5 Transformer
5 Transformer
Application of Transformers
Generation, Transmission, Distribution &
Heavy Industries
In Generation
11/22/33kV – Step up
Transmission
110/132/220/230/400/765kV
Distribution
66 / 33 /22 /11 kV – Step Down
Core Construction
Three Limb Construction – Core Type
Distribution Transformer
Small Capacity Transformer
Five Limb Construction – Shell Type
Power Transformer
High Capacity – 5MVA & Above
Transformer Winding
Copper Flat / bars
Aluminium Flats
Use of 1 Transformer
In Generation Station
Reduce Space
Reduce level of damage in case of fault
Transportation Limitations
In Hilly areas
Auto transformer
Single Winding Transformer
Voltage Regulation applications
Reduce Cost & Losses
Ideal for
230 KV to 110 KV
400 KV to 110 KV
Parts of Transformer
Core – CRGO Silicon Steel, Laser Scribed
CRGO Silicon Steel, Amorphous
Windings – Copper / Aluminium
Tank, Tank Cover & Cooling Pins
Cooling Fans - Optional
Conservator Tank
Parts of Transformer – Contd.
Breather – Slicagel
Buchholtz Relay
Thermometer
HV & LV Bushing
Heater
Why, Transformer is High?
Transformer is a Static Device
No friction, Windage & Mechanical Losses
Typical Efficiency is 99 to 99.6%
Maximum Efficiency
at20-30% in Distribution Transformer
at 25-40% in Power Transformer
Insulation Used in
Power Transformers
Class A,B,C,F & H are used for Dry
Type
Enamel insulation
Oil immersed Transformer
Coilinsulation by Craft Paper, Manila paper
& Bamboo
Insulating Varnish for impregnating the
windings
Transformer Oil
Methods of Cooling
Air – Small Trs.
Gas
Synthetic Oil
Mineral Oil
Solid Insulation – Cast Resin Tr.
Water Cooled – High Capacity Tr.
Types of Cooling
Acronym Type Size
ONAN Oil Natural Air Upto 30 MVA
Natural
ONAF Oil Natural Air 30 to 60 MVA
Forced
OFAF Oil Forced Air Forced > 60 MVA
Types of Cooling –Contd.
Acronym Type Size
OFWF Oil Forced Water > 100 MVA
Forced
AN Air Natural < 1.5 MVA
Compensation for Voltage Variation
Tap Changing facilities
OFF Load Tap Changers
ON Load Tap Changers (OLTC)
To maintain voltage – Z drop
To compensate line drops
Compensation for Voltage Variation
Tapping Provide on HT Side
IE rule
LT Voltage Varies ± 5%
HT Voltage Varies ± 12.5%
Additional Tapping for Power Transformers
Off Load Tap Changer
Suitable for Small Distribution
Transformer
Tap changing require 5 to 10 minutes
Disturb stability of power system
On Load Tap Changers (OLTC)
Preferred for Power
Transformer
Improve Power System Stability
Impedance Voltage
Impedance Voltage is applied across one
winding of a Transformer
Produce normal full load current to flow thro’
the second wdg., when Short circuited
Determines
The Fault Level
Regulation
Conditions for Parallel
Operation of Transformers
Essential conditions to be satisfied
are
Polaritymust be same
Voltage ratio must be same
Phase Sequence Must be same
Identical vector diagram for Three phase
transformers
% of Impedance preferable same
What happens if the voltage ratios
are not identical?
The difference in voltage will cause
a circulating current through the two
secondary, If they are connected in parallel
This is not be permitted
This current would merely load the
transformer
And heat it up without any useful work
being done
Before paralleling, it is essential
to ensure that there is
No voltage difference between the
terminals to be paralleled
In transformers already in
service
Make sure that the tap positions of
the transformers are correctly set
every time they are put in parallel
Is it necessary Capacities of two Tr.
be Same for parallel operation?
Not Necessary
When different capacities are paralleled
They should share the load in proportion to their
capacities
This can be ensured if the % Z of the two
transformers are nearly the same
Deviation should not be more than ±10 % from the
average % of Z of the two Tr.
How does % of Z affect load
sharing in Parallel Operation?
The % of Z of a transformer determines
The voltage drop between the no load & full load
When two transformers work in parallel the
load current in each will be such that
The voltage drop in both is identical because they
are connected to a common busbar
Transformer with lower % of Z will have a
lesser drop
it will take a greater share of the load
Example
If a 500 KVA and a 1000 KVA Tr. are in
parallel to meet a load of 1050 KVA
The expected load taken by the two
should be 350 KVA and 700 KVA
respectively
If % of Z is in proportion to their
capacities
This will be so if their % of Z is equal
Example
Suppose that the 1000 KVA Tr. takes only
500 KVA instead of its share of 700 KVA,
the 500 KVA unit will have to take 550 KVA
The smaller unit gets overloaded, while the
bigger unit is loaded to half its capacity only
Permitted Size of Transformers
to Be in Parallel
Generally speaking, the ratio of outputs of
transformers working in parallel should not
exceed 3:1
The deviation in % Z should not be more than
±10 percent from the average of the two
Transformers value
Hazards against which a
transformer requires protection?
Overloading of Tr. & Short circuits
Internal faults like loose contacts, faults
between adjacent turns and earth faults in
the windings or leads
Improper design of Tr. or auxiliaries
Avoidedby obtaining equip. from a reputable
manufacturer
Hazards against which a
transformer requires protection?
Insistence on compliance with latest relevant
specification by ISI or BIS
Completion of routine tests prescribed &
Careful inspection before final commissioning
Improper maintenance
Avoided by employing qualified and trained
engineers and staff
Hazards against which a
transformer requires protection?
Hazards of external origin like lightning
surges, system over voltages
This is to ensure proper insulation co-
ordination and to install surge arrestors
having the correct characteristics
Transformer Protection
Transformer is a robust & serviceable
equipment
Which rarely gives trouble, but can be
damaged by negligence.
Protective equipment required
The deciding factor is the size of the tr.
A multiplicity of protective devices is likely to
reduce reliability instead of improving it
The Tr. should be robust in
construction & reliable in operation
This applies to all the connected ancillaries,
like air blowers, oil pumps and trip circuit
batteries
The protective measure for electrical
equipment is that its body should be
solidly earthed
bytwo independent conductors, which are
of adequate capacity
Protection for Indoor
Distribution transformer
Capacities of the Transformer vary
from 5 KVA to 500 KVA
With their primary connected to HT
supply upto 11 kV
Distribution Tr. are protected by
A circuit breaker fitted with an
overload tripping device
A thermal overload release etc
If there is a bank of small Tr., each
Tr. may be protected by
HRC type fuses on LT Side
A circuit breaker on HT Side
Energy Savings
Operating Transformer on Different
Freq. than the Designed
No objection to operate a
Transformer at a Higher Freq.
Flux
density will be lower
Magnetizing current is less
At Low frequency
Core will over saturate
Exciting current will be abnormal
Small Deviation in freq. Permitted up
to 10%
Reduce voltage & De-rate Capacity
Noisy Operation of Transformer
Noise / Hum is due to core expands & contracts
MagnetoStriction Effect
To reduce Hum, the core must be tightly clamped
Due to insulation failure between core
laminations
Flux density must be reduced as much as possible
– Design limitations
Over Voltage / Magnetic Saturation
Effectiveness of Spark/Rod Gap
Simplest form of protecting system due
to over voltage
For Transformer & Switch Gear Bushing
Air gap is set to breakdown if the line
voltage reaches a value of 20% above
the normal voltage of the system
Effectiveness of Spark/Rod Gap
Energy contained in the surge is bypassed
safely to earth
Act as secondary protection if LA fails to
protect
Time delay for spark over is appreciably
high than LA
Disadvantage is arc persist across the gap
Operation of Lightning Arrestor
Consists of series of spark gap & several
non-linear resistance like thyrite,
metrosil
Non-linear resistance – Resistance
inversely proportional to the applied
voltage
Extremely low value when high voltage surge
appears
Operation of Lightning Arrestor