Chapter 2 (Transformer)
Chapter 2 (Transformer)
Transformer
Introduction
What is a transformer ?
It is a stationary electrical device that transfers
electrical power from one circuit to another by magnetic
coupling.
It does so without change of frequency and without any
moving parts.
Transformer works only with AC .
There are two or more stationary electric circuits that
are coupled magnetically.
1
Why do we need transformers?
The most important tasks performed by transformers are:-
a. Changing voltage and current levels in electrical power
systems
b. Matching source and load impedances for maximum
power transfer
c. Electrical isolation (isolating one circuit from another)
2
Cont….
3
Transformer Classification
4
Cont…
In terms of their function
1 - Power transformer
2 - Distribution transformer
3 - Measuring transformers
A) Voltage transformer
B) Current transformer
4 - Autotransformer- Tapped autotransformer
5
Power Transformer
It is a power transformer
connected to the output of
a generator and used to
step its voltage up to the
transmission level.
6
Power Transformer
8
Distribution transformer
Transformers smaller than 500 kVA are generally
called distribution transformers. Pole-top and small,
pad-mounted transformers that serve residences and
small businesses are typically distribution
transformers.
A step-down transformer receives energy at a higher
voltage and delivers it at a lower voltage for
distribution to various loads.
The usual consumer voltage requirement is 220v or
400v.
9
Measuring transformers
A)Voltage Transformer
Voltage transformers are used where the voltage of an
AC circuit exceeds 750 V as it is not possible to
provide adequate insulation on measuring instruments
for voltage more than this.
10
B)Current Transformer
11
Autotransformer :- tapped autotransformer
Transformers having only one winding are called
autotransformers,
An autotransformer has the usual magnetic core but
only one winding, which is common to both the primary
and secondary circuits.
12
According to transformer design or
construction
Based on the construction
transformer are two types
a) Shell type transformer
- In this type, the laminated
insulated sheet iron core
a) shell-type transformer
surrounds the copper
windings.
b) Core type transformer.
- In this type, the copper
windings surround the
laminated sheet iron core.
b) Core-type transformer
13
The Magnetic Circuit
15
Three-Phase Core Form and Three-Phase Shell Form
16
In terms of cooling
The cooling of a transformer depends upon the application.
Transformers intended for indoor use are primarily of the dry type but
can also be liquid immersed. For outdoor use, transformers are usually
liquid immersed
1)Air Cooling For Dry Type Transformers
-It is used for transformers that use voltages below 25KV.
a) Air natural Type (A.N.)
- This type of Transformer Cooling method applies to dry type transformer of
small rating.
- As power ratings increase, transformers are often cooled by forced-air cooling.
b) Air Forced type (A.F.).
- The air is forced on to the tank surface to increase the rate of heat dissipation.
- The fans are switched on when the temperature of the winding increases above
permissible level
17
2) Cooling For Oil Immersed Transformers
a) Oil Natural Air Natural Type (O.N.A.N.)
- This type of Transformer cooling is widely used for
oil filled transformers up to about 30MVA.
- Heat is transferred from transformer windings and
core to the oil and
- The heated oil is cooled by the natural air.
- Cooling area is increased by providing the cooling
tubes.
18
Oil Natural Air Natural Transformer Cooling
19
b) Oil Natural Air Forced Type (O.N.A.F.)
- In higher rating transformers where the heat
dissipation is difficult
- This type of cooling is used.
- Fans are used to forced and air blast on radiators.
20
c) Oil Forced Air Forced Type (O.F.A.F.)
- Oil Natural Air Forced type of cooling is not adequate
to remove the heat caused by the losses.
- Transformers above 60 MVA employ a combination
of Forced Oil and Forced Air Cooling.
21
d)Oil Forced Water Forced (O.F.W.F.)
- This type of cooling is provided for very large transformers
which have ratings of some hundreds of MVA
- This type of transformers is used in large substations and
power plants.
22
The essential elements of a transformer are
a)Two coils having mutual inductance wound on a laminated steel core.
Many transformers have separate coils and contain many turns of wire .
The winding receiving electrical energy from the source is called the
primary winding.
The winding which receives energy from the primary winding, via the
magnetic field, is called the “secondary” winding.
Either the high- or low-voltage winding can be the primary or the
secondary.
b)The two coils are insulated from each other and magnetic core.
A magnetic circuit or core of a transformer is designed to provide a path
for the magnetic field, which is necessary for induction of voltages
between windings.
Special paper and wood are used for insulation and internal structural
support
.
23
Cont…
c) A suitable container for the assembled core and
windings.
d) A suitable medium for insulating the core and its
windings from the container.
e) Suitable brushings for insulating and bringing out the
terminals of windings from the container
24
Accessories Of Transformer
Conservator
This is an expansion tank. It function is to keep the
transformer tank full of oil irrespective whether
expansion or contraction of oil take place.
It mounted above the transformer and connected to the
tank by a pipe.
Temperature gauge
This indicates temperature of the latest oil in the tank. It
is connected to an alarm.
Oil gauge
This indicates the level of the oil in the tank.
Sometimes it is provided with the alarm contracts when
the oil level falls down below a minimum level, contacts
close and give an alarm. 25
Buckholtz relay
It is a gas operated relay. It is located in the pipe connected to
the conservator.
When the a fault occurs in the transformer gas bubbles are
released and these operate the relay to give an alarm signal.
Breather
To prevent entry of moisture in to the tank, a breather with
silica gel is provided in the transformer.
Silica gel absorbs the moisture and allows only dry air to enter
the tank
26
Working Principle of transformer
When one coil is connected to a source of a.c voltage
an alternating flux setup in the laminated core, most of
which is linked with the other coil in which it produces
mutually induced e.m.f. If the circuit of the second coil
is closed a current flows in it and so electrical energy is
transferred entirely magnetically from the first coil to
the second coil.
27
Hence magnetic flux linked with the secondary coil changes
which induces e.m.f. in the secondary.
28
E.m.f Equation Of Transformer
The induced e.m.f in a transformer is proportional to the
product of number of turns N and the rate of change of
flux.
e= N*d
dt
29
Cont…
The magnetic flux() increases from zero to its
maximum value m in 1/4th of a cycle.
dt=1/4f second
Average rate of change of flux = m =4f mwb/s or
volt 1/4f
Now rate of change of flux per turn means induced
e.m.f in volts.
Average e.m.f /turn =4f m volts
If flux varies sinusoidal, then r.m.s value of induced
e.m.f is obtained by multiplying the average value
with the form factor.
Form factor = r.m.s value = 1.11
Average value 30
Cont…
r.m.s value of e.m.f/turn = 1.11*average value
= 1.11* 4f m
= 4.44f m volt
Now r.m.s value of the induced e.m.f in the whole of
primary winding(E1).
E1 = induced e.m.f/turn*No of primary winding.
= 4.44f N1 m = 4.44f N1BmA
Similarly r.m.s value of e.m.f induced in secondary is
E2 = 4.44f N2 m = 4.44f N2BmA
31
Ideal Transformers
An ideal transformer is a lossless device with an input
winding and an output winding.
It has the following properties:
- No iron and copper losses
- No leakage fluxes
- A core of infinite magnetic permeability and of
infinite electrical resistivity
- Flux is confined to the core and winding resistances
are negligible.
For ideal transformer E1=V1 and E2= V2
The power in ideal transformer V1I1 =V2I2
E1/E2 =V1/V2 =N1/N2 =I2/I1
32
Ideal Transformers
33
The relationships between the input voltage and the output voltage, and between
the input current and the output current, are given by the following equations.
v p t is t
In instantaneous quantities a
vs t i p t
vpt ist Np
a
vst i pt Ns
Vp I
In rms quantities s a
Vs Ip
34
Cont…
Np: Number of turns on the primary winding
Ns: Number of turns on the secondary winding
vp(t): voltage applied to the primary side
vs(t): voltage at the secondary side
a: turns ratio
ip(t): current flowing into the primary side
is(t): current flowing into the secondary side
35
Derivation of the Relationship
36
Power in an Ideal Transformer
37
Theory of Operation of Single-Phase Real
Transformers
P M LP
S M LS
39
The voltage ratio across a real transformer
40
The current ratio on a transformer
41
Magnetization Current
43
44
Impedance Transformation through a Transformer
Consider the following circuit, where a load impedance ZL is
connected in the secondary winding. The RMS values of
current and voltage in the secondary winding are related to the
impedance by
45
Cont…
i.e., When a load impedance ZL is connected across the
secondary winding terminals, the AC source connected on the
input side sees the load impedance magnified by the factor
a2.We say that the load impedance is reflected or referred to
the primary side by the square of the turns ratio a.
46
Cont…
This circuit can be simplified as follows
47
Cont…
This circuit can be simplified as follows
48
Cont…
In a similar manner, it can be shown that if an impedance is
connected on the source side of the circuit (as shown below),
the load sees it changed by a factor of (1/ a2).
49
Cont…
If we look at this circuit from the load side (i.e., as seen by the
load), the voltage of the source and the impedance appear
changed as shown below
50
Impedance Matching
A very important application of transformers is as an
impedance matching device using the concept of “reflected
load”.
Recall that the maximum power transfer theorem states that a
power source delivers maximum power to the load when the
load resistance is equal to the internal resistance of the source.
This can be accomplished by using a transformer to match the
two resistances
52
Cont…
Thus, by choosing the appropriate turns ratio for the
transformer in equation (a), the effective load resistance R’ L
can be made equal to the internal resistance of the source, no
matter what value the actual load resistance RL takes. This
process is called impedance matching. A practical example of
impedance matching in given below.
For example, if the internal resistance of the source is 75Ω,
and the resistance of the load is 300Ω, a transformer with turns
ratio of 1:2 can be used for impedance matching as shown
below.
54
3. Hysteresis losses. Hysteresis losses are associated with the
rearrangement of the magnetic domains in the core during
each half-cycle. They are a complex, nonlinear function of
the voltage applied to the transformer.
4. Leakage flux. The fluxes which escape the core and pass
through only one of the transformer windings are leakage
fluxes. These escaped fluxes produce a self-inductance in the
primary and secondary coils, and the effects of this
inductance must be accounted for.
55
The exact equivalent circuit of a real transformer
Cooper losses are modeled by the resistors Rp and Rs
Leakage flux in a primary winding produces the voltage:
ELp(t)=NdФLP/dt
Since much of the leakage flux pass through air, and air has a constant
reluctance that is much higher than the core reluctance, the primary coil’s
leakage flux is
56
The exact equivalent circuit of a real transformer
Recognizing that the self-inductance of the primary coil is
58
Cont…
59
Approximate equivalent circuit of a transformer
60
Transformer Tests
It is possible to experimentally determine the parameters of
the approximate the equivalent circuit. An adequate
approximation of these values can be obtained with only two
tests….
- Open-circuit test
- Short-circuit test
Open-circuit test
Transformer's secondary winding is open-
circuited.
Primary winding is connected to a full-rated
line voltage.
The primary current on no load is usually
less than 5% of the full load. So copper loss
is very small than the primary loss(I2R)or full
load and there fore can be neglected. Hence
the wattmeter readings give the core loss Pi
of the transformer.
Input voltage, input current, and input power
to the transformer are measured. 61
Short circuit test
Transformer's secondary winding
is short-circuited
Primary winding is connected to a
fairly low-voltage source.
The input voltage is adjusted until
the current in the short-circuited
windings is equal to its rated
value.
Input voltage, input current, and
input power to the transformer are
measured.
Excitation current is negligible,
since the input voltage is very low.
Thus, the voltage drop in the
excitation branch can be ignored.
All the voltage drop can be
attributed to the series elements in
the circuit
62
Determining the values of components
63
Determining the values of components
64
Determining the values of components
65
Determining the values of components
66
Efficiency of transformer
The efficiency of transformer depends on loss.
The loss occurring in a transformer can be divided into two
parts.
a) Copper loss in primary and secondary winding as
(I21R1 +I22 R2 ).
It depends upon the square of the load current.
b) Iron losses in the core due to hysteresis and eddy currents.
Hysteresis loss
The magnetic core of a transformer is subjected to an
alternating magnetization. So far each cycle of e.m.f a
hysteresis loop is traced out.
Hysteresis loss per second(Ph)in watts is given by the
following expression.
67
Cont…
Ph = hBm1.6fV
Where:- h = Hysteresis coefficient.
Bm = Maximum flux density in the core(T).
f = Supply frequency in Hz
V = Volume of the core in m3
Hysteresis loss depends upon
71
Rating of transformer.
As seen cooper loss of a transformer depends on the
current and iron loss on voltage. Hence total loss of
transformer depends on volt-ampere(VA) and not on
phase angle between current and voltage i.e. it is
independent on load power factor. That is why rating
of transformer is in KVA and not in KW.
A transformer is described by its rated apparent
power.
72
Transformer Voltage Regulation
Because a real transformer has series impedance within it, the
output voltage of a transformer varies with the load even if the
input voltage remains constant.
The voltage regulation of a transformer is the change in the
magnitude of the secondary terminal voltage from no-load to
full-load.
%voltage regulation=Vs(no load)-Vs(full load)*100%
Vs(rated voltage)
%voltage regulation=Vp (no load)-Vp (full load)*100%
Vp ( rated voltage)
Where:- Vs = Secondary voltage
Vp= Primary voltage
The purpose of voltage regulation is to determine the percentage
of voltage drop between no load and full load
73
Parallel operation of transformers
The operation of transformers in parallel becomes necessary
owing to the following reasons
i. With two or more transformers operating in parallel, the power
system becomes more reliable. For instance if one transformer
develops fault, it can be removed and the other transformers
can maintain the flow of power, though at a reduced level.
ii. Transformers can be switched off or on, depending upon the
power demand. In this manner, the transformer losses
decreases and the system becomes more economical and
efficient in operation.
iii. The cost of standby (spare) set is reduced when two or more
transformers are installed.
74
Conditions for satisfactory operation of transformers in parallel
75
Cont…
76
For Single Phase Transformers
Only the first four conditions apply as there is no phase sequence and
phase displacement due to voltage transformation.
If the turn-ratios or voltage ratings are not the same, a circulating current
will flow even at no-load.
If the percent impedance or the ratios of resistance to reactance are not the
same, the sharing of load between the transformers when applied will no
longer be proportional to their KVA ratings. Hence the capacities of the
transformers can not be utilized to a full extent.
The total capacity of two paralleled transformers that have unequal percent
impedances is expressed by the relation
ZB
Total capacity S A SB
ZA
Where, SA and ZA are the respective capacity and percent impedance of the
transformer of larger percent impedance and SB and ZB are the respective
capacity and percent impedance of the transformer of smaller percent
impedance. 77
Three phase transformer
A B C
P P P
P S P S P S
I II III
a b c
S S S
Output
Figure (a) 3-phase transformer both windings in star; b) three-pase core-type transformer
79
Three phase transformer
A single-unit 3-phase core-type transformer uses a
three-limbed core, one limb for each phase winding
as shown in Figure b
Actually, each limb has the L.V. winding placed
adjacent to the laminated steel core and then H.V.
winding is placed over the 1.v. winding.
Appropriate insulation is placed in between the
core and 1.v. winding and also in between the two
windings.
80
Three-Phase Transformer Connections
81
Three-Phase Transformer Connections
82
Star-delta (Y-) Connection
I 3aI
V
V I
3 3a
V aI
83
Star-delta (Y-) Connection
84
Delta-Star (-Y) connection:-
85
Delta-Star (-Y) connection:-
86
Delta-Delta (-) Connection
I kI
V
I kI k
V
3 3
87
Delta-Delta (-) Connection
88
Star-Star (Y-Y) Connection
kI
V I V
3 kI V
V 3k
k
89
Star-Star (Y-Y) Connection
90
Cont…
Star VP = VL ÷ √3 VL = √3 × VP IP = IL IL = IP
Delta VP = VL VL = VP IP = IL ÷ √3 IL = √3 × IP
91
Paralleling Three-Phase Transformers
The operation of transformers in parallel becomes necessary
owing to the following reasons :
With two or more transformers operating in parallel, the power
system becomes more reliable. For instance if one transformer
develops fault, it can be removed and the other transformers
can maintain the flow of power, though at a reduced level.
Transformers can be switched off or on, depending upon the
power demand. In this manner, the transformer losses
decreases and the system becomes more economical and
efficient in operation.
The cost of standby (spare) set is reduced when two or more
transformers are installed
92
Conditions for satisfactory operation of transformers in parallel:
94
Operation of three phase transformers in parallel
95
Special type of transformer
Auto-transformer
It is a transformer with one winding only, part of this being
common to both primary and secondary.
Obviously, in this transformer the primary and secondary
are not electrically isolated from each other as in the case
with a 2-winding transformer.
But its theory and operation are similar to those of a two-
winding transformer. Because of its one winding, it uses
less copper and hence is cheaper than the 2 – winding
transformer.
As shown in Fig.(a), AB, is primary winding having N1
turns and BC is secondary winding having N2 turns. By
neglecting iron losses and no-load current,
96
Cont…
97
Advantages of Auto-transformer
It effects a saving in winding material (copper or
aluminum), since the secondary winding is part of the
primary current.
Lower copper loss, therefore efficiency is higher than in
the two winding transformer.
Lower leakage reactance's, lower exciting current.
Variable output voltage can be obtained.
Disadvantages of Auto-Transformer
There is a direct connection between the primary and
secondary sides.
Should an open-circuit develop between points b and c, the
full mains voltage would be applied to the secondary.
The short-circuit current is much larger than for normal two-
winding transformer 98
Instrument Transformers
99
Types of Instrument Transformer
102
Cont…
The secondary winding has very small load
impedance which is the current coil of ammeter. The
primary side has a few number of turns and the
secondary side has large number of turns.
The primary winding carries a full load current and
this current is stepped down to a suitable value which
is within the range of ammeter.
The operation of current transformer differs slightly
from the power transformer. In case of current
transformer, the secondary winding has a very small
impedance or “Burden” , so the current transformer
operates on short circuit conditions.
103
Impedance or burden of Instrument Transformer
Burden across the secondary of an instrument
transformer is also defined as the ratio of secondary
voltage to secondary current.
ZL = secondary voltage/ secondary current
=V/I
The units of burden are ohms
104
Core constructions Current Transformers
In order to minimize the exciting ampere turns
required, the core must have a low reluctance and
small iron losses
The following three types of core constructions are
generally employed :
1. Core type
2. Shell type
3. Ring type
105
Core type
It is rectangular form core type. The laminations are
of L shaped assembled together.
The winding are placed on one of the shorter limbs,
with the primary usually wound over the secondary.
The main advantage of this type of core is that
sufficient space is available for insulation and is
suitable for high voltage work.
106
Shell type
In shell type, the windings are placed at the central
limb, thus it gives better protection to the windings.
107
Ring type
Ring type core is commonly used when primary
current is large. The secondary winding is distributed
round the ring and the primary winding is a single
bar.
It is a joint less core and there is very small leakage
reactance.
108
Types of Current Transformers
As far as the construction of CT is concerned, these
are of following types
1. Bar type CT
This type of CT is placed on the panel board to
measure the current of bus bars. The bus bar whose
current is to be measured is made to pass through CT.
It is of circular or ring type, on which secondary
winding is placed. The ammeter is connected in the
secondary windings.
109
Types of Current Transformers
2. Clamp on / Tong tester
This type of CT can be used with a single conductor. The
core of the CT can be split with the help of a trigger switch
and therefore, the core can be clamped around a live
conductor to measure the current. The single conductor acts
as a primary and the secondary is wound on the core of CT.
The ammeter is connected in the secondary. This is a portable
instrument and generally used in laboratories.
110
Measurement of voltage by voltage or potential
transformer(VT or PT)
The primary winding is connected to the voltage side
to be measured and secondary to the voltmeter.
The function of PT is to steps down the voltage to the
level of voltmeter.
111
Cont…
These are used to measure alternating high voltage by
means of low range voltmeters or for energizing the
potential coils of wattmeter and energy meters.
These types of transformers are also used in relays
and protection schemes.
The high voltage which is to be measured is fed to the
primary of PT, which is stepped down and is
measured by a low range voltmeter on the secondary.
The turns of primary side are more than secondary
side.
112
Difference between CT and PT
The few important points regarding the difference in
the working of current transformer and potential
transformer are given below
1. The current transformer is also known as series
transformer. The secondary of CT is virtually under
short circuit conditions when the primary of CT is
energized.
The potential transformer is also known as parallel
transformer. The secondary of PT can be left open
circuited without any damage being caused either to
the transformer or to the operator.
113
Difference between CT and PT
2. Under normal conditions, the line voltage of the PT is
nearly constant. The flux density and the exciting
current of a PT varies between small range whereas the
primary current and excitation of a CT varies over a
wide range under normal working conditions.
3. The current in the primary of CT is independent of
secondary winding conditions whereas current in the
primary of PT depends upon the secondary circuit
burden.
4. The primary winding of the PT is connected across full
line voltage, whereas the CT is connected in series with
one of the lines and therefore a small voltage exists
across its terminals. However the current transformer
carries full line current. 114
Disadvantages of Instrument Transformer
115
Cont…
116
Application of Current Transformer(CT) and voltage
transformer(VT)
The following are the applications
1. CT and VT are used in panel board of sub station or
grid station to measure the bus bar current or voltage
which is very high.
2. CT and VT are widely used in power measuring
circuits. The current or voltage coil of the wattmeter
is connected with CT or VT.
3. CT and VT are also used in power houses, sub
stations etc. in conjunction with the relays for
protection.
117
Transformer design aspects
Design is a creative physical realization of theoretical concepts
Engineering design is application of science, technology and
invention to produce a machine which can perform a specific task
with optimum economy and efficiency.
The major considerations to develop a good design are
1) Cost
2) Durability
3) Compliance with performance criteria as per the specification.
These requirements are conflicting and usually it is difficult to meet
all of them. It is impossible to design a machine which is cheep and
is also durable at the same time. A machine which is expected to
have long life span must use high quality materials which are
expensive.
118
Transformer design aspects
The basic structural parts of a transformer which engineers should
design carefully are;
- Magnetic parts (iron core)
- Conductor parts (windings)
- Insulating parts (dielectrics)
- Ventilation and cooling parts(thermal)
- Mechanical parts
1. Specifications
In order to design a transformer, a designer needs to know the following
important specifications;
1. Capacity ( power rating) of the transformer, in KVA;
2. Voltage ratings of primary and secondary windings, in KV;
3. Number of phases, 1 - phase or 3 – phase;
4. working Frequency, in Hz;
5. Type of connections in 3 – phase transformers , STAR or DELTA;
6. Tapping, if any
119
Transformer design aspects
7. Type of iron assembly, Core or Shell type;
8. Type of transformer, Power or Distribution;
9. Operating average ambient temperature, in oC; (generally 40oC)
10. Type of cooling to be used;
a) Cooling medium; air, Oil, water
b) Circulation type; Natural, forced
c) Simple cooling, mixed cooling
11. Temperature rise above ambient, depending on insulation class;
12. Voltage regulation;
a) % or P.U. at full load at 75oC unity P.F. or 0.8 P.F. lag
b) impedance, % or P.U.
c) reactance, % or P.U.
13. No – load current;
a) Amperes
b) % 0f rated current at rated voltage and rated frequency;
14. Efficiency, in % or P.U. at full load, ½ load, ¾ load at unity P.F. and 0.8 P.F
120
2. Basic principles
d
e , volts Faraday ' s law
dt
d
e N , volts for N number of turns
dt
121
Single phase transformer components
122
Assembled single phase transformer iron core
123
a. Single phase transformer
Let the basic quantities required for transformer design are designated as
follows;
S – output , KVA
φm - main flux, wb
Bm – max. flux density, wb/m2
δ – current density, A/m2
Agi – gross core area, m2
Ai – net core area = staking factor x gross core area, m2
Ac – area of copper in the window, m2
Aw – window area, m2
D – distance between core centers, m
d – diameter of circumscribing circle, m
Kw – window space factor
f – frequency, Hz
Et – emf per turn, v
124
Cont…
• Np, Ns – number of turns in prim. & second. windings respectively.
• Ip, Is – current in prim. & second. windings respectively, A
• Vp, Vs – terminal voltage of prim. &second. windings, V
• ap, as – area of conductors of prim. & second. windings, m2
• li – mean length of flux path in iron, m
• Lmi – length of mean turn of transformer windings, m
• Gi – weight of active iron, kg
• Gc – weight of copper, kg
• Pi – loss in iron per kg, w (specific iron loss)
• Pc – loss in copper per kg, w (specific copper loss)
Then;
125
Cont…
126
Cont…
127
a) Rating of single phase transformers in KVA
128
b . Three phase transformers
129
Assembled iron core of a 3-phase transformer
130
3. Output equation – EMF per turn of a winding
131
Cont…
132
Optimum Design
133
Cont…
• Design work can now be started by suitably choosing values of B m,
δ, and Kw and determining Ai and Aw.
134
Cont…
135
Assembled magnetic core
136
5. Selection of design constants
• Designing work depends on proper selection of design constants; Bm, δ, Kw and Aw.
137
Cont…
Choice of current density (δ) – Higher values of current density helps to design
a transformer with lower dimensions. However, it is mainly limited by
- heat produced during nominal operation and efficiency of the transformer.
- type of transformer ( Power or distribution) because of different
requirement of i2r and iron losses. Permissible values can be taken from
catalogues considering cooling system to be employed.
Choice of window space factor (Kw) – It is the ratio of copper area in the
window to the total window area. The total window area includes the copper
area, the insulation and open areas for air or oil. The amount of copper and
insulation used depends on the KVA and voltage rating respectively and there
fore, the choice of Kw.
Choice of window dimensions (Aw) - Too a narrow window results in
increased height of window where distance between adjacent limbs/winding
is less. This reduces leakage reactance. If lower height is chosen, the
window width increases resulting increased distance between adjacent
limbs/windings and increased leakage reactance. Thus, height and width of
the window is taken considering desirability of leakage reactance. Usually,
Hw/W w is taken as 2 – 4. Aw = Hw x Ww
138
6. Design of windings
139
Cont…
140
Cont…
• Choice of type of winding – There are different types of windings
employed in transformers such as cylindrical, helical, cross over,
and continuous disc type. Choice of type of winding depends on
voltage and current ratings.
Once the type is properly selected, the winding is designed to fit to
the window dimension with proper provision for cooling ducts,
insulation and clearances.
7. Design of insulation – the fundamental considerations in the design
of transformer insulation are that of voltages between different parts.
i.e. insulation
- between core and LV winding
- between LV and HV windings
- between HV windings on two consecutive limbs
- between yoke and LV as well as HV windings.
Different types of insulators like pressboard, paper, oil immersed paper,
oil, Bakelite, etc can be used 141
Cont…
8. Design of cooling systems – For large power transformers,
tubes and radiators are employed to circulate natural or forced
cooling medium. ( air, oil, water etc.)
• In addition to the above main parts, tank and other
mechanical parts are designed as required depending on the
power and type of the transformer
142
O U
K Y
A N
TH
143