On July 1st, 2022 it was noticed that the HT and LT switchgears in substation SS-53 changed over to the incomer-1. During checking, it was noticed that incomer-2 HT transformer tripped on Buchholtz protection due to low conservator oil level. On observation, the HT transformer-2 conservator level had gone to zero. It was found that the oil drain valve of the Nitrogen Injection Fire Fighting System was open and had drained the oil into the oil pit, causing the low conservator oil level.

Uploaded by

Ganesh Bhandary
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
506 views

NIFPS

On July 1st, 2022 it was noticed that the HT and LT switchgears in substation SS-53 changed over to the incomer-1. During checking, it was noticed that incomer-2 HT transformer tripped on Buchholtz protection due to low conservator oil level. On observation, the HT transformer-2 conservator level had gone to zero. It was found that the oil drain valve of the Nitrogen Injection Fire Fighting System was open and had drained the oil into the oil pit, causing the low conservator oil level.

Uploaded by

Ganesh Bhandary
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 8

ON 1.7.

22 WE HAVE NOTICED ALL HT AND LT SWITCHGEARS IN SS-53 CHANGE OVER TOOK PLACE TO INCOMER-1

DURING CHECKING IT WAS NOTICED INCOMER-2 HT TRANSFORMER GOT TRIPPED ON BUCHOLTZ PROTECTION/
CONSERVATOR OIL LEVEL LOW

ON OBSERVATION HT TRANFORMER-2 CONSERVATOR LEVEL HAS GONE TO ZERO

BOTH 33kV AND 6.6kV TERMINAL BOX INSPECTION CARRIED OUT FOR BUSHING LEAK AND FOUND NORMAL

ON FURTHER CHECKING WE HAVE FOUND OIL DRAIN VALVE OF NIFPS SYSTEM WAS PASSING AND DRAINED OFF
OIL TO OIL PIT
CONSERVATOR
NITROGEN OIL DRAIN VALVE

TCI
V

NITROGEN
TCI
V
BUCHOLTZ
RELAY
NITROGEN
OIL DRAIN VALVE
NITROGEN INJECTION FIRE FIGHTING SYSTEM

PREVENTION OF TANK RUPTURE/ EXPLOSION/FIRE DUE TO INTERNAL FAULT/ ARCING

INSTALLED FOR OIL FILLED TRANSFORMER >=10 MVA

SUPPLIED BY CTR , PUNE HAVING TECHNICAL COLLABORATION WITH ELIN, AUSTRIA

N2 CYCLINDER 68 LITRE WATER CAPACITY 10 M3 GAS AT 150 Kg/Cm2

FIRE DETECTOR HEAT SENSING TEMP 141 DEGC WITH HEAT SENSING AREA 800MM RADIUS

TCIV (TRANSFORMER-CONSERVATOR ISOLATION VALVE/ PRE STRESSED NRV) MIN 60 LITRE/MIN FLOW RATE

USED TO PREVENT FLOW OF OIL FROM CONSERVATOR TO MAIN TANK DURING TANK FIRE

OIL DRAIN PIPE : 80 MM DIA

NITROGEN INJECTION PIPE: 25 MM DIA

N2 REFILL ALARM< 70 KG/CM2