Lecture Frequency Control
Lecture Frequency Control
ESE-817
• Control Scale
PRIMARY CONTROL
• Primary Control is more commonly known as
Frequency Response. Frequency Response occurs
within the first few seconds following a change in
system frequency (disturbance) to stabilize the
Interconnection.
• The objective of the primary control is to maintain
the balance between generation and load.
• In control theory, the primary control corresponds
to a proportional controller (P controller).
It is important to remember that Primary Control will not return frequency to normal, but
only stabilize it. Other control components are used to restore frequency to normal.
PRIMARY CONTROL
Governor Action
Load
PRIMARY CONTROL
Governor Action (Governor Control
Mechanism).
• Turbine Governors are the main source of
primary frequency response.
• Governors on generators are similar to cruise
control on your car. They sense a change in
speed and adjust the energy input into the
generators’ prime mover.
PRIMARY CONTROL
Load
The speed of motors in an Interconnection change in
direct proportion to frequency. As frequency drops,
motors will turn slower and draw less energy.
Rapid reduction of system load may also be effected
by automatic operation of under-frequency relays
which interrupt pre-defined loads within fractions of
seconds or within seconds of frequency reaching a
predetermined value.
• System in balance.
• Load increases, but generation is unaffected.
• Energy is taken from the kinetic energy of all
synchronous machines.
• The synchronous machines will rotate slower.
• The frequency decreases.
• Frequency sensors in some power plants detect the
frequency decrease and increase generation in that
power plant until the frequency is stable again.
PRIMARY CONTROL - Overview
GAIN
Example-1 Solution
Example 2:
• One minute after the load increase in example
1, the load decreases by 6 MW. What is the
new frequency going to be?
GAIN
Example 2 — Solution I
Compare to the situation after the load increase
in example 1, i.e.,
• Δf = ΔG/R = 6/200 Hz = 0.03 Hz,
• Load decrease ⇒ Frequency increase
• Hence, the new frequency is
• f = 49.93 + 0.03 = 49.96 Hz.
GAIN
• Example 2 — Solution II
Compare to the situation before the load increase
in example 1, i.e.,
• Δf = ΔG/R = 4/200 Hz = 0.02 Hz,
• Load increase ⇒ Frequency decrease
• Hence, the new frequency is
• f = 49.98 – 0.02 = 49.96 Hz.
LIMITATIONS IN PRIMARY CONTROL