CSA Presentation
CSA Presentation
Method
● Introduction
● Open-Loop Control
● Closed-Loop Control
● Single variable control loop
● Type of Control Modes
● Tuning the controller
● Advanced Control Techniques
Introduction
● Many different operations are performed in an industrial machine to manufacture a
product.
● For example, fluids flow through pipes at a certain rate, ingredients fill a vat to a required
level, heat is applied to a vessel to cause a chemical reaction, or a vacuum pressure is
applied to a confined tank to extracts its contents.
● Each one of these operations is referred to as a process.
● Many of these individual processes are combined and run simultaneously to produce a
finished product of a desired quality as rapidly and inexpensively as possible.
● To satisfy these requirements, each process must be precisely controlled, often by some
type of automatic control device.
● The automatic operations performed by an industrial manufacturing machine are
referred to as process control.
Example of Process
Open-Loop Control
● Process control operations are performed automatically by either open-loop or closed-
loop systems. If the process is controlled only by setpoint commands, without feedback
measurements signal, the system is referred to as open-loop system.
● Open-loop control is used in application where simple processes are performed. Timing
functions are often the key factor used to control the operation.
● Examples of an open-loop process machines are cafeteria dishwashers, commercial
laundry machines, and printed circuit board burn-in chambers.
● This equipment runs through a series of timed cycles, which are activated by controller
devices such as relay ladder logic hardware, sequential drum controllers, programmable
controllers, or computers.
● The advantage of open-loop system is that they are relatively inexpensive. Their main
drawback is that without a feedback loop, there are no control capabilities to make
corrections if the process deviates from its required state.
Example of an open-loop system
Closed-Loop Control
● The act of controlling one specific variable within a process through the use
of either an analog or digital control method.
Element of a single variable control loop
● Measuring device.
● Transducer/Transmitter.
● Controller.
● When a step change occurs, the change is not immediate and any
corrective actions made by the loop takes time.
Response time of the instrument
● Time lag can be defined as the time duration in which a change is received at
● Time lag also includes the time it takes for a signal to pass from one instrument
to the other.
There are 6 factors which contribute to instrument time delay, which are:
● When a step change occurs, the loop reacts by altering the manipulated variable.
● However static a change is opposed by the static inertia of the controlled variable
creating a delay.
● Over time the energy will overcome the resistance and produce the desired state.
● This delay reaction is referred to as pure lag.
● A common method to analyse pure lag is to introduce a
step change and observe the response.
DEAD TIME
Dead time is the time between the instant a deviation of the controlled variable occurs and
the instant corrective action begins.
Ways to reduce time reaction in a system
1. Select a controller with features that provide the appropriate control action for a
particular process.
2. Properly tune the controller to optimize the process regulation.
Factor which affect pure lag
The 4 main factors which can affect pure lag:
● Dead time, which is the time between the instant a deviation of the
controlled variable occurs and the instant corrective action begins.
Control Modes:
● On-Off
● Proportional
● Integral
● Derivative
On-Off
● The type of control mode often used for slow acting operations.
● This kind of action controls a final control element that has only two conditions,fully on or fully off the controller
cannot move the final control element to any intermediate position between the two extremes.
● The advantages of the on-off control are that it is the least expensive closed-loop system and the easiest to
design.
● Its limitation is that it cannot vary the controlled variable with precision.
● The controller compares the temperature (controlled variable) to the set point. When the temperature increases
above the set point, the controller turns a compressor (final control element) fully on. As the temperature lowers
below the set point, the compressor is turned off. The controlled variable cycles above and below the set point, as
shown in Figure 15-5(a).
● The drawback of this system is that the rate at which the final control element switches on and off is very high.
This condition can result in excessive wear to equipment. To reduce the switching rate, an on-off differential, or
hysteresis, is programmed into the controller. Also referred to as a deadband, it causes the controller to produce
its on and off signals at different values around the set point.
● For example, a home heating thermostat may have a deadband of 4 degrees. If the temperature setting is 70
degrees, the furnace turns on at 68 degrees and turns off at 72 degrees, as shown graphically in Figure 15-5(b).
The drawback of using a deadband is that the controlled variable will deviate from the set point by a larger amount
than a system that does not use this method.
Proportional Mode
● The error signal is the difference between the measured variable and the set point.
● A small error will cause the output to change by a small amount and a large error will
cause a larger output change. The output of the proportional controller moves the final
control element to a definite position to attain a desired value of the controlled variable.
● The proportional action can be accomplished in two different ways, by the time
proportioning method, and by the amplitude proportional method
Time Proportioning
● The output at the controller is continually switched fully on and fully off, the average voltage produced is varied by
changing the ratio of signal on to signal off.
● The ratio produced by the controller is determined by how much the measured variable differs from the set point
At set point
● The magnitude of the signal is proportional to the size of the error signal. The analog signal produced by a
controller is either a variable voltage or a variable current.
● The controller also has the capability of amplifying the amount at which its output changes in proportion
to the change applied to its input.
● There are two ways to refer to the amplification of a proportional controller:
● Proportional gain which is the ratio of change in output to the change in input
● Proportional band is the percentage change in the controlled variable that causes the final control
element to go through 100 percent of its range
Integral mode
● Integral control mode is a mode which allows the PV(process variable) to return to SP(set point).
● This action is accomplished by repeating the proportional mode so long as the error is still present.
● The main purpose of the integral mode is to eliminate offsets or steady state error.
● The integral mode accomplishes this task by integrating the error over a period of time intervals.
● This process can be defined by the formula:
● KC/TI ∫edt
● KC = Controller gain
● TI = integral constant or reset time
● t = Time
● The integral control action will occur until no errors exist, as the function occurs over a period of time.
● The integral action can also be expressed as:
● Repeats per minute = the number of times the proportional action is repeated per minute.
● Minute per repeats = the number of minutes it takes for a single repeat.
Derivative mode
● Though integral mode is effective at eliminating offset, it is far slower then proportional mode.
● A faster mode compared to proportional mode is derivative mode (rate mode).
● The main function of derivative mode is to speed up controller action, compensating for delays in the
feedback loop.
● It can be expressed by the formula:
● KC*TD*dERR/dt
● Where TD is the derivative or rate time.
● The derivative mode only acts when the error change with time.
● An advantage of derivative mode is that it can reduce the time taken to return PV to SP, however it can
also amplify the affects of noisy signals.
Tuning the controller
Steps:
● Time consuming.
● One mode affects another mode.
● Re adjust component oftenly.
● Time.
● Patience.
● Optimal balance.
● Achieve desired output.
ziegler -Nichols tuning method
In early 1940s,
Two engineers
Graph
The graph provides three different values to determine the proper controller settings:
l. The effective delay (D), which is the time that expires from when the step change is made until the process variable
begins to react. This delay is caused by the process lag, dead time, or both.
2. The process reaction rate, which is defined as how much the process changes per unit of time. This value is
obtained by calculating the slope of the process reaction curve. A curve with a steep slope indicates a faster
reaction rate than a curve with a gradual slope.
3. The unit reaction rate, which is a measure of how much the process reacts for each percent of actuator change. To
determine this value, the size of the step change must be taken from the graph. The size is read as a percentage of
the span.
The reaction curve tuning method performs an open-loop step change with the controller in the manual mode to
obtain process identification information.
Direct curve method
where,
R = Process Reaction Rate
A = Time in minutes
B = Percentage of the process variable
change
Step 6: Calculate the unit reaction rate (RI).
Divide the reaction rate (R) by the percentage of
the actuator change (X).
● First Order Plus Dead Time: The first order reference, pertains to lag time due to the time
constant of the process.
-The dead time refers to the movement from when the final control element begins to change
until the time at which the sensor begins sending a feedback signal to the controller.
● Second Order Process: There are two time constant delays in a second order process. One is due
to the lag time of the process and the response time of instruments in a control loop, such as a
sensor or a transmitter.
Controller autotuning
-Incorporation of PID modes into single loop. To gain adequate control of the system.
- Cascade control is a system that uses two additional components, a sensor, and a controller
to form a second feedback loop.
- Often results in faster. more precise performance than with single loop PID control systems.
Feedforward Control
Feedforward control
Feedforward Control
Feedforward Control
-By measuring a variable that enters a process and by taking corrective action if it is affected by
a disturbance, a deviation of the controlled variable for set point is reduced or eliminated.
-feedback systems determine a correction that needs to be made after the control variable
deviates from the set point.
-only used when no variation from set point can be tolerated in a process or a system is very
slow in responding to corrective action.
Ratio Control
Ratio Control
-Proportionally control the flow of one ingredient based of the amount of flow of another
ingredient.
-The ratio control flow method is used for continuous blending application, or can be
integrated to provide a specified volume for a batch process
Adaptive Control
Adaptive Control
-a device or controller (which has adaptive capabilities) that converts non-linear signal to linear
signal.