22 WE HAVE NOTICED ALL HT AND LT SWITCHGEARS IN SS-53 CHANGE OVER TOOK PLACE TO INCOMER-1
DURING CHECKING IT WAS NOTICED INCOMER-2 HT TRANSFORMER GOT TRIPPED ON BUCHOLTZ PROTECTION/
CONSERVATOR OIL LEVEL LOW
BOTH 33kV AND 6.6kV TERMINAL BOX INSPECTION CARRIED OUT FOR BUSHING LEAK AND FOUND NORMAL
ON FURTHER CHECKING WE HAVE FOUND OIL DRAIN VALVE OF NIFPS SYSTEM WAS PASSING AND DRAINED OFF
OIL TO OIL PIT
CONSERVATOR
NITROGEN OIL DRAIN VALVE
TCI
V
NITROGEN
TCI
V
BUCHOLTZ
RELAY
NITROGEN
OIL DRAIN VALVE
NITROGEN INJECTION FIRE FIGHTING SYSTEM
FIRE DETECTOR HEAT SENSING TEMP 141 DEGC WITH HEAT SENSING AREA 800MM RADIUS
TCIV (TRANSFORMER-CONSERVATOR ISOLATION VALVE/ PRE STRESSED NRV) MIN 60 LITRE/MIN FLOW RATE
USED TO PREVENT FLOW OF OIL FROM CONSERVATOR TO MAIN TANK DURING TANK FIRE