02 - Basis Stator Earth Fault Protection

The document discusses voltages, currents, and logic for detecting earth faults in electrical systems. It explains how voltages and currents are affected by earth faults in different phases. Diagrams show voltage and current vectors during earth faults. The document also discusses using displacement voltage and earth current measurements to locate faults and setting thresholds for protection.

Uploaded by

Vishnu Patidar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

02 - Basis Stator Earth Fault Protection

The document discusses voltages, currents, and logic for detecting earth faults in electrical systems. It explains how voltages and currents are affected by earth faults in different phases. Diagrams show voltage and current vectors during earth faults. The document also discusses using displacement voltage and earth current measurements to locate faults and setting thresholds for protection.

Uploaded by

Vishnu Patidar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 5

Power Transmission and Distribution

Voltages in Case of an Earth Fault


Energy Automation
Progress. It‘s that simple.
L1
L2
L3

Voltage without earth fault Voltages at the point of an earth fault at phase L1

UL3,E UL3,E = UL31

UE = -UL1,E

M M
UL1,E UL1,E = 0

 UL,E voltage decreases in the faulty


phase (min  0)

UL2,E = UL21  UL,E voltage in the both “healthy” phases


UL2,E  ULx,E ... phase-earth-voltage are increase (max  phase-to-phase)
 UE displacement-voltage
 no displacement voltage (UE = 0)
(can be measured at star point to earth)

Power Automation 1
Power Transmission and Distribution

Currents in the Case of an Earth Fault


Energy Automation
Progress. It‘s that simple.
Model:

IE/3 Equivalent voltage UE at the point of fault


L1
L2
IE =3  IE/3 = 3 UE/ZE
L3
ZE
~ ~ ~ IE IE/3 ... earth fault current in one phase
UE
ZE ... earth impedance at one phase
Vector diagram: earth fault in phase L1

L1
UL3,E
L2
L3
IC 3
3U0 =3UE

IC,2
IC,3
3U0
IE = = 3U0 jCE
1

jC UL2,E
3 UEE IE
=
ZE

Power Automation 2
Power Transmission and Distribution

Correlation from Earth fault Location


Energy Automation
Progress. It‘s that simple. Displacement voltage UE (U0) and earth current IE (3I0) as a function of the fault
location of an earth fault in the machine winding.

UE ZE

UL1,E UL2,E
UL1,E UL2,E

UE
UE

UE
IE = 3
ZE

At faults close to the star-point the displacement voltage and the earth
currents become small

Power Automation 3
Power Transmission and Distribution

Directional Stator Earth Fault Protection - Logic


Energy Automation
Progress. It‘s that simple.

Power Automation 4
Power Transmission and Distribution

Stator Earth Fault Protection – Setting Calc


Energy Automation
Progress. It‘s that simple.

9) 90% Stator Earth Fault Protection

The stator earth fault protection detects earth faults in the stator windings of threephase
phase

10 % of Earth Fault voltage reflected in the NGT Primary = 0.1*11000/1.732

Vp = 635.1 Volts

Vs = 635.1*240/11000

=13.8 Volts with 3 sec Definite time delay goes for trip

Note : The NGT connection is assumed to be 11KV/240V

Power Automation 5