitations
Too High
– Accelerates corrosion
– Condensation
– Fungus (mold)
Too Low
– Static electricity
Emerson Confidential
Controlling Db & Relative Humidity
Thermal insulation
Required to reduce solar heat gain
Vapor barrier
Required to prevent moisture migration thru walls, ceiling and floor
Aluminum foil, polyethylene sheeting, epoxy paint
Seal all openings
Pipe and cable cutouts
Use double doors & maintain site under positive pressure
To increase life of air filters
Emerson Confidential
Air Cleanliness
Emerson Confidential
Precision Applications
Smaller Rooms Still Have the Same Requirements
As Large Rooms Which Are Different Than Comfort
Applications:
– Lower Design Conditions
– Higher Sensible Heat Ratio
– Higher Load Density
– Humidity Control
– Higher Efficiency Filtration
– Year Round Operation
– Redundancy
Emerson Confidential
New ASHRAE Document
“Thermal Guidelines for Data Processing
Environments” - January 2004
– Equipment Environment Specifications
– Facility Temperature & Humidity Measurement
– Equipment and Facility Layout
– Equipment Manufacturers Heat & Airflow Reporting
Emerson Confidential
Participating Equipment Vendors
Cisco Cray Dell
Fujitsu Hitachi H-P
IBM Intel Lucent
Motorola NCR Sun
Unisys
Emerson Confidential
Environmental Conditions Defined
“The conditions for Classes 1 through 4 are the result of
consensus among the many environmental specifications
of manufacturers of IT equipment.”
Recommended
– “Facilities should be designed and operated to target the
recommended range.”
Allowable
– “Equipment should be designed to operate within the extremes of
the allowable operating environment. In addition to the allowable
dry-bulb temperature and relative humidity ranges, the maximum
dew point and maximum elevation values are part of the
allowable operating environment definitions”
Emerson Confidential
Environmental Class Definitions
Class 1
– “Typically a data center with tightly controlled environmental
parameters (dew point, temperature, and relative humidity) and
mission critical operations; types of products typically
designed for this environment are enterprise servers and storage
products.”
Class 2
– “Typically an information technology space or office or lab
environment with some control of environmental parameters
(dew point, temperature, and relative humidity); types of products
typically designed for this environment are small servers, storage
products, personal computers, and workstations.”
Emerson Confidential
Environmental Class Definitions
Class 3
– “Typically an office, home or transportable environment with little
control of environmental parameters (temperature only)
………..”
Class 4
– “Typically a point-of-sale or light industrial or factory
environment……………”
Emerson Confidential
Equipment Environment
Specification
PRODUCT OPERATION
2 50 – 95 68 – 77 20 – 80 40 – 55 69.8
3 41 – 95 NA 8 – 80 NA 82.4
4 41 – 104 NA 8 – 80 NA 82.4
Emerson Confidential
ASHRAE Class 2 Operating Conditions
0.35
Absolute Humidity - lbs / lb
0.3
0.25
100 % RH 50 % RH
0.2
0.1
0.05
0
32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5 102.5
Ambient Dry Bulb Temperature - F
Emerson Confidential
ASHRAE Class 2 Operating Conditions
0.35
Absolute Humidity - lbs / lb
0.3
0.25
100 % RH 50 % RH
0.2
0.15
Allowable Range
0.1
0.05
0
32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5 102.5
Ambient Dry Bulb Temperature - F
Emerson Confidential
ASHRAE Class 2 Operating Conditions
0.35
Absolute Humidity - lbs / lb
0.3
0.25
100 % RH 50 % RH
0.2
0.1
0.05
0
32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5 102.5
Ambient Dry Bulb Temperature - F
Emerson Confidential
ASHRAE Class 2 Operating Conditions
0.35
Absolute Humidity - lbs / lb
0.3
0.25
100 % RH 50 % RH
0.2
0.15
0.05
0
32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5 102.5
Computers
Telecom Industrial
Medical
Emerson Confidential
Problems Due to a Poor Environment
Temperature Swings
– Electronic Components Thermal Stress
– Potential System Life Reduction
Hot Spots
– Thermal Shutdown of System
High Humidity All of these can
– Condensation lead to Downtime
Low Humidity and
– Static Electrical Discharge Subsequent Loss
Dust of Revenue
– Electrical Short Circuits
Emerson Confidential
Air-Conditioning Differences
Comfort - Designed For People
- Emphasis on latent (moist) heat
- 1000 - 2500 hrs/year operation
Emerson Confidential
Heat Load Density
450
400
Comfort AC
350
300
Square Feet
250
per Ton
200
150
100 Precision AC
50
0
Heat Density in an Electronics Application is
3-5 times Higher than Typical Office Area
Emerson Confidential and going higher
Heat Load Density
80 Precision AC
70
60
Watts /
50
sq. ft
40
30
20 Comfort AC
10
0
Heat Density in an Electronics Application is
3-5 times Higher than Typical Office Area
and going higher
Emerson Confidential
Cooling Capacity
Comfort A/C:
Sensible Capacity = 6-7 tons
Latent Capacity = 3-4 tons
Precision A/C:
Sensible Capacity = 8-9 tons
Latent Capacity = 1-2 tons
Emerson Confidential
Condenser
Expansion
Valve Compressor
Evaporator
Emerson Confidential
Comfort Approach
MECHANICAL ROOM
TELECOM
Return Ductwork SWITCH
ROOM
Electrical
Service Thermostat
ON/OFF
TEMPERATURE Reheat
CONTROLS Electrical
Service
Humidifier
Humidistat Raised
EV Water Line Floor
A PO
RA Drain
FILTER
TO
R Supply
Ductwork Supply
Conventional AC Unit
Drain
Electrical Service
Emerson Confidential
NOTE: Air Cooled System Requires Remote Condensing Section
Precision Approach
TELECOM SWITCH ROOM
Return Air
Digital Switch
Mech. Room
Not Required
FILTE Microprocessor
R Controls
Precision
EVAPORATOR
AC
Reheat
Humidifier
Raised Floor
1x Electrical Service
1x Water Line
1x Drain
NOTE: Emerson
Air CooledConfidential
System Supply Air
Requires Remote Condenser
Underfloor Air Distribution
(Preferred)
Digital Switch
Precision
AC
Emerson Confidential
Raised floor
Overhead Distribution
Digital Switch
Precision
Emerson Confidential
AC
Modular Approach #2
Mech. Rm. or
Corridor
TELECOM SWITCH ROOM
Return Air
Plenum
or Duct Digital Switch
Microprocessor FILTE
Controls
R
Precision
AC
EVAPORATOR
Reheat
Humidifier
Raised Floor
1x Electrical Service
1x Water Line
1x Drain
Supply Air
Emerson Confidential
NOTE: Air Cooled System Requires Remote Condenser
Mini-Mate2 Systems
1, 1.5, 2, 3, 5, 8 Tons
Air Cooled
– Self contained
– Outside Prop Fan Condensing Unit
– Inside Centrifugal Fan Condensing Unit
• Close coupled or remote
Water/Glycol Cooled
– Self Contained
– Close coupled or remote condensing unit
Chilled Water
Emerson Confidential
Mini-Mate2 Systems
Self-Contained Systems
– 1 & 1.5 ton
– All chilled water
Emerson Confidential
Mini-Mate2 Systems
Split Systems
– All tonnages
Emerson Confidential
Air Cooled DX
Condenser
Roof
Refrigerant piping
Deluxe System3
Raised
Floor
Emerson Confidential
Chilled Water
Chiller
Pump
Water piping
Deluxe System3
Raised
Floor
Emerson Confidential
Water Cooled
Cooling Tower or
Pump Drycooler
Water Piping
Deluxe System3
Water Cooled
Condensers
Humidifier
Emerson Confidential
Redundant Dual Cooling System
Emerson Confidential
The Liebert Integrated Products Solution
Emerson Confidential
Critical HPAC Facilities
Hiflex
Himod
Emerson Confidential
The Himod Range
4 Basic modules
6 Cooling versions
Dual circuit
Compact solution
Emerson Confidential
Modules and Cooling Capacity
DX = 20-25 kW
CW = 25-45 kW
DX = 26-67 kW
CW = 50-140 kW
Emerson Confidential
A0 Class Safety: Maximum Level of
Fire-Proof Treatment
• Sandwich panels
• CFC free materials
Emerson Confidential
Himod Features
Flexibility
Efficiency
Ease of maintenance
Total reliability
Emerson Confidential
High Efficiency
Innovative fan
High COP
scroll compressors Large coils
EER up to 4.0
for DX units
(>30% in comparison with traditional systems)
Emerson Confidential
Innovative Radial Fan
ESP up to 350Pa
Autotrasformer 20 speeds
Ativibrating mounts
Efficient running
Low noise
Ad-hoc regulation and flexibility
Reliability
Emerson Confidential
Emerson Confidential
Energy Efficiency of the “Plug Fan”
145
467 Pa 0R
PM
462 Pa 12
20
RP
M
7000 Airflow
7000 Airflow
3
Emerson Confidential
HIMOD Range S - EC Fan
ELECTRONICALLY
COMMUTATED
FAN MOTOR
Emerson Confidential
EC Fan Energy Efficiency
2 0 00
1 8 00
n
Fa
EC
1 6 00
1 4 00
In pu t P o w e r [W a tt]
1 2 00
rm er er
fo r t
1 0 00
ot rans Inve
Aut ncy
ue
8 00
e q
6 00 Fr
4 00
2 00
EC fan is 16-38% more efficient
than frequency controller
0
50 0 0 7 00 0 90 00 1 1 00 0 13 00 0 15 0 00 1 7 00 0 19 0 00
a ir flo w [m ³/h]
Emerson Confidential
Himod-S vs Hiflex Energy Savings
Highest ventilation efficiency allows for lowest noise and vibration operation
70
60
50
SPL [dB(A)]
20
10
0
Hirange: Global SPL = 64.2 dB(A)
31,5 63
125
Himod: Global SPL = 61.6 dB(A)
250
500 1000
2000
4000
8000
Frequency [Hz]
Emerson Confidential
Accessories to Customize Special
Applications solutions
Emerson Confidential
Microprocessor Controller
Microface E controller
• Modularity
• Connectivity
Emerson Confidential
Self Setting
Step 1: Self detection & parameter setting
Each unit detects its sensors and components
The system detects number of units and units in
standby
The system detects the number of connected
units automatically
Emerson Confidential
Teamwork:
Teamwork: Mode
Mode 22
Teamwork: Mode 1
Hirobus
Unit 1 Unit 2 Unit 3
Unbalanced
Balanced
SystemSystem
Emerson Confidential
Hiromatic E Benefits
020 SYSTEM SETUP
021 NUMBER OF UNITS 4
022 TEAMWORK MODE 2
023 HM ID NUMBER 1
024 BAUDRATE 20833
025 COMMUNICATION READ/WRITE
026 HM EPROM VERSION WXG 1.60.200
www.eurovent.org
Liebert Himod
y o l
nc tr
ty d a rk o n l
i l i n w o C ve R
a b d u e t o n L e E E
ce R e N t i d d d
r vi i t n it i ca u n o a ie
Se c u - U d if S o l l L r tif
r 6 i
tal l Ci o 1 u m e s t
t F u C e
C
o n a t h w s R 0 7
Fr Du Up De Lo Be EE R-
4
Emerson Confidential
U.S. Clean Air Act Phaseout
Requirements - HCFC-22
January 1, 2010
– “ban on the production and consumption of virgin
chemical unless used as feedstock or refrigerant in
appliances manufactured prior to 1/1/2010”
January 1, 2020
– “ban on production and consumption, except for
specified exemptions”
Emerson Confidential
New European Regulation EEC no.2037/2000
dated 26.06.2000, it is applying from 01.10.2000
Emerson Confidential
Emerson Confidential
Refrigerant Comparisons
Emerson Confidential
Special Applications
• Metrological rooms
• Laboratories
• Microelectronics
• Textile industry
• Paper industry
• Tobacco industry
Emerson Confidential
Circuit logic
Condenser
3-way
Thermostatic modulating
valve valve
Compressor
Evaporator
Emerson Confidential
HIMOD-S Constant Version
Keep environment control
also in case of partial load
Very close control of
temperature and humidity
(±0.3°C; ±2%RH)
Emerson Confidential
Dual Circuit Screw Compressor
Air Cooled Chillers
Chiller
L
Q
Superchiller
L
Q
kW 0 300 400 500 600 700 800 900 1000 1100 1200
Emerson Confidential
Main Features
Integration with indoor air conditioners
Supersaver
@connectivity
Emerson Confidential
Superchiller
Chiller with Freecooling module
Built-in Freecooling section
Emerson Confidential
Control During Compre s s or Ope ra tion
Ambie nt S e ns or
4
t to Inle t Eva pora tor Outle t S e ns or
Te mpe rature Inle t S e ns or
Fre e ze Prote ction
Control
S lide Puls ing
1 2 3
Fre e Cooling Eva pora tor
Inle t S e ns or
DX Fa ns FC Compre s s ors
t to Ambie nt (from P re s s ure )
Actua tor
Emerson Confidential
Control During Fre e cooling Ope ra tion
Ambie nt
4 S e ns or
1 2 3
Fre e Cooling Eva pora tor
Inle t S e ns or
FC Fa ns FC
(from te mpe ra ture )
Actua tor
Emerson Confidential
Control During FC + DX Ope ra tion
Ambie nt
4 S e ns or
1 2 3
Fre e Cooling Eva pora tor
Inle t S e ns or
FC + DX Fa ns FC Compre s s ors
(from P ress ure )
Actua tor
Emerson Confidential
Superchiller
Chiller with Freecooling module
Santiago, Chile
Chiller
Superchiller (-24%)
Emerson Confidential
CW Air Conditioning Systems
Normally in a CW system, each AC unit modulates the
cooling capacity by means of a 3-way valve:
13°C
15°C 15°C
Emerson Confidential
Benefits of System Control Integration
With combined action of intelligent software
and functions of @connectivity
It is possible:
Emerson Confidential
What is @-connectivity
COMUNICATION
Company Intranet IP Network
Ethernet
PROCESS KNOWLEDGE
Easy rules to program
PC allows to
monitor all
INTEGRATION functions of all units
Controll & exchange info w/ and programming
all units in a/c chiller system strategy of
@connectivity
Emerson Confidential
Some function of @connectivity
De-humidification
Safety Working
Emerson Confidential
Examples of @-connectivity
IF heat load decrease: “Supersaver
” - SUPERCHILLER
MATRIX 10°C
HIMOD - chilled water
> + Freecooling!!!
20°C 20°C
Emerson Confidential
Process at FULL LOAD
Set Point
26 25 24 23 22 15 °C 10 °C
Room Temperature
Percentage of water in the AC unit
100% NO by-pass
23 23
100% 100%
22……...26 22……...26
70%
25 25
50%
100% 22……...26 100% 22……...26
30%
24 24
0% FULL by-pass
100% \ 22……...26 100% 22……...26
Emerson Confidential
Process at 50% LOAD Standard Chiller
Set Point
26 25 24 23 22 12.5 °C 10 °C
Room Temperature
Percentage of water in the AC unit
100% NO by-pass
23 23
30% 30%
22……...26 22……...26
70%
25 25
50%
30%
24 24
50% 50%
\ 22……...26 22……...26
0% FULL by-pass
Emerson Confidential
Process at 50% LOAD Matrix/Himod System
Set Point 15 °C
26 25 24 23 22
12.5 °C
Room Temperature
Percentage of water in the AC unit
100% NO by-pass
23 23
50% 50%
22……...26 22……...26
70%
25 25
50%
100% 22……...26 22……...26
100%
30%
24 24
0% FULL by-pass
Emerson Confidential
Integration with HPAC Fan Coils
Liebert HIROSS HPAC indoor units can obtain via ‘Supersaver
System’, higher energy savings and thus the system SEER
The percentage of energy saving can be greater than 35%
This solution does not require any mechanical modification
60
chiller
Energy consumption [MWh]
Superchiller
50
Superchiller + Supersaver
40
30
20
10
0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Emerson Confidential
Shelter & Small Cabinet Applications
Hisp
Hiwall
Hiline
kW 0 5 10 15 20
Emerson Confidential
HiwallTT Main Features
Cooling capacity 5 to 21 kW
“Invest-as-you-grow” design
Hiwall TT
Auto-test software
Emerson Confidential
Autotest & Self-Commissioning
Microface controller
Hiwall TT
Complete automated cycle
– Evaporator fan
– Compressor
– Heaters
– Freecooling damper
– Alarms
No parameter adjustment is needed
No skilled technicians needed
Emerson Confidential
Hiwall TT Main Features
Cooling capacity up to 21 kW
Scroll compressor
Hiwall TT
Thermostatic valve
Emerson Confidential
Hiwall TT New features
“Invest-as-you-grow” design
Hiwall TT
Wall cut-out compatibility
Anti-vandalism grids
Auto-test software
Lift-up capability
Emerson Confidential
Invest The same wall cut-outs fit the whole range
No further modifications from 5 to 21 kW
as You Grow
Hiwall TT
Time Technology KW
Emerson Confidential
Autotest &
Self-Commissioning
Emerson Confidential
Microface 48VDC Control
No DC/DC converter
On Hiwall TT only
Emerson Confidential
Enhanced 48VDC Operation
Emerson Confidential
Economizer Option
Energy Saver
Use outside fresh air to cool down by means of a modulating damper, while the
compressor is on stand by mode
Emerson Confidential
Emergency Cooling Concept
Two DC power “Plug Fans” for higher reliability, redundancy and energy
efficiency
230V ac
22.0
48V dc
Emerson Confidential
Microface 48VDC Control
HiwallTT
No AC to DC converter
Emerson Confidential
Operating conditions of a BTS
with & without Emergency Cooling Hot spots without Emergency Cooling
Room Temp. 60
[°C]
Without Emergency
50 Cooling
40
Outdoor Temp.
30
20
Operating Time [h] 0 0.5 1 1.5 2 2.5
According to the ETSI norms, with “EMERGENCY COOLING” a maximum
temperature gradient of 0,5 *K can be achieved
Emerson Confidential
Noise Level 45 dBa @ 3 mtrs
Emerson Confidential
Small Cabinet Applications
Heat Management
system:
Heat Exchangers or
Active Air Conditioners
Emerson Confidential
HCS4U, Example of Installation
Acoustic attenuator
weather-proof plenum
Emerson Confidential
HCS4U System
– Air discharge: downflow.
– Built-in microprocessor control with adjustable parameters.
– Alarms detection and storage in local memory.
– Fresh air Free cooling (FC) operation, modulating control.
– 48VDC Emergency Cooling (Evaporator fans, FC, control).
– R134a ozone-friendly refrigerant.
– Operating ambient temperature: -20°C to +45°C.
– Maximum ambient temperature: -45°C to +55°C.
– Max. outdoor noise: 50 dB(A) @ 1m (door mounted silencers).
– Sensors: Clogged air filter, airflow loss, indoor, outdoor and supply air temperature.
Emerson Confidential
Liebert Product Range
DataMate
MiniMate
Challenger
Himod
kW 0 10 20 30 40 50 60 70 80 90 100
Emerson Confidential
DataMate
Emerson Confidential
DataMate Flexibility
Emerson Confidential
MiniMate
1 to 8 Tons
Emerson Confidential
MiniMate
Product Features
Scroll compressor
– Energy efficiency
– Higher reliability
Quiet operation
Typical applications
– Data processing
– Telecomm sites
– Hospital rooms
– Clean rooms
– Metrology labs
Emerson Confidential
MiniMate 1 to 8 Tons
Electric Reheat
– Reheat Capacity = Sensible Capacity
SCR Controlled Reheats
– Compressor runs continuously
– Reheat element modulates for very tight temperature control applications
Emerson Confidential
MiniMate
2, 3, 5 & 8-Tons
Up to 2” of External Static
Pressure for Hospitals and
Clean Rooms
Emerson Confidential
MiniMate Key Options
Disconnect Switch
Hot Water Reheat
SCR Reheat
Firestat
Larger Humidifier
Filter Clog Alarm
Smoke Detector
DX & CW Cooling
Hot Gas Bypass
Emerson Confidential
Challenger 3 & 5 Tons
Upflow
For ducted systems Downflow
or free discharge For raised floor
Emerson Confidential
Challenger Product Features
Scroll compressor
– Higher efficiency &
reliability
Serviceable from the front
Infrared humidifier
Coaxial Water Condenser
– Longer life than brazed
plate heat exchanger
Stainless steel fin-tube reheat
– Lower surface temperature
Emerson Confidential
Liebert Product Range
Deluxe DX
Deluxe CW
ICX DX
ICS CW
kW 0 10 20 30 40 50 60 70 80 90 100
Emerson Confidential
Deluxe Product Description
20-100 kW (6-30 ton) Precision Air
Conditioning System for Critical
Electronic Areas:
– Computer Rooms
– Telecommunications
Equipment Rooms
– Process Control Rooms
Emerson Confidential
Deluxe Product Features
Main Features
– Semi-Hermetic Compressor
– A-frame evaporator
– Infrared Humidifier
– 3-stage SS reheat
– 2 levels of controls
– Shell & Tube condensers
Emerson Confidential
Deluxe Product Features
Semi-hermetic Compressors:
– EER 11.7
– Reliability
– Quiet Operation
Optional 4-Step Control
– Tighter Temperature Control
– Higher System Energy Efficiency
Emerson Confidential
4-Step Summary
Benefits
– Temperature Stability
– Less Compressor Cycling, Longer Life
– Better Load Matching
– Longer ‘On’ Cycles
– Slower Rates of Change
– Lower Inrush Currents
– Softer Starts
Emerson Confidential
Deluxe Product Features
4 Step Operation
Step 1 - One Compressor
Unloaded
Step 2 - Both Compressors
Unloaded
Step 3- One Unloaded, One Full
Capacity
Step 4 - Both Compressors Full
Capacity
Emerson Confidential
Scroll Compressor
One Moving Component
– Energy Efficiency
• (11.3 EER)
– Reliability
• 52% Reduction in Failure rate
from Hermetic Compressor it
Replaced
• Liquid Refrigerant Ok
– Quiet Operation
Emerson Confidential
CARLYLE 06D Vs COPELAND SCROLL
L ie b e r t C o r p o r a t io n C a r ly l e C o m p r e s s o r
C AR LY LE 0 6 D V s C O P E LAN D S C R O L L
EER C o m p a r is o n w ith R-22 @ 4 5 F S S T
35
Ca rly le 0 6 D S -H
30
0 6 D ’s a r e 2 to 2 0 % Co pe la nd S c ro ll
25 h ig h e r E E R !
Ty pic al Co pe S - H ??
20
15
10
80 F 90 F 10 0 F 110 F 12 0 F 13 0 F
S A T U R A T E D C O N D E N S IN G , F
Emerson Confidential
Theory of Infrared Humidification
Reflector
Infrared Bulb
Air Flow
Grains of
pure moisture
Infrared humidifier
– Fast response, 6 seconds
– Emits only pure vapor
– Microprocessor based flush/fill rate
– Not conductivity dependent
– Bypass air used
Optional steam canister humidifier
– Water quality affects capacity
– Offered to meet competitive specifications
Emerson Confidential
Deluxe System3
Product Features
Emerson Confidential
Liebert Product Range
Intelecool
Rack Cooler
Datacool
kW 0 10 20 30 40 50 60 70 80 90 100
Emerson Confidential
InteleCool2
1.5 to 5 Tons
Emerson Confidential
InteleCool
Options
– Scroll Compressor
– Aluminum Panels
– DUC o Tele2 Controls
– Right or left hand
Compressor
– Free Cooling Damper
– Economizer
Emerson Confidential
Complete Microprocessor Control
System
Microface E control
Emerson Confidential
Connectivity - the evolution
Hiromatic EVOLUTION
Emerson Confidential
Hiromatic
Hiromatic Evolution
Evolution
New
keyboard
Emerson Confidential
Hiromatic
Hiromatic Evolution
Evolution
M ICRO NEWS
LCD display: 240X64 dots
Back Light Voltage board: improved visibility
New Microcontroller: 80C557 Philips
Emerson Confidential
Answers to be given:
Emerson Confidential
Self Setting
Step 1: Self Detection
Emerson Confidential
Self Setting
Step 2: Self Setting of Control Parameters
according:
Available Components
Emerson Confidential
Answer : Self Setting
How to activate Auto-Setup
Emerson Confidential
Self Setting
The Auto-Setup will calculate permanently:
Teamwork Mode
Emerson Confidential
Self Setting
Teamwork Mode 1:
All Temp and Hum values are shared, all connected
Units work as 1 multi-step unit.
… works perfectly in small and balanced installations
Emerson Confidential
Introducing: The Setup-Assistant.
Emerson Confidential
The Setup-Assistant.
Emerson Confidential
Answer 2: new Features
Hiromatic Menus with Graphical Icons
Online Help available, 175 pages of detailed description
8 days Graphic Data Record for Temperature and Humidity
12 hours Graphic Data Record for Temperature and Humidity
Microface with Real Time Clock, extended E2Prom and RAM
Memory: Status Reports and Graphics are no more lost after
Power Off’s, everything remains stored.
Emerson Confidential
Hiromatic Icons
Emerson Confidential
Answer 3: Self-Diagnostic System
The System monitors itself:
Emerson Confidential
Self-Diagnostic System
Wellness Factor readings:
• Number of components starts
• Number of Power-Off’s
• Average operating time
• Number of Alarms
Emerson Confidential
Self-Diagnostic System
Example: Information on Compressor 1
Registered Components:
Fan(s)
Compressors
Heaters
Humidifier
Emerson Confidential
Self-Diagnostic System
The result of Wellness Calculation leads to the „Next
Maintenance Calculation“
Emerson Confidential
Next Maintenance Indication
Main Indication Window on Display
Emerson Confidential
Summary
Hiromatic E with Icons
175 pages of Online-Help
Easy Setup using the Assistant
Auto-Test
Auto-Setting of Parameters
8 days Graphic Data Record
Component’s behaviour is recorded and gives Wellness-
Feedback
Wellness Calculation results in “Next Maintenance Time”
SMM: Unit gives Values to Mobile Phones
Emerson Confidential
Thank You
Division Logo