Chapter 7 Powerpoint
Chapter 7 Powerpoint
Chapter 7:
Solar Energy for Buildings
Cooling energy loads are complicated
Hot roof
TAMB Ti qINT
qSOLAR
qENVELOPE
Ventilation,
qVENT
Infiltration
dehumidification
qA/C
PA/C
Air Conditioner
qREJECTED
AC Cooling Energy Load begins with CDD
Sunrise
S
E β
φ
β = Altitude angle
W
Effect of Sun’s Path on Incident Angles
June 21 Summer
Winter
90-L+23.5o
Dec 21
90-L- 23.5o
South South
(a) Altitude angle at noon (b) Designing an overhang
β
N =90 −L+δ
Effect of roof overhang on
Solar Shading
P
βN
Y
Y = P tan βN
Noon
Shadow line
South
Sizing a Roof Overhang to shade
summer sun, admit winter sun
summer JUNE 21 winter DEC 21
P Y = 2 tan 29o = 1.1 ft
y 2 ft
P=
8 ft tan β N
8 29o
P= = 2.0 ft 1.1 ft
tan(76 )
76o o
Afternoon S
W E Morning
S N sun
sun
1800
1600
South-facing
Daily Insolation (Btu/ft2-day)
1400
East, West-facing
1200
1000
800
600
400
Latitude 40 N
200
Clear sky
0
1
Jan 2
Feb 3
Mar 4
Apr 5
May 6
Jun 7
Jly 8
Aug 9
Sep 10
Oct 11 Dec
Nov 12
Building Orientation
GOOD
Sunset Sunrise BAD
Summer Summer
N
N
plants
plants
W E W E
S S
Sunset Sunrise
Winter Winter
Calculating Solar Gain
Solar Gain:
= 1204 Btu/ft2day x 0.71
= 855 Btu/ft2day
* House without solar 1,108 per year using all 250 ft2 of windows
Note *Rows are calculated values. All other information is data entry
Thermal mass needed if excess solar gain
Need thermal storage, ∆Qs
Solar gains with
large window Total house
area heat loss rate
MN Noon MN
Effect of Mass on indoor temperature
100
14% So. glass, no extra mass
90
14%, extra mass
80
70
Temperature (oF)
60
50
Ambient
40
7% So. Glass, no extra mass
30
20
10
0
6 12 18 24 30
6am Noon 6pm MN 6am
Passive Solar Heating Types
Air Circulation in Passive Solar
Convective Loop or Envelope House
Effect of Passive Gains on Auxiliary
Thermal Index (Btu/ft2-oF-da)
Estimating Solar Performance:
Load Collector Ratio (LCR) method
24(UA) ST
LCR =
Ap
log10 (LCR2 LCR)
SSF =0.18 +0.3
log10 (LCR2 LCR5)
QDEL (Btu/yr) = 24 (UA)ST HDD65 (1-
SSF)
Q = 64 g/d x 365 d/yr x (130 – 55)oF x 1 Btu/lboF x 8.34 lb/gal = 14.6x106 Btu/yr
Tin Cold
Controller Hot
Flow ∆T
Insulation
Absorber plate
Frame Pump
The Flat Plate Collector
η UL “slope factor”
η
F R UL
X = “inlet parameter”
Tp − Tamb T − Tamb
X = in
a. b. I
I
Unglazed,
pool collector
Single-glazed
DHW collector
η
Double-glazed
Space heating
Space Heat
Pool DHW
__ __
__
T in −T amb
η=FR (τα)Kτα −FRU L __
I
__ 100 o
−80 o
F
η=0.75 ⋅0.93 −1.18 Btu hr Fft
o 2
2
=0.55 =55%
166 Btu hrft
A(ft 2 )
=
(
gal /day )⋅8.34 lb gal ⋅1Btu lb oF ⋅∆ T oF
=
64 ⋅8.34 (
140 −60)
=46 ft 2
Insolation(
Btu / ft 2 day )
⋅η Collector ⋅(
1−losses) 1997 ⋅0.55 ⋅0.85
Solar Water Heating Analysis
Evaculated Tube collectors
Batch Water Heater:
Integrated Collector and Storage (ICS)
160
140
T(F) or Insol (Btu/ft2hr)/10
120
Morning
100
80
60 Tamb Evening
40
20 I/10
0
6 9 12 15 18 21 24 27 30