Transformer Protection in Substation
Transformer Protection in Substation
Mechanical protections
Bucholz main – alarm and trip
• Buchholz OLTC-Trip
• Pressure release valve
• Winding temperature-Alarm(70°C) and Trip(85°C)
• Oil temperature-Alarm(65°C) &Trip (75°C)
PROTECTIONS OF 200MVA#2
Electrical protections
• Differential protection(R/Y/B), REF protection,
• Over Flux-Alarm&Trip ,O/C,E/F (LV )-Areva, Micom P632
• Redundant REF protection:- Alstom, P50 Agile P154
• B/U O/C Protection for Tertiary :Alstom, P50 Agile P154
• Directional E/F and O/C protection: relay(HV side) : Micom P14D,Make Alstom
• Directional O/C protection: relay(LV side) : type CDD, Make Alstom
• Directional E/F protection (LV) :- Alstom, Micom P14D
Mechanical protections
Bucholz main – alarm and trip
• Buchholz OLTC-Trip
• Pressure release valve
• Winding temperature-Alarm and Trip
• Oil temperature-Alarm&Trip
110/66kV 63MVA Transformer
• 2 Nos.
• Make : BHEL.
• Full load dry current(HV):-330.664 A with cooling fan(220.443 A without fan)
• Secondary( L V ) current:-551.107 A with cooling fan (367.405 A without fan)
• Vector group:- YNa0d11
• Percentage Impedance:-35.14% (HV-TV), 10.54% (HV-LV)
• Type of cooling:-ONAF/ONAN
• Normal Tap Position – 3
PROTECTIONS
Mechanical protections
• Main Buchholz
• WTI,OTI
• OLTC Buchholz
• PRV
Electrical Protections
provided in 110 kV side:
• Differential protection (87)-SEL-787
• REF protection (64R) : ER,5B3 Current balance relay
• Over current & Earth Fault Relay (2O/C+1E/F) (51R/B/N):-Type 2TJM10 of
Easun Reyrolle make
Provided in 66 kV side
• Over current & Earth Fualt Relay (2O/C+1E/F) (51R/B/N):-ER, 2TJM10
110/33kV 16MVA Transformer
• Two winding transformer
• On Load Tap Changer having 10 Nos. Of Taps.
• Make : IMP, Bombay.
• Full load dry current:- 83.98 A with cooling fan (52.49 A without fan )
• Secondary( L V ) current:- 279.93 A with cooling fan (174.95 A without fan)
• Vector group:- YNyn0
• Percentage Impedance:-10.57%
• Type of cooling:-ONAN/ONAF
• Normalal Tap Position – 3
• NCT:- mounted internally
PROTECTIONS
Mechanical
• WTI/OTI
• Buchholz
• OLTC Buchholz
• PRV
Electrical
provided in 110 kV side:
• Differential protection (87) relay: type 4C21 for each phase of make ER
• REF Protection (64R) : 5B3 Current balance relay make ER
• Over current & Earth fault relay 50A/B/N – MIT 114 make ER
provided in 33 kV side
• REF Protection (64R) – 5B3 Current balance relay make ER
• Over current and Earth Fault relay 50A/B/N –MIT113 make ER
66 kV / 11 kV , 10 MVA TRANSFORMER NO.1
• The allowable limits will vary with the location on the power system. Typically, the further
away from generation and load, the more phase angle difference can be tolerated.
• Synch-check relays typically do not provide indication of the voltage magnitude, frequency
or phase angle.
• A synch-check relay decides internally whether its conditions for closing are satisfied.
• The synch-check relay will either allow or prevent closing depending on its settings.
• Typical synch-check relay may allow closing if the voltage angle across the breaker is less
than 30°.