The document provides an overview of the testing procedures for various equipment at the Tricom 50MW Wind Power Project grid station, including: 1. Five sessions are outlined covering testing of equipment like transformers, protection relays, SVC, metering systems, and cables. 2. Procedures for isolator, circuit breaker, and transformer testing are described involving steps like functional testing, commissioning, and insulation resistance measurement. 3. Additional details are given for procedures like contact resistance testing, SF6 gas testing, insulation resistance measurement, operating time tests, and AC withstand voltage tests for specific equipment.

Uploaded by

GYUNGHYUN JIA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
158 views

Testing Presentation

The document provides an overview of the testing procedures for various equipment at the Tricom 50MW Wind Power Project grid station, including: 1. Five sessions are outlined covering testing of equipment like transformers, protection relays, SVC, metering systems, and cables. 2. Procedures for isolator, circuit breaker, and transformer testing are described involving steps like functional testing, commissioning, and insulation resistance measurement. 3. Additional details are given for procedures like contact resistance testing, SF6 gas testing, insulation resistance measurement, operating time tests, and AC withstand voltage tests for specific equipment.

Uploaded by

GYUNGHYUN JIA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 17

WELCOME at

HDEC Wind Power Project


132kV Grid Station

Project Name: Tricom 50MW Wind Power Project


Client: Tricom Wind Power Private Limited
Contractor: Hydrochina International Engineering Co., LTD
Session 1 Session 2 Session 3 Session 4 Session 5
Single Line Diagram CT and PT Transformer Protection Relays SVC, SA, Metering
system and power
cables
Isolator, C.Bs diff Testing of CT and PT Transformer Testing Testing of relays SVC Testing

Distance (SOTF, STUB, SA Testing


Isolator and Circuit AR, VT Fail, PSB, PUTT)
Breaker Testing

C.B Functional Testing Primary and Secondary Commissioning Differential, OC EF, BF Control and power
Injection Procedure Protection (DTT), BB cable testing
Commissioning Protection
Procedure
Marshalling
Loop Testing
Configuration of Relays

Interlocking Scheme Earth Mesh Testing Battery Bank and Pilot Protection Scheme Switchgear Testing
battery charger
Local/Remote operation Commissioning Trip Circuit Verification

Alarms and Indications


Single Line Diagram – Line Bay
Equipment List

1. Surge arrestor (4)

2. CCVT (2)

3. Line trap (12)

4. Isolator with Earth Switch (5)

5. CT (9)

6. Circuit Breaker (11)


Isolator with earth switch Circuit Breaker
1. Isolate object (C.B, TF) at Current Zero Condition 1. Use to isolate object (Line, TF) in fault condition
2. Operates automatically (relay command)
2. Does not operate automatically
3. Use for maintenance work 3. Use for Protection

4. Earth switch safety and ground the induction and


trap charge.
5. Reroute Power flow

Any other difference??


Disconnector Switch Testing
1. Measurement of Contact Resistance
2. Measurement of Insulation Resistance
3. Operating Time Test
4. Interlocking between Isolator and earth switch
5. AC withstand Voltage Test
Isolator/Disconnector Switch
1. Measurement of Contact Resistance
IEC 62271-102, IEEE C37.35
 Purpose
i. Key purpose is to measure resistance between contacts.
ii. It will also show that alignment of isolator is perfect

 Procedure
i. Connect power cables and sensing leads at both male
and female terminals.
ii. Inject 100A current.
iii. Test set will show calculated value using Ohm law
formula.
iv. Value should be in (<80μΩ)
Isolator/Disconnector Switch
2. Measurement of IR Test
IEC 62271-102
 Purpose
i. To measure the insulation level between live part to ground
 Procedure
• Connect power cables at top of the isolator and steel structure
or ground.
• Inject 5kV voltage
• Measure resistance value at 15 sec and 60sec to calculate form
factor value.
• Value should be in GΩ and form factor more than 1.

3. Operating Time Test


4. Interlocking between Isolator and earth switch
5. AC withstand Voltage Test

IEC 60060-3
 Purpose
i. To measure the effectiveness of insulation level

 Procedure
• Connect power cable at top of the object and other cable to the ground.
• Short and ground other phases which are not under testing
• Increase voltage gradually till our required voltage, and then start time.
• Measure leakage current, there should no flashover.
• Reduce voltage slowly to zero after testing
• Before opening connections, use earthing rod for discharging current.
• After Hi-pot testing, measure IR value as well.
SF6 Circuit Breaker
Standard: IEC 62271, IEEE/ANSI C37-09

1. Open-Close Timing Test, Duty cycle


Contact Resistance

2. Contact Resistance
SF6 Gas Test

Timing Test
IR Test

3. SF6 Gas test (Moisture, Dew Point)


Test

4. Measurement of Insulation Resistance Test


5. Coil Resistance
6. Spring Charging time
7. AC Withstand Voltage test
Purpose
i. Verify C.B opening and closing time.
Testing Procedure
i. Open isolators from both ends
ii. Connect sensing leads on all poles
iii. Connect opening and closing circuit of C.B with testing set for
trigging.
iv. Trigger test set for open and close time
v. Write down observed values and take print out as well

Timing Test
vi. Open time would be 25-35ms & close time 70-90ms
Resistance
SF6 Gas Test
IR Test

Contact

Circuit Diagram
Purpose
i. Verify resistance between male and female contact is within limit.
 Testing Procedure
i. Open isolators from both ends
ii. Connect sensing leads and current leads at both ends of C.B
iii. Inject 100A current
iv. Write down observed values and take print out as well
v. Test set will use Ohms law for calculation.
R=V/I
vi. Resistance value should be <100μΩ, manufacturer and voltage level

Resistance Test
SF6 Gas Test

Timing Test
IR Test

Circuit Diagram

Contact
Purpose
i. To verify that SF6 gas (Dew point and Purity) is as per Specification.
Procedure
i. Connect testing set with SF6 breaker.
ii. Testing set will automatically measure both dew point and purity
of SF6 gas
iii. Observe the measured values
iv. Pump back the SF6 gas sample from testing set to breaker.

Contact Resistance
IR Test

SF6 Gas Test

Timing Test
Test
Measurement of Insulation Resistance Test
Purpose
i. To measure the ohmic value of the insulation, which will show isolation level b/w Objects
Procedure
i. Open both sides isolators
ii. Connect power cables at top of the breaker and steel structure or ground.
iii. Inject voltage as per specifications, 5kV
iv. Measure resistance value at 15 sec and 60sec to calculate form factor value.
v. Value of FF should be more than 1.

Contact Resistance

Timing Test
SF6 Gas Test
IR Test
Circuit Diagram

Test
5. AC withstand Voltage Test

IEC 60060-3
 Purpose
i. To measure the effectiveness of insulation level

 Procedure
• Isolate equipment from other devices
• Short and ground other phases which are not under testing
• Connect power cable at top of the object and other cable to the ground.
• Increase voltage gradually till our required voltage, and then start time.
• Measure leakage current.
• Reduce voltage slowly to zero after testing
• Before opening connections, use earthing rod for discharging current.
• After Hi-pot testing, measure IR value as well.
Commissioning of Circuit Breaker
1. DMM
2. Equipment Drawing
3. Scheme Drawings
4. Termination Plan

Pole Discrepancy Anti-Pumping feature


Function
01 Pole discrepancy function confirms that
all poles have been closed, if any pole 02 This feature confirms that there is
no permanent command for
remains open, this feature opens other closing.
two poles as well.

SF6 Gas Lockout

03 SF6 gas lock helps to generate


alarm and lockout the C.B if gas
pressure gets low to specific value
5.5 bar alarm and 5 bar lockout

Trip Circuit verification AC supply, heater, lighting


As there are two tripping coils and AC supply is used for lightning and
04 one closing coils. Make it sure that
C.B trips through both coils.
05 sockets. And heater is used to
make cabinet temperature
nominal in winter.