Sanitary Drainage and Vent System Design Example
Sanitary Drainage and Vent System Design Example
For all fixtures, there is a maximum horizontal distance between the fixture trap and a
vent. The distance depends on the pipe size being used. In this case, the plumbing code states
that this distance is 5 ft (1.5 m).
5. DFU. The section of pipe that serves the lavatory and kitchen sink must be sized.
From Table 14.1, the number of fixture units for the kitchen sink being served is 2
DFU and for the lavatory, 1 DFU, for a total of 3 DFU. Referring to Table 14.2, the
minimum pipe size is 1½ in or 38 mm. The maximum horizontal distance from
fixture trap to vent is limited to 5 ft (1.5 m). The accumulated information is listed as
follows.
Bathtub 2 DFU
Lavatory 1 DFU
Total 5 DFU
From Table 14.2 the pipe size is 2 in or 50 mm. Add this information to the tabular
form.