Lecture 7 (Chaptr 5)
Lecture 7 (Chaptr 5)
where VR, IR and cos φR are the receiving end voltage, current and power factor
while VS, IS and cos φS are the corresponding values at the sending end.
Performance of Single Phase Short
Transmission Lines
• As stated earlier, the effects of line capacitance are neglected for a short
transmission line. Therefore, while studying the performance of such a line,
only resistance and inductance of the line are taken into account. The
equivalent circuit of a single phase short transmission line is shown in Fig. 5.1
(i). Here, the total line resistance and inductance are shown as concentrated or
lumped instead of being distributed. The circuit is a simple a.c. series circuit.
Let I = load current
R = loop resistance i.e., resistance of both conductors
XL = loop reactance
VR = receiving end voltage
cos φR = receiving end power factor (lagging)
VS = sending end voltage
cos φS = sending end power factor
Cont’d
Figure 5.1
The phasor diagram of the line for lagging load power
factor is shown in Fig. 5.1 (ii). From the right angled
triangle ODC, we get,
Medium Transmission Lines
• In short transmission line calculations, the effects of the line capacitance are
neglected because such lines have smaller lengths and transmit power at relatively
low voltages (< 20 kV). However, as the length and voltage of the line increase, the
capacitance gradually becomes of greater importance. Since medium transmission
lines have sufficient length (50-150 km) and usually operate at voltages greater
than 20 kV, the effects of capacitance cannot be neglected. Therefore, in order to
obtain reasonable accuracy in medium transmission line calculations, the line
capacitance must be taken into consideration.
The capacitance is uniformly distributed over the entire length of the line.
However, in order to make the calculations simple, the line capacitance is assumed
to be lumped or concentrated in the form of capacitors shunted across the line at
one or more points. Such a treatment of localizing the line capacitance gives
reasonably accurate results. The most commonly used methods (known as
localized capacitance methods) for the solution of medium transmissions lines are :
(i) End condenser method (ii) Nominal T method (iii) Nominal π method.
Although the above methods are used for obtaining the performance calculations
of medium lines, they can also be used for short lines if their line capacitance is
given in a particular problem.
End Condenser Method
Cont’d
• In this method, the capacitance of
the line is lumped or concentrated at
the receiving or load end as shown in
Fig. 5.2 This method of localizing the
line capacitance at the load end
overestimates the effects of
capacitance.
• In Fig. 5.2, one phase of the 3-phase
transmission line is shown as it is
more convenient to work in phase
instead of line-to-line values.
Let IR = load current per phase
R = resistance per phase
XL = inductive reactance per phase
C = capacitance per phase
Figure 5.2
cos φR = receiving end power factor
(lagging)
VS = sending end voltage per phase
Cont..
• The *phasor diagram for the
circuit is shown in Fig 5.3.
• Taking the receiving end voltage
VR as the reference phasor,
• we have, VR = VR + j 0
• Load current, IR = IR (cos φR − j
sin φR)
• Capacitive current, IC = j VR ω C
= j 2 π f C VR
• The sending end current IS is the
phasor sum of load current
• IR and capacitive current IC i.e.,
Figure 5.3
Cont..
• IS = IR + IC
• = IR (cos φR − j sin φR) + j 2 π f C VR
• = IR cos φR + j (−IR sin φR + 2 π f CVR)
• Voltage drop/phase = IS Z =IS (R + j XL)
• Sending end voltage, VS = VR +IS Z =VR+ IS (R + j XL)
• Thus, the magnitude of sending end voltage VS can be
calculated.
Nominal T Method
• In this method, the whole line capacitance is assumed to be
concentrated at the middle point of the line and half the line
resistance and reactance are lumped on its either side as
shown in Fig. 5.4. Therefore, in this arrangement, full charging
current flows over half the line. In Fig. 5.4, one phase of 3-
phase transmission line is shown as it is advantageous to work
in phase instead of line-to-line values.
Figure 5.4
Cont..
• The phasor diagram for the circuit is shown in Fig. 5.5. Taking
the receiving end voltage VR as the reference phasor, we
have, Receiving end voltage, VR = VR + j 0
• Load current, IR = IR (cos φ R − j sin φ R)
Figure 5.5
Nominal π Method
• In this method, capacitance of each conductor (i.e., line to
neutral) is divided into two halves; one half being lumped at
the sending end and the other half at the receiving end as
shown in Fig. 5.6. It is obvious that capacitance at the sending
end has no effect on the line drop. However, its charging
current must be added to line current in order to obtain the
total sending end current.
Figure 5.6
Cont..
• The phasor diagram for the circuit is shown in Fig. 5.7. Taking
the receiving end voltage as the reference phasor, we have,
Figure 5.7
Long Transmission Lines
• It is well known that line constants of the transmission line are
uniformly distributed over the entire length of the line.
However, reasonable accuracy can be obtained in line
calculations for short and medium lines by considering these
constants as lumped. If such an assumption of lumped
constants is applied to long transmission lines (having length
excess of about 150 km), it is found that serious errors are
introduced in the performance calculations. Therefore, in
order to obtain fair degree of accuracy in the performance
calculations of long lines, the line constants are considered as
uniformly distributed throughout the length of the line.
Rigorous mathematical treatment is required for the solution
of such lines.
•• Fig. 5.8 shows the equivalent circuit of a 3-phase long transmission line on a phase-
neutral
• basis. The whole line length is divided into n sections, each section having line
constants 1n
th of those for the whole line. The following points may by noted :
• (i) The line constants are uniformly distributed over the entire length of line as is
actually the
case.
• (ii) The resistance and inductive reactance are the series elements.
• (iii) The leakage susceptance (B) and leakage conductance (G) are shunt elements.
• The leakage susceptance is due to the fact that capacitance exists between line and
neutral. The leakage conductance takes into account the energy losses occurring
through leakage over the insulators or due to corona effect between conductors.
Admittance =
• Analysis of Long Transmission Line (Rigorous
method)
Generalised Circuit Constants of a
Transmission Line
Cont’d
Cont’d
• As stated previously, the sending end voltage (VS) and sending
end current (IS) of a transmission line can be expressed as :