Earthing System of Substation
Earthing System of Substation
2
• Switchyard earthing means laying of an earth-mat
and connecting all non-current carrying parts of
equipments of yard as well as control room to the
earth-mat.
• Safe passage to fault current to enable to operate
protective devices and provide safety to
personnel and Equipments.
• Intentional earthing system is created by laying
earthing rod of mild steel in the soil of substation
area.
Step potential:
The potential difference
shunted by a human body
between two accessible points
on the ground separated by a
distance of one pace assumed
to be equal to one meter.
Touch potential:-
The potential difference
between a point on the
ground and a point on an
object likely to carry fault
current (e.g., frame of
equipment) which can be
touched by a person.
• To limit step & touch potential to the working staff in
substation
• Provides low impedance path to fault currents to ensure
prompt and consistent operation of protective device
• Stabilizes the circuit potentials with respect to ground
and limit the overall potential rise
• Keeps the maximum voltage gradients within safe limit
during ground fault condition inside and around
substation
• Touch Potential – The potential difference between two
points, one on the ground where a man may stand and any
other point which can be simultaneously touched by either
hand.
1. Design parameters,
2. Usage of design parameters for deciding
– Type of earthing conductors and their material and size,
– Maximum permissible dangerous ( touch and step ) potential
difference for human beings in the station area,
– Layout of horizontal grid conductors to keep touch and step
potentials within permissible limits,
3. Locations of rod / pipe / plate electrodes for control of potential
difference and fulfillment of statutory and other requirements,
and
4. Earth electrodes for system ( neutral ) and electronic equipment
earthing.
The main elements of the earthing system of
HVAC stations are :
• Horizontally buried bare strip / round conductors
• Vertically buried bare rod/pipe/plate electrodes
• Bare / insulated earth lead conductors between
above ground earthing points / terminals
equipment / structures and underground buried
horizontal conductors / vertical electrodes.
Where,
Ac Cross section area mm2
I Current, Amp
ρ Resistivity of material micro - ohm
α Resistance temperature coefficient of material per oC
(0.00423)
δ Density of material gm/cm3 (7.86 gm/cm3)
θm The maximum permissible temperature deg.C
θo Ambient temperature deg.C
tf Duration of current flow, seconds
S Specific heat of the material, cal/gm oC (0.114 cal/gm oC)
36
100
D
80
Curve B 4 mesh
A
40
20
Curve C 16 mesh
0
Curve D 64 mesh
• Difficult conditions for the design of an
earthing system are any or all of
Where,
ρ is the resistivity of the soil in Ω-m
R(V/I) is the measured resistance in Ω
S is the distance between adjacent electrodes in meter
e is the depth of burial of electrodes in meter
V Voltage difference between the two inner electrodes in Volts
I Current flowing through the two outer electrodes in Amps
C1,C2 Current electrodes
P1,P2 Potential electrodes
• We have started implementing ‘Maintenance free treated earth
electrode’ in place of ‘CI pipe earthing pits’.
For Normal Soil For Rocky Soil
• Shield wires are strung to provide DSLP for yard
equipments. Hence, do not ignore to provide
earth wires if removed.
• Always use clip-on
type digital meter to
measure healthiness
of earth pits and
equipment structure
earthing.
• Never open the
earth connection.
• Never keep riser unconnected to • Grass/plants/shrubs shall be
earthmat. removed from the yard.
• Never open earth connection in live
switchyard.
• Laying of earth-mat and proper welding as per
standard earthing philosophy.