Lecture 3 Fire Safety
Lecture 3 Fire Safety
BUILDINGS
FIRE TRIANGLE
FRDM may, in addition to its duties under sub-section (1) perform such other duties
as may be imposed on it by law or as the minister may direct it to perform.
Salient points of ACT 341
Functions of FRDM (Fire Rescue Department
M’sia)
Abatement of fire-hazard
Fire certificate
Power of Director of FRDM
Enforcement
Uniform Building By Laws
1984
BUILDING PLAN APPROVAL
When designing a building plan, an architect
must comply with fire safety requirement.
Compliance with FRDM is one of the
requirement before building plan can be
approved by a LA.
UBBL is the requirement that architects must
adhere to when designing a building plan.
part VII and
VIII of UBBL
Two parts of Fire Fighting scope in
Malaysia:-
1) Passive Fire Protection (Part VII)
which usually under the responsibility of the
Architect
2) Active Fire Protection (Part VIII)
which usually under the responsibility of the
M&E consultant
PFP and AFP are meant to work together during a
fire, not one in place of the other. Both active and
passive fire protection systems can control fires.
FLOWCHART OF BUILDING
PLAN APPROVAL AND
BOMBA REQUIREMENT
Architect submit
building plan to LA
and BOMBA
Then, the BOMBA authority will either approve or ask the Architects to
resubmit the building plan for amendments.
After the Architect gain the approval from BOMBA, then the M&E consultant
will start designing the active protection part for the building.
The letter of approval from BOMBA for the Architects will usually contain an
instruction for the M&E consultants to adhere to the requirements. Even
though the BOMBA authority is different for each state in Malaysia, the
requirements are similar, which must follow the Uniform Building By Law
1984.
The M&E consultant will still have to refer to the Tenth Schedule requirements
in the UBBL to determine types of active fire protection mandatory to the
building design.
PART VII
PART VIII
( FIRE REQUIREMENT)
It is a group of systems that require some amount of action or motion in order to work
efficiently in the event of a fire. Actions may be manually operated, like a fire
extinguisher or automatic, like a sprinkler, but either way they require some amount of
action.
AFP includes fire/smoke alarm systems, sprinkler systems, and fire extinguishers as
well as firefighters. Fire/smoke alarm systems are used to detect whether there is fire
and/or smoke in a building. Sprinkler systems are used to help slow the growth of the
fire. Fire extinguishers and firefighters are used to help put out the fire altogether.
The active protection part is referred as per clause 225
Part 1 in the Uniform Building By-Laws 1984:-
A fire alarm system has a number of devices working together to detect and warn people
through visual and audio appliances when smoke, fire, carbon monoxide or
other emergencies are present. These alarms may be activated automatically from smoke
detectors, and heat detectors or may also be activated via manual fire alarm
activation devices such as manual call points, break glass,
ACTIVE FIRE PROTECTION SYSTEM
fire sprinkler system
1. Fire Extinguisher shall be conspicuously located where they will be readily accessible and
immediately available in the event of fire. Preferably they shall be located along normal paths of
travel, including exits from an area.
2. Fire Extinguisher shall not be obstructed or obscured from view. Exception: In large rooms, and in
certain locations where visual obstruction cannot be completely avoided, means shall be provided to
indicate the location.
3. Fire Extinguisher shall be installed on the hangers or in the brackets supplied, mounted in cabinets,
or set on shelves unless the extinguishers are of the wheeled type.
4. Fire Extinguishers installed under conditions where they are subject to dislodgement shall be
installed in brackets specifically designed to cope with this problem. Subject to physical damage, shall
be protected from impact.
5. Fire Extinguisher mounted in cabinets or wall recesses or set on shelves shall be placed in a manner
such that the extinguisher operating instructions face outward. The location of such extinguishers shall
be marked conspicuously.
Design Standards
Under the Uniform Building By-Laws 1984, the requirement for fire extinguishers are
stipulated under By-Law 227.
Portable fire extinguishers should comply with the following Malaysian Standards :-
MS 1539-3 : 2003 Specification for portable fire extinguishers : Part 3 : Selection
and installation – Code of practice (First revision)
MS 1539-4 : 2010 Specification for portable fire extinguishers : Part 4 :
Maintenance of portable fire extinguishers - Code of practice
MS 1539-6:2010 Specification for Small Disposable Fire Extinguishers of
Aerosol Type
MS 1180 : 1990 Fire Extinguishers Media
Spacing
Generally, any occupant should not need to travel more than 15 metres to
reach a fire extinguishers.
.
WET RISER SYSTEM
Wet Riser System is one of the permanent fire-fighting
installations inside a building that are necessary to assist the
fire brigade to put out fires in the event of a fire.