Batch - 14 - Protection Scheme of Busbars and Transmission Lines
Batch - 14 - Protection Scheme of Busbars and Transmission Lines
• The relays at A, B and C are set to operate for impedance less than Z1, Z2 and Z3
respectively.
• Suppose a fault occurs between sub-stations B and C, the fault impedance at power
station and sub-station A and B will be Z1 + Z and Z respectively.
• It is clear that for the portion shown, only relay at B will operate.
• Similarly, if a fault occurs within section A B, then only relay at A will operate. In this
manner, instantaneous protection can be obtained for all conditions of operation.
ZONE
In actual practice, it is not possible to obtain instantaneous
protection for complete length of the line due to
inaccuracies in the relay elements and instrument
transformers.
Thus the relay at A would not be very reliable in
distinguishing between a fault at 99% of the distance A B
and the one at 101% of distance A B.
This difficulty is overcome by using ‘three-zone’ distance
protection.
Inthis scheme of protection, three distance elements are
used at each terminal.
The zone 1 element covers first 90% of the line and is arranged to trip
instantaneously for faults in this portion.
The zone 2 element trips for faults in the remaining 10% of the line and for
faults in the next line section, but a time delay is introduced to prevent the
line from being tripped if the fault is in the next section.
The zone 3 element provides back-up protection in the event a fault in the
next section is not cleared by its breaker.
THANK YOU!