Lecture 7
Lecture 7
(ME 439)
Instructor Dr. Muhammad Asif
Lecture 7
2
The ASHRAE Handbook (3) summarizes standard
atmospheric data for altitudes up to 60,000 ft (18,291 m).
Atmospheric pressure may be estimated as a function of
elevation by the following relation:
3
Fundamental Parameters
Enthalpy of Dry Air Enthalpy of Water vapors
5
Fundamental Parameters
Enthalpy of Moist air Dry-bulb temperature
ordinary temperature of atmospheric air is
In most practical applications, the amount of dry air in
frequently referred to as the dry-bulb
the air–water-vapor mixture remains constant, but the
temperature
amount of water vapor changes.
Therefore, the enthalpy of atmospheric air is expressed Dew-Point Temperature
per unit mass of dry air.
The temperature at which condensation
The total enthalpy (an extensive property) of atmospheric begins when the air is cooled at constant
air is the sum of the enthalpies of dry air and the water pressure (i.e., the saturation temperature of
vapor: water corresponding to the vapor pressure.)
6
ADIABATIC SATURATION AND
WET-BULB TEMPERATURES
Properties on Charts
1. Dry bulb temperature (dbt)
2. Wet bulb temperature (wbt)
3. Dew-point temperature (dpt)
4. Specific humidity (ꞷ)
5. Relative humidity (φ)
6. Enthalpy of moist air (h)
7. Specific volume of moist air (v)
8
AIR-CONDITIONING PROCESSES
9
Simple Heating and Cooling ( = constant)
(cooling coil) 11
HUMIDIFICATION/DEHUMIDIFICATION
12
Heating with Humidification
- Winter Application ; cooling towers
13
Sensible Heat factor
The ratio of the sensible heat to the total heat is known as sensible heat factor SHF
𝑆𝑒𝑛𝑠𝑖𝑏𝑙𝑒h𝑒𝑎𝑡 𝑆𝐻
𝑆𝐻𝐹 = =
𝑇𝑜𝑡𝑎𝑙 h𝑒𝑎𝑡 𝑆𝐻 + 𝐿𝐻
14
Cooling with Dehumidification
- Summer application
15
Adiabatic Mixing of Airstreams
Many A-C applications require the mixing of two airstreams.
This is particularly true for large buildings, most production and
process plants, and hospitals, which require that the
conditioned air be mixed with a certain fraction of fresh outside
air before it is routed into the living space.
16
Cooling and humidification (Evaporative cooling)
Mass balance
Energy balance
17
EXAMPLE 1
Consider a single duct, single zone, constant speed air handling unit
in which 39.6 m3/min mixture of outdoor air and recirculated room air
at 31℃ dbt and 18.5℃ wbt enters a cooling coil. The effective
surface temperature of the coil is 4.4 ℃. The surface area of the coil
is such as would give 12.5 kW of refrigeration with the given
entering air state. Determine the dbt and wbt of the air leaving the
coil and the by-pass factor.
18
First of all mark initial state of the moist air,
Then the effective surface temperature (ADP) of the coil at 4.4℃
19
EXAMPLE 2
Consider a room is to be maintained at 22℃, 55% RH. Outside saturated air at
3℃ is first heated and then water at 10℃ is sprayed to get the required humidity.
Calculate
1. Required mass of sprayed water per m3 of air
2. The temperature to which the air must be heated
22 C
20
At point 3 (22℃, 55% RH) W3 = 0.00904 kg/kg of dry air
21
EXAMPLE 3
You are required to design an air conditioning plant for the LH-1 of FME, in which
seating capacity is 60 students. Let say the weather condition is now a days (winter
season) and assume for a particular day the outdoor conditions are measured with a sling
thermometer that shows 12℃ dbt, 10 ℃ WBT and 1 atm pressure. The required
conditions in the classroom are 20℃, 60% RH, and air circulation of 0.3 m3/min/person
(from ASHREA handbook). The required conditions in the classrooms are achieved by
first heating and then adiabatic humidification.
Calculate
a. Required heating capacity of the coil and surface temperature of the coil if the bypass
factor of coil is 0.4.
b. Capacity of the humidifier
22
23
Practice following exercise Problem
3-6, 3-7, 3-16, 3-24, 3-43
24