Lecture 1 Refrigerating Machine Reversed Carnot Cycle Simple Vapor Compression Cycle
Lecture 1 Refrigerating Machine Reversed Carnot Cycle Simple Vapor Compression Cycle
WHERE: E W
QR
QA = THE HEAT SUPPLIED
QR = THE HEAT REJECTED T2 = COLD
RESERVOIR
W = THE NETWORK
E = THE THERMAL EFFICIENCY
W = QR – QA T1 = COLD BODY
COP = QA/W
QA
EER = BTU/HR/WATTS OR 3.412 COP
WHERE: W R
QR
QA = THE HEAT ABSORBED FROM THE COLD BODY
OR REFRIGERATION EFFECT.
T2 =
QR = THE HEAT REJECTED TO THE SURROUNDINGS SURROUNDINGS
W = THE WORK DONE OR MECHANICAL ENERGY CONSUMED
COP = THE COEFFICIENT OF PERFORMANCE
EER = THE ENERGY EFFICIENCY RATING
COMPRESSO
TURBINE
R
4 1
EVAPORATO
R
• T-S DIAGRAM OF CARNOT REFRIGERATION 3 T2 = T3 2
PROCESS DESCRIPTION:
T1 = T4
1-2 : ISENTROPIC COMPRESSION, S1 = S2 4 1
2-3 : ISOTHERMAL HEAT REJECTION, T2 = T3
3-4 : ISENTROPIC EXPANSION, S3 = S4
4-1 : ISOTHERMAL HEAT ABSORB, T4 = T1
• FORMULAS
1. QA = HEAT ABSORBED AT EVAPORATOR
= T1(S1-S4)
2. QR = HEAT REJECTED AT THE CONDENSER
= T2(S2-S3)
3. W = WORK OF COMPRESSION OR WORK INPUT
= QR-QA
4. COPR = COP OF REFRIGERATOR
= QA/W = T1/(T2-T1)
5. COPHP = COP OF HEAT PUMP
=1/E
= T2/(T2-T1)
• PROBLEMS
= 1 + C – C(
= 1 + C –C(V1/V2)
WHERE C= PERCENT CLEARANCE
V2= DISCHARGE VOLUME
K= 1.304 FOR AMMONIA
9. ADIABATIC COMPRESSION EFFICIENCY,NCI:
NCI= ISENTROPIC WC/ IDEAL WC
10. MECHANICAL EFFICIENCY
NM= INDICATED WORK/BRAKE WORK
• PROBLEM
1. A SIMPLE SATURATED REFRIGERATION CYCLE FOR R-12 SYSTEM OPERATES AT AN
EVAPORATING TEMPERATURE 0F -5C AND A CONDENSING TEMPERATURE OF 40C.
DETERMINE (A) THE REFRIGERATING EFFECT PER KG, (B) THE WORK PER KG, ©
THE HEAT REJECTED AT THE CONDENSER PER KG, (D) THE COP. FOR A
REFRIGERATING CAPACITY OF 1 KW, DETERMINE (E) THE TOTAL HEAT REJECTED
AT THE CONDENSER, (F) THE WORK, AND (G) THE VOLUME FLOW RATE.
ANS: A. 110.8 KJ/KG, B. 22.7KJ/KG, C. 133.5 KJ/KG, D. 4.88, E. 1.206 KJ/S, F. 0.205KJ/S, G.
0.0005866 M3/S
2. A STANDARD VAPOR COMPRESSION SYSTEM PRODUCES 20 TONS OF
REFRIGERATION USING R-12 AS A REFRIGERANT WHILE OPERATING BETWEEN
CONDENSER TEMPERATURE OF 41.6C AND AN EVAPORATOR TEMPERATURE OF
-25C. DETERMINE (A) REFRIGERATING EFFECT IN KJ/KG, (B) THE CIRCULATING
RATE IN KG/S, © THE POWER SUPPLIED, (D) THE COP, (E) THE HEAT REJECTED IN
KW, AND (F) THE VOLUME FLOWRATE IN L/S.
ANS: A. 100.26KJ/KG, B. 0.7022KG/S, C. 25.69 KW, D. 2.74, E. 96.09 KW, F. 92.18 L/S