Generator Management Relay: Protection, Metering, and Monitoring Functions For Generators
Generator Management Relay: Protection, Metering, and Monitoring Functions For Generators
Presented by:
2
What a Generator looks like
Generator Protection
3
Generator Protection
4
Overview
5
Why Upgrade? Generator and Transformer
6
Generator Management Relay
Product Overview
• Ideal Protection for Induction and
Synchronous Generators at 25, 50 and 60Hz
• Complete Generator Protection including:
• Generator Stator Differential
• 2 or 3 Zone Distance Backup
• 100% Stator Ground
• High speed sampling, 12 samples per cycle
• Drawout Case Installation
• Powerful Fault Recording: Waveform,
Sequence of Events
• Ethernet and Serial Communications
• Metering of all important parameters
7
Theory
8
Show Generator Theory General Overview and
Typical System from Training CD
9
Generator Protection
System
Ground
Stator
Ground
Exciter
The
"Wild"
G Power
System
Stator
Phase
System
Phase
11
Generator Protection
Overexcitation
Over Open
Power Loss of Field
Loss of Field Circuits
Overexcitation
Overexcitation
Exciter
The
"Wild"
G Power
System
Abnormal
Inadvertent Frequency
Abnormal Energizing,
Frequency Pole Flashover
Loss of
Reverse Breaker Synchronism
Power Failure
– Unwillingness to upgrade:
• Lack of expertise
– To recognize deficiency
– To perform the work
• “Generators don’t trip” (wrong)
• Operating procedures will save the day
13
ANSI/IEEE Standards
• Latest developments reflected in:
– Std. 242: Buff Book
– C37.102: IEEE Guide for Generator Protection
– C37.101: IEEE Guide for AC Generator Ground Protection
– C37.106: IEEE Guide for Abnormal Frequency Protection
for Power Generating Plants
32 Reverse Power
40 Loss of Excitation
51V voltage restraint
51G Ground overcurrent
87 Differential
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
51V voltage restraint
51G Ground overcurrent
87 Differential
• Medium – up to 12.5 MW
16
Small Machine Protection
IEEE Buff Book
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential
• Large – up to 50 MW 17
Large Machine Protection
IEEE C37.102
• Unit Connected,
• High Z
Grounded
32 Reverse Power
40 Loss of Excitation
46 Negative Sequence
49 Thermal Overload
51V voltage restraint
51G Ground overcurrent
64 Ground Relay
87 Differential
18
HYBRID SYSTEM
19
Protection Functions
Protection Functions Include:
• Generator Stator Differential
• Backup Distance Protection
• 100% Stator Ground
• Generator Unbalance
• Loss of Excitation
• Accidental Energization
• Breaker Fail
• Phase Overcurrent – Voltage Restraint
• Neutral Inst. / Timed Overcurrent
• Neg. Sequence Overcurrent
• Under / Over Voltage
• Under / Over Frequency
• Generator Thermal Model
• RTD Temperature
• Overexcitation – Volts/Hertz
20
Generator Protection
21
Generator Protection with GSU Wrap
PTs on Low Side
22
Generator Protection with GSU Wrap
PTs on High Side
23
Generator Protection
PTs on Low Side
24
Desirable Attributes - Generator
25
Desirable Attributes - Generator
26
Line – Ground faults – Delta Connected Generator
27
Line – Ground faults – Wye Connected Generator
28
Protection Functions
Generator Stator Differential
• Stator Phase Differential
• Dual Slope Percent Restraint Operating
Characteristic
• Directional Supervision under saturation
conditions
29
Protection Functions
Voltage Protection
• Phase Overvoltage
• Phase Undervoltage
• Neutral Overvoltage (fundamental)
• Neutral Undervoltage (3rd Harmonic)
• Voltage Phase Reversal
Frequency Protection
• Overfrequency
• Underfrequency Undervoltage Trip Curves
30
Protection Functions
Thermal Protection
• Generator Thermal Model
• RTD Alarming and Tripping
• RTD Biased Thermal Model
Inadvertent Energization
• Prevents Accidentally Closing a Stopped Generator onto a
Live Line
• Armed when Generator is Offline and Voltage is below a pre-set level
Volt/Hertz (Overexcitation)
• Detects changes in the Volts/Hertz ratio of the
generator or associated transformer Loss of Excitation
31
Wiring
32
33
34
35
36
Example
37
Enhanced Security
Prevents Unauthorized Access and Provide Traceability
38