Advanced Power System
Advanced Power System
2. The bus-bar zone, for the purpose of protection, includes ……….... , ……… and
…………….
e) bus-bars, fault bus protection, circuit breakers
f) bus-bars, isolating switches, fault bus protection
g) bus-bars, isolating switches, circuit breakers
h) bus-bars, circuit breakers
Problem 3-4
3. The two most commonly used schemes for bus bars protection are ……….. and
………….
a) differential protection, fault bus protection
b) circuit breakers, fault bus protection
c) circuit breakers, differential protection
d) isolating switches, circuit breakers
4. The probability of faults occurring on the line is much more due to their ……..
and ……..
e) smaller length, higher voltage
f) greater length, exposure to atmospheric conditions
g) no proper maintenance, no man in charge
h) greater length higher voltage
Problem 5-6
5. In time-graded overcurrent protection, ………….. discrimination is incorporated.
a) time
b) period
c) distance
d) Length
14. In case of earth fault, the ungrounded neutral system ………………. lead to arcing
ground.
e) does
f) does not
g) can
h) will not
Problem 15-16
15. Grounding transformer is used where neutral …………….. available.
a) is
b) is not
c) is not active
d) neither available or not
18. In Peterson coil grounding, when inductive fault current becomes equal to
capacitive current of the system, then …………………
e) Xc = 3Xl
f) Xc = Xl
g) Xl = 3Xc
h) Xl = Xc
Problem 19-20
19. In voltage transformer grounding ………………. of single phase transformer is
connected between neutral and earth.
a) secondary
b) primary
c) both secondary and primary
d) None
22. When single line to earth fault occurs on an ungrounded neutral system, the capacitive
current in the two healthy phases rises to ……………….. times the normal value.
e) √3
f) √4
g) √5
h) √6
Problem 23-24
23. When single line to earth fault occurs in solid grounding system, the phase to earth
voltage of the remaining two healthy phases remain at ………………..
a) higher phase voltage
b) normal phase voltage
c) lower phase voltage
d) equal phase voltage
24. A 132 kV, 3-phase, 50 Hz transmission line 200 km long consists of three conductors of
effective diameter 20mm arranged in a vertical plane with 4 m spacing and regularly
transposed. Find the inductance on the system.
e) 2.5H
f) 1.3H
g) 1.82H
h) 3.1H
Problem 25-26
25. Refer to the problem # 24; calculate the kVA rating of the arc suppression coil
in the system.
a) 10060kVA
b) 11040kVA
c) 12000kVA
d) 29020kVA
26. A 50 Hz overhead line has line to earth capacitance of 1.2uF. It is desired to use
earth fault neutralizer. Determine the reactance to neutralize the capacitance of
100% of the length of the line.
e) 884.2Ω
f) 884.15Ω
g) 884.19Ω
h) 887.6Ω
Problem 27-28
27. Refer to problem 26; determine the reactance to neutralize the capacitance of
90% of the length of the line.
a) 982.43Ω
b) 985.6Ω
c) 988.7Ω
d) 982.12Ω
28. Refer to the problem 26; determine the reactance to neutralize the capacitance
of 80% of the length of the line.
e) 1106.72Ω
f) 1105.24Ω
g) 1110.6Ω
h) 1108.33Ω
Problem 29-30
29. Calculate the reactance of Peterson coil suitable for a 33kV, 3-phase transmission line
having a capacitance to earth of each conductor as 4.4uF. Assume supply frequency to be 50
Hz.
a) 234.6Ω
b) 236.7Ω
c) 235.8Ω
d) 232.4Ω
32. An ideal location for the sub-station would be at the …………….. of load.
e) centre of gravity
f) near
g) far from centre
h) outside the area
Problem 33-34
33. Pole-mounted sub-stations are used for ………………….. distribution.
a) primary
b) secondary
c) long distance
d) higher voltage
36. For voltages greater than 33kV, ……………. bus-bar arrangement is employed.
e) single
f) duplicate
g) triplex
h) multiple
Problem 37-38
37. The kVA rating of transformer in a pole-mounted sub-station does not exceed
………..
a) 300kVA
b) 400kVA
c) 100kVA
d) 200kVA
43. Power factor correction sub-stations are generally located at the ………….. end
of a transmission line.
a) sending
b) receiving
c) transmission
d) Collecting
46. A 3-phase, 11kV, 10MVA alternator has sequence reactance of Xo= 0.05 p.u., X1=.15p.u.,
and X2-= .15 p.u. If the generator is on no load, find the ratio of fault currents for L-G fault to
that when all the 3-phases are dead short circuited.
e) 1.284Ω
f) 1.555Ω
g) 1.635Ω
h) 1.752Ω
Problem 47-48
47. A 3-phase, 3-wire system has a normal voltage of 10.4kV between the lines. It is supplied
by a generator having positive, negative and zero sequence of 0.6, 0.5 and 0.2 Ω per phase
respectively. Calculate the fault current which flows when a line-to-line fault occurs at the
generator terminals.
a) 885.7A
b) 567.3A
c) 984.5A
d) 793.3A
48. The per unit values of positive, negative and zero sequence reactance’s of a network at
fault are .08, .07 and .05. Determine the fault current if the fault is double line-to ground.
e) j14p.u.
f) j15p.u.
g) j16p.u.
h) j17p.u.
Problem 49-50
49. The operator ‘a’ rotates the vector through ……………. in the anticlockwise
direction.
a) 90°
b) 120°
c) 180°
d) 360°