Vol Stability Slides
Vol Stability Slides
Ph.D. Seminar
Indian Institute of Technology, Bombay
Jignesh M. Solanki
1
What is voltage stability ?
maintain steady acceptable voltages at all buses in the system
a system enters a state of voltage instability when a disturbance, increase
in load demand
inability of a power system to meet the demand for reactive power
a criterion for voltage stability stability is that,
bus voltage magnitude increase as reactive
power injection at the same
bus increase
a system is voltage unstable if,
V-Q sensitivity
2
voltage instability is essentially a local phenomenon
voltage collapse is more complex than simple voltage
instability
3
ILLUSTRATION OF VOLTAGE
INSTABILITY
4
CLASSIFICATION OF VOLTAGE
STABILITY
5
LARGE DISTURBANCE VOLTAGE
STABILITY (LDVS)
It is concerned with systems ability to control voltages
following large disturbances such as system faults, loss of
generator or circuit contingency.
Load characteristics and the interaction of both continuous
and discrete controls and protections.
Determination of LDVS requires the examination of the
non-linear dynamic performance of a system over a period
of time (ULTC and generator field current limiter)
6
For analysis long-term dynamic simulations are required.
A criterion of large disturbance voltage stability, is that,
following a given disturbance and system control actions,
voltage at all buses reach acceptable steady state levels.
7
SMALL DISTURBANCE VOLTAGE
STABILITY (SDVS)
control voltages following small perturbations
load characteristics, continuous control and discrete
control
Basic process a steady state nature
Stability margin, identifying factors influencing stability,
examine wide range of system conditions and large
number of post contingency scenarios.
A criterion for SDVS, V-Q sensitivity
8
TRANSIENT VOLTAGE STABILITY
0 to 10 seconds, transient rotor angle stability
voltage
voltage collapse is caused by unfavorable fast
acting load components (IM and DC converters)
For severe voltage dips the reactive power demand
of IM increases, contributing to V.C
Electrical islanding and under frequency load
shedding resulting V.C. when imbalance is greater
than about 50%.
9
Voltage decays faster than frequency
under frequency relays may not operate
There are incidents where the voltage collapses before
frequency decays to the under frequency load shedding set
points
10
LONGER TERM VOLTAGE STABILITY
2-3 minutes
involves high loads, high power inputs from remote
generation and a sudden large disturbance (lass of
generator or loss of major transmission line)
the disturbance causes high reactive power losses and
voltage sags in load areas
the tap changer sense low voltages and act to restore
disturbance voltages thereby restoring load power levels
11
further sags of transmission voltages.
generator farther away must then provide reactive power
this is inefficient and ineffective
no longer support by generation and transmission system.
partial and complete voltage collapse.
12
RELATION OF VOLTAGE STABILITY
AND ROTOR ANGLE STABILITY
VOLTAGE STABILITY ROTOR ANGLE STABILITY
13
VOLTAGE INSTABILITY IN MATURE
POWER SYSTEM
intensive use of existing generation and transmission.
new generation in load areas and transmission lines from
Amp.
losses = 2700 MVAr
15
V-Q CURVES
voltage security is closely related to reactive power and a
v-q curves gives reactive power margin at the test bus.
V-Q curve sketches showing effect of voltage sensitive loads and tap changers on limit
17
VOLTAGE STABILITY ANALYSIS
DYNAMIC ANALYSIS
18
STATIC ANALYSIS
19
DETERMINATION OF SHORTEST
DISTANCE TO INSTABILITY
increase load from Po,Qo in some direction until an eigen
value of a Jacobian is practically zero.
surface S represents the locus of all combinations of P and
Q which results in a zero eigen value of Jacobian.
P1,Q1 corrosponding to this point is the stability limit
which lies on or extremely near to S.
20
CAUSES OF VOLTAGE COLLAPSE
the load on the transmission lines is too high.
the voltage sources are too far from the load centres.
the source voltages are too low.
large distances between generation and load.
ULTC action during low voltage conditions.
poor co-ordination between various control and protective
systems.
insufficient load reactive compensation.
21
PREVENTION OF VOLTAGE
COLLEPSE
application of reactive power compensating devices
control of network voltage and generator reactive o/p
co-ordination of protection / controls
control of transformer tap changers
undervoltage load shedding
stability margin
spinning reserve
operators' action
22
GENERIC DYNAMIC LOAD MODEL
Pt = V or Pv = c2V2 + c1V + c0
Ps = P0V or Ps = P0(d2V2 + d1V + d0)
where V is the per-unit magnitude of the voltage imposed
on the load
It can be seen that, at steady-state, state variable x of the
model is constant
23
e = Ps – P, must be zero
The transient output is then determined by the transient
characteristics P = xPt
The mismatch between the model output and the steady-state
load demand is the error signal e
This signal is fed back to the integration block that gradually
changes the state variable x
This process is continues until a new steady-state (e=0) is
reached
Pt(V) = V, Ps(V) = P0Va; Qt(V) = V, Qs(V) = Q0Vb
24
LOAD MODELLING
ix3 = ixE = ixM + ixC ; iy3 = iyE + iyN + iyC
Exponential load Polynomial load
P(V3) = Po (V3/V3o) P = Po [aP(V/Vo)2 + bP(V/Vo) + CP]
25
CONCLUSION
Three key concepts of voltage stability are
the load characteristics as seen from the bulk power network
the available means for voltage control at generators and in the
network
the ability of network to transfer power particularly reactive power
from the point of production to the point of consumption
The network steady state loadability limit is not necessarily the voltage
instability limit
Static power flow based analyses of the post disturbance steady state is
the useful method of analyzing longer term voltage stability
The fundamental cause of voltage instability is identified as
incapability of combined transmission and generation system to meet
excessive load demand in either real power or reactive power form
26
Thank You
27
28