04 ShortCircuitCalculations
04 ShortCircuitCalculations
Page 2
28.06.2008
Steffen Schmidt
Purpose of Short-Circuit Calculations Dimensioning of switching devices Dynamic dimensioning of switchgear Thermal rating of electrical devices (e.g. cables) Protection coordination Fault diagnostic Input data for Earthing studies Interference calculations EMC planning ..
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 3
28.06.2008
Steffen Schmidt
Short-Circuit Calculation Standards IEC 60909: Short-Circuit Current Calculation in Three-Phase A.C. Systems European Standard EN 60909 German National Standard DIN VDE 0102 further National Standards Engineering Recommendation G74 (UK) Procedure to Meet the Requirements of IEC 60909 for the Calculation of Short-Circuit Currents in Three-Phase AC Power Systems ANSI IIEEE Std. C37.5 (US) IEEE Guide for Calculation of Fault Currents for Application of a.c. High Voltage Circuit Breakers Rated on a Total Current Basis.
Page 4 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Short-Circuit Calculations Standard IEC 60909 IEC 60909 : Short-circuit currents in threephase a.c. systems Part 0: Part 1: Part 2: Part 3: Calculation of currents Factors for the calculation of short-circuit currents Electrical equipment; data for short-circuit current calculations Currents during two separate simultaneous line-to-earth short circuits and partial short-circuit currents flowing through earth Examples for the calculation of short-circuit currents
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Part 4:
Page 5
28.06.2008
Steffen Schmidt
Short-Circuit Calculations Scope of IEC 60909 three-phase a.c. systems low voltage and high voltage systems up to 500 kV nominal frequency of 50 Hz and 60 Hz balanced and unbalanced short circuits three phase short circuits two phase short circuits (with and without earth connection) single phase line-to-earth short circuits in systems with solidly earthed or impedance earthed neutral two separate simultaneous single-phase line-to-earth short circuits in a systems with isolated neutral or a resonance earthed neutral (IEC 60909-3) maximum short circuit currents minimum short circuit currents
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 6
28.06.2008
Steffen Schmidt
3-phase
2-phase
1-phase
Page 7
28.06.2008
Steffen Schmidt
Page 8
28.06.2008
Steffen Schmidt
Page 9
28.06.2008
Steffen Schmidt
Short-Circuit Calculations Definitions according IEC 60909 (I) initial symmetrical short-circuit current Ik r.m.s. value of the a.c. symmetrical component of a prospective (available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value initial symmetrical short-circuit power Sk fictitious value determined as a product of the initial symmetrical shortcircuit current Ik, the nominal system voltage Un and the factor 3:
" " Sk = 3 Un Ik
NOTE: Sk is often used to calculate the internal impedance of a network feeder at the connection point. In this case the definition given should be used in the following form:
3 c Un Z= " Sk
Page 10 28.06.2008 Steffen Schmidt
Short-Circuit Calculations Definitions according IEC 60909 (II) decaying (aperiodic) component id.c. of short-circuit current mean value between the top and bottom envelope of a short-circuit current decaying from an initial value to zero peak short-circuit current ip maximum possible instantaneous value of the prospective (available) short-circuit current
NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment at which the short circuit occurs.
Page 11
28.06.2008
Steffen Schmidt
3 3 IB
tB
Page 12
28.06.2008
Steffen Schmidt
Short-Circuit Calculations Definitions according IEC 60909 (III) steady-state short-circuit current Ik r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena symmetrical short-circuit breaking current Ib r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device
Page 13
28.06.2008
Steffen Schmidt
Temperature rise of electrical Initial symmetrical short-circuit current Ik devices (e.g. cables) Fault duration Selective detection of partial short-circuit currents Potential rise; Magnetic fields Minimum symmetrical shortcircuit current Ik Maximum initial symmetrical short-circuit current Ik
Page 14
28.06.2008
Steffen Schmidt
Standard IEC 60909 Simplifications and Assumption Assumptions quasi-static state instead of dynamic calculation no change in the type of short circuit during fault duration no change in the network during fault duration arc resistances are not taken into account impedance of transformers is referred to tap changer in main position neglecting of all shunt impedances except for C0
Page 15
28.06.2008
Steffen Schmidt
Page 16
28.06.2008
Steffen Schmidt
equivalent circuit
ZN Q ZT A ZL
~
I"K
c.U n 3
Operational data and the passive load of consumers are neglected Tap-changer position of transformers is dispensable Excitation of generators is dispensable Load flow (local and time) is dispensable
Page 17 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Short circuit in meshed grid Equivalent voltage source at the short-circuit location real network equivalent circuit
Page 18
28.06.2008
Steffen Schmidt
Voltage Factor c c is a safety factor to consider the following effects: voltage variations depending on time and place, changing of transformer taps, neglecting loads and capacitances by calculations, the subtransient behaviour of generators and motors.
Voltage factor c for calculation of Nominal voltage Low voltage 100 V 1000 V -systems with a tolerance of 6% -systems with a tolerance of 10% Medium voltage >1 kV 35 kV High voltage >35 kV 1.05 1.10 1.10 1.10 0.95 0.95 1.00 1.00
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 19
28.06.2008
Steffen Schmidt
Motors
shall be considered
shall be neglected
at 20C
at maximum temperature
Page 20
28.06.2008
Steffen Schmidt
Page 21
28.06.2008
Steffen Schmidt
Short Circuit Impedances For network feeders, transformer, overhead lines, cable etc. impedance of positive sequence system = impedance of negative sequence system impedance of zero sequence system usually different topology can be different for zero sequence system Correction factors for generators, generator blocks, network transformer factors are valid in zero, positive, negative sequence system
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 22
28.06.2008
Steffen Schmidt
Network feeders At a feeder connection point usually one of the following values is given: the initial symmetrical short circuit current Ik the initial short-circuit power Sk
3 c Un c Un ZQ = = " " Sk 3 Ik
XQ =
ZQ 3 (R / X)3 +
If R/X of the network feeder is unknown, one of the following values can be used: R/X = 0.1 R/X = 0.0 for high voltage systems >35 kV fed by overhead lines
Page 23 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
ZTK = ZT KT general
c max KT = 3 3 ,3 3 3 xT + ,3
KT
00 . 0 00 . 0 33 . 3 3 3 3 3 3 3 3 3
cmax = 333 . cmax = 000 .
xT [%]
The Correction factor is KT<1.0 for transformers with xT >7.5 %. Reduction of transformer impedance Increase of short-circuit currents
Page 25 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
ZGK = ZG KG general
KG = Un c max UrG 3 x sin rG + d
for continuous operation above rated voltage: UrG (1+pG) instead of UrG turbine generator:
Page 26
X(2) = X(1)
Steffen Schmidt Copyright Siemens X(2) = 1/2 (Xd" + Xq") AG 2008. All rights reserved.
E D SE PTI NC
ZS(O) = (tr2 ZG +ZTHV) KS(O) power station with on-load tap changer:
3 3 UnQ UrTLV c max KS = 3 3 UrG UrTHV 3 x x T sin rG + d
power station without on-load tap changers: UnQ U c max K SO = rTLV (3 p t ) UrG (3 pG ) UrTHV + 3 x sin rG + d
Page 27
28.06.2008
Steffen Schmidt
Asynchronous Motors Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents
XM =
ZM 3 (RM / XM )3 +
If R/X is unknown, the following values can be used: R/X = 0.1 medium voltage motors power per pole pair > 1 MW R/X = 0.15 medium voltage motors power per pole pair 1 MW R/X = 0.42 low voltage motors (including connection cables)
Page 28 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
low voltage motors can be neglected if IrM Ik groups of motors can be combined to a equivalent motor ILR/IrM = 5 can be used
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 29
28.06.2008
Steffen Schmidt
Page 30
28.06.2008
Steffen Schmidt
Calculation of initial short circuit current Procedure Set up equivalent circuit in symmetrical components Consider fault conditions in 3-phase system transformation into symmetrical components Calculation of fault currents in symmetrical components transformation into 3-phase system
Page 31
28.06.2008
Steffen Schmidt
(1)
(1)
(1) (1)
(1)
(1)
(1)
(1)
(2) (2)
(0) (0)
(0) (0)
Page 32
28.06.2008
Steffen Schmidt
Calculation of initial short circuit current 3-phase short circuit L1-L2-L3-system L1 L2 L3 ~ ~ ~ -Uf
I sc3 = c Ur 3Z (3 )
Z(1)l
012-system
~
c Un 3
Z(1)r
~
(1) Z(2)r
Z(2)l
~
(2)
Z(0)l
Z(0)r
~
(0)
UL1 =
Uf
fault location
( Uf)
Steffen Schmidt
28.06.2008
Z(1)l
012-system
~
c Un 3
Z(1)r
~
(1)
~
-Uf
Z(2)l
Z(2)r
c U r I sc3 = Z (3 + Z ( 3 ) )
I c U r 3 sc3 = I sc3 3 3Z ( 3 )
U U (3 U ( 3 = c n ) ) 3
~
(2)
Z(0)l
Z(0)r
~
(0)
I sc3 =
fault location
I(0) = 0
I(1) = I(2)
Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Calculation of 2-phase initial short circuit current with ground connection L1-L2-L3-system
L1 L2 L3
Z(1)l
012-system
~
c Un 3
Z(1)r
~
(1)
Z(2)l
Z(2)r
-Uf
E I scE3
3c U r = Z (3 + 3 ( 3 Z ) )
~
(2)
Z(0)l
Z(0)r
~
(0)
I L3 = 3
U L3= a c U L3= a c
Page 35
Un 3 3
Steffen Schmidt
fault location
Un
U (3 U ( 3 = c ) )
Un
= U (3 U ( 3 ) ) 3
28.06.2008
Z(1)l
012-System
Z(1)r
~
(1)
Z(2)l
Z(2)r
-Uf
3c U r Z (3 + Z ( 3 + Z ( 3 ) ) )
~
c Un 3 Z(0)l
~
Z(0)r
(2)
~
(0)
U L3= c
IL2 = 0 IL3 = 0
Page 36
Un 3
fault location
U ( 3 + U (3 + U ( 3 = c ) ) )
I(0) = I(1) = I(2)
Un 3
28.06.2008
Steffen Schmidt
Largest initial short circuit current Because of Z1 Z2 the largest short circuit current can be observed for Z1 / Z0 < 1 3-phase short circuit for Z1 / Z0 > 1 2-phase short circuit with earth connection (current in earth connection)
Page 37
28.06.2008
Steffen Schmidt
S" kQ UnQ
r:3
k3
Calculation of short circuit currents by programs (1/3) Basic equation i=Yu Y: matrix of admittances (for short circuit)
3 Y 3 3 3 Y 3 3 . . . . . . '' = I sci Y i3 . . . . . . 3 Y n3 . . . . . . . Y3 n . Y3 n . . . . Y in . . . . Y nn U3 U 3 . . . Ur c 3 . . . U n
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 39
28.06.2008
Steffen Schmidt
Calculation of short circuit currents by programs (2/3) Inversion of matrix of admittances u = Y-1 i
U3 U 3 . . . Ur = c 3 . . . U n Z 3 3 Z 3 3 . . . Z i3 . . . Z n3 . . . . . . . . Z3 n Z3 n . . . Z in . . . Z nn 3 3 . . . '' I sci . . . 3
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Z ii
Page 40
28.06.2008
Steffen Schmidt
from line i:
c Ur " = Z ii I sci 3
I " = c U r sci 3 Z ii
calculation of all node voltages from there -> calculation of all short circuit currents
Page 41
28.06.2008
Steffen Schmidt
Page 42
28.06.2008
Steffen Schmidt
Page 43
28.06.2008
Steffen Schmidt
Example
Page 44
28.06.2008
Steffen Schmidt
Page 45
28.06.2008
Steffen Schmidt
3 c Un ZI = " Sk
33( 3 kV ) . 3 ZI = 3 GVA
ZI = 33 3 . 33
RI = 33 3 . 33
XI = 33 3 . 33
Page 46
28.06.2008
Steffen Schmidt
Impedance of Transformer
3 Un Z T = uk Sn
Z T = 33 . 3
( 3 kV ) 3 3
3 MVA 3
( 3 kV ) 3 3 R T = 3 3kVA 3 ( 3 MVA ) 3 3
R T = 30 0 . 00 X T = 30 0 . 00
3 Un R T = PkrT 3 Sn
Z T = 33 3 . 33
Page 47
28.06.2008
Steffen Schmidt
K T = 33 . 3 K T = 33 . 3
c max 3 33 x T + . 33 . 3 33 30 0 0 + . . 00
K T = 30 0 0 . 00 Z TK = 33 3 . 33 R TK = 33 3 . 33 X TK = 33 3 . 33
Page 48
28.06.2008
Steffen Schmidt
RL = R' RL = 33 / km 3 km . 3
RL = 33 3 . 33
XL = X' XL = 33 / km 3 km . 3
XI = 33 3 . 33
Page 49
28.06.2008
Steffen Schmidt
R = RI + R TK R = 33 3 + 33 3 . 33 . 33 R = 33 3 . 33
" Ik =
" Ik =
( 33 3 ) 3+ (33 3 ) 3 . 33 . 33
" Ik = 33 . kA
Page 50
28.06.2008
Steffen Schmidt
R = RI + R TK + RL R = 33 3 + 33 3 + 33 3 . 33 . 33 . 33 R = 33 3 . 33
" Ik =
" Ik =
( 33 3 ) 3+ ( 33 3 ) 3 . 33 . 33
" Ik = 33 . kA
Page 51
28.06.2008
Steffen Schmidt
Page 52
28.06.2008
Steffen Schmidt
Peak Short-Circuit Current Calculation acc. IEC 60909 maximum possible instantaneous value of expected short circuit current equation for calculation: ip = 3 Ik "
= 30 + 33 e 3 / X . 0 . 3 R
Page 53
28.06.2008
Steffen Schmidt
Peak Short-Circuit Current Calculation in non-meshed Networks The peak short-circuit current ip at a short-circuit location, fed from sources which are not meshed with one another is the sum of the partial short-circuit currents:
M G
ip3
ip3
ip3
ip3
Peak Short-Circuit Current Calculation in meshed Networks Method A: uniform ratio R/X smallest value of all network branches quite inexact Method B: ratio R/X at the fault location factor b from relation R/X at the fault location (equation or diagram) =1,15 b Method C: procedure with substitute frequency factor from relation Rc/Xc with substitute frequency fc = 20 Hz R R c fc = X Xc f best results for meshed networks
Page 55 28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG 100 MVA RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA RGf = 0,15 Xd" for generators with UrG 1000 V
Page 56
28.06.2008
Steffen Schmidt
" Ik = 33 . kA
R = 33 3 . 33 R / X = 0.0244
X = 33 3 . 33
= 1.02 + 0.98 e 3R / X
= 1.93
" ip = 2 Ik
ip = 21.8 kA
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 57
28.06.2008
Steffen Schmidt
" Ik = 33 . kA
R = 30 0 . 00 R / X = 0.5442
X = 33 3 . 33
= 1.02 + 0.98 e 3R / X
= 1.21
" ip = 2 Ik
ip = 3.4 kA
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 58
28.06.2008
Steffen Schmidt
Page 59
28.06.2008
Steffen Schmidt
Breaking Current Differentiation Differentiation between short circuits near or far from generator Definition short circuit near to generator for at least one synchronous machine is: Ik > 2 Ir,Generator or Ikwith motor > 1.05 Ikwithout motor Breaking current Ib for short circuit far from generator Ib = Ik
Page 60
28.06.2008
Steffen Schmidt
Breaking Current Calculation in non-meshed Networks The breaking current IB at a short-circuit location, fed from sources which are not meshed is the sum of the partial short-circuit currents:
M G
IB3 = I k
IB3= Ik
IB3 = qI k
I B3= qI k
Breaking current Decay of Current fed from Generators IB = Ik Factor to consider the decay of short circuit current fed from generators.
Page 62
28.06.2008
Steffen Schmidt
Breaking current Decay of Current fed from Asynchronous Motors IB = q Ik Factor q to consider the decay of short circuit current fed from asynchronous motors.
Page 63
28.06.2008
Steffen Schmidt
Breaking Current Calculation in meshed Networks Simplified calculation: Ib = Ik For increased accuracy can be used:
U"Mj U"Gi " " Ib = I (3 i ) IkGi (3 jq j ) IkMj i c Un / 3 j c Un / 3
" k
"
"
"
"
subtransient reactance of the synchronous machine (i) reactance of the asynchronous motors (j) contribution to initial symmetrical short-circuit current from the synchronous machines (i) and the asynchronous motors (j) as measured at the machine terminals
28.06.2008 Steffen Schmidt Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Continuous short circuit current Ik r.m.s. value of short circuit current after decay of all transient effects depending on type and excitation of generators statement in standard only for single fed short circuit calculation by factors (similar to breaking current) Continuous short circuit current is normally not calculated by network calculation programs. For short circuits far from generator and as worst case estimation Ik = Ik
Copyright Siemens AG 2008. All rights reserved. E D SE PTI NC
Page 65
28.06.2008
Steffen Schmidt
Page 66
28.06.2008
Steffen Schmidt
A B C
Load flow calculation that considers all network parameters, such as loads, tap positions, etc. Place voltage source with the voltage that was determined by the load flow calculation at the fault location. Superposition of A and B
Page 67
28.06.2008
Steffen Schmidt
Page 68
28.06.2008
Steffen Schmidt
Load flow
3 3A 3 33V 33 33 3V ~ 3A 3 3 3A 3 3 3 33 3V 33 3V 3A 3 3 3A 3 3 3A 3 33 3V 3 3 ~
33V 33 -3 V 33V 33
33 V 3. -0000 .0 V 3 33 V 3. 3 3 33 A 3. 3
33 3V -333 V 33 3V
33 3V
3 33 V 3. 3
33 3V
33 3V
Page 69
28.06.2008
Steffen Schmidt
Break time!
Page 70
28.06.2008
Steffen Schmidt
Contact Steffen Schmidt Senior Consultant Siemens AG, Energy Sector E D SE PTI NC Freyeslebenstr. 1 91058 Erlangen Phone: +49 9131 - 7 32764 Fax: +49 9131 - 7 32525 E-mail: [email protected]
Page 71
28.06.2008
Steffen Schmidt
Page 72
28.06.2008
Steffen Schmidt