L-9 Analysis of Multistorey Building For Wind Load Part-2
L-9 Analysis of Multistorey Building For Wind Load Part-2
Part-2
MULTISTOREY
BUILDING FOR
WIND LOAD
THEORY OF STRUCTURE-IV (AP-411)
Calculate WIND LOAD at different heights (10m,15m, 20m, 30m )
and floor levels using static method with help of the given data.
GIVEN DATA
•No. of stories=10
•Height of each storey=3m
•Height of the structure =3x10=30m
•Location of the building= Vadodara
•Design life of the structure =50
•Category 3
•Topography=plane with upwind slope less than 3 degee
30M
15M
PLAN ELEVATION
STEP 1
CALCULATING DESIGN WIND SPEED
As per IS 875
part 3
Table 1
Clause 5.3.1
As per IS 875
part 3
Table 2 Clause
5.3.2.2
Vz = 44 X 1 X K2 X 1 10 38.72
VZ VALUE
HEIGHT Vz VALUE Pz VALUE
(m/s) HEIGHT
(m/s) (N/m2)
10 38.72
10 38.72 899.54
15 41.36
15 41.36 1026.38
20 43.12
20 43.12 1115.60
F= Ae x Pd x Cf
• F=wind load
• Ae= effective frontal area obstructing wind, which is identified for
each structure
• Cf =force coefficient
• pd =design wind pressure
FINDING Cf VALUE USING GRAPH
FIND H/B RATIO AND CHECK IF IT IS GREATER OR LESSER THEN 1
( HELPS TO DECIDE WHICH GRAPH TO FIND Cf)
1.25 > 1
USE GRAPH 6A
A / B = 0.62
H/B = 1.25
Cf=1.2
2.CALCULATING VALUE OF FRONTAL AREA (Ae)
Ae = 1 x 6 =6 m2
30M
15M
PLAN ELEVATION
2.CALCULATING VALUE OF DESIGN
LOAD AT DIFFERENT HEIGHT
F = Ae X Cf X Pz F = WIND LOAD
HEIGHT Pz DESIGN PRESSURE
( in N/m) ( in KN/m )
10m
6.58 Km/m
0m
DESIGN
LOADING HEIGHT OF FORCE AT EACH
STOREY FORCE 27.06
LEVEL EACH FLOOR STOREY (KN) 10
KN/m
10 27-30 3 9.02 27.06 26.28 9
25.5 8
9 24-27 3 8.76 26.28