Module 2
Module 2
D Characteristic For electrical circuits with high in rush current. Typically 12-15 times the
normal rated current.(Eg- Transformers, X-ray Machines etc). SC release set
to 10-20 times In.
K Characteristic For high level of in rush current devices. Instantaneous trip is 812I n. . Ideal
for Motors & Transformers.
S Characteristics For Highly Inductive loads (For circuits with coils and light filaments).
LV MCB availability format
The details given are the minimum requirements and the owner of the building is at liberty to
decide to opt for higher number of points in consultation with the design engineer so as to meet
the present and future anticipated loads.
Estimation of load requirements (Contd)
Details of socket outlets required for domestic buildings (NEC -2011)
The details given are the minimum requirements and the owner of the building is at liberty to
decide to opt for higher number of points in consultation with the design engineer so as to meet
the present and future anticipated loads.
Estimation of load requirements (Contd)
• Total Installed apparent power = sum of kVA rating of individual loads.
• MD kVA need not be equal to the installed kVA.
• Because all loads may not operate simultaneously at full load.
• Hence a correction factor need to be applied to the installed capacity
to determine the maximum demand of the building.
• The two factors for this are
• Factor of maximum utilisation. - ku
• Factor of Simultaneity - ks
Estimation of load requirements (Contd)
Factor of maximum utilisation. - ku
• Loads normally operate at values lower than the rated load.
• For example – Motors.
• For getting a reliable estimate of the operating load , Factor of
maximum utilisation ku is applied.
Standard values of ku
Sl.No Load Type ku
Example problem - 1
GROUND
FLOOR
PLAN
Estimation of load requirements (Contd)
FIRST
FLOOR
PLAN
Estimation of load requirements (Contd)
Estimation of load requirements (Contd)
• 1 x 40 W = 40W Fluorescent Fixtures
• WB = Wall brackets with 11/15W CF Lamps.
• CF = Ceiling fans (1200mm or 1500 mm).
• 6A = 6A light socket points.
• 16/6A = 16/6A power socket points.
• EF = 220/300mm fresh air fans.
Estimation of load requirements (Contd)
2 Protected against solid objects over 2 Protected against direct sprays of water up
12mm, e.g. fingers. to 150 from the vertical.
3 Protected against solid objects over 3 Protected against direct sprays of water up
2.5mm, e.g. tools & wires. to 600 from the vertical.
Protected against solid objects over Protected against water splashed from all
4 4
1mm, e.g. wires & nails. directions, limited ingress permitted.
Consumer units confirming to IS-8623, Universal Single Phase IP20 & IP42 4 4+4
mounting with 100 A Copper bus bar , neutral bar, with 8 4+8
earth bus, cable ties and removable gland plates at metallic or 12 4+12
top & bottom. Provision for double pole acrylic
RCD/MCB/Isolator as incoming & single pole MCB as door.
out going.
Regular DBs confirming to IS-8623 with 100 A bus Single Phase IP20 4 4
bars, neutral & earth bars. 8 8
12 12
Flush mounting DBs confirming to IS-8623 and with Single Phase IP20 4 2+4
reversible pan assembly for top & bottom cable 8 2+8
entry , masking sheet for protection against entry of
concrete, and with provision for double pole 12 2+12
RCCB/MCB/isolator as incomer and MCBs as
outgoing.
PAN Assembly – 12 way TP+E & N
Different Types of distribution boards available (Contd)
Type description No of Protection Number No of
Phases class of ways MCB
modules
Consumer Units confirming to IS 8623,Universal mounting with Three IP20 & IP42 3x3 6+9
100A copper bus bar, neutral bar, earth bus, cable ties & Phase with metallic or
removable gland plates at top & bottom. Provision for 4 pole acrylic door.
RCCB as incoming & 3 Single pole MCBs a outgoing.
ETPN DBs confirming to IS-8623 , Universal mounting with 100A Three IP20 & IP42 4 8+12
copper bus bar, neutral bar, earth bus, cable ties & removable Phase with metallic or 6 8+18
gland plates at top & bottom with knock outs & suitable for acrylic door. 8 8+24
fixing four pole RCD/MCB/isolator as incoming and single pole 12 8+36
MCB as outgoing
Per Phase isolation DBs. Confirming to IS8623 , Universal Three IP20 & IP42 4 8+12
mounting with 100A copper bus bar, neutral bar, earth bus, Phase with metallic or 6 8+18
cable ties & removable gland plates at top & bottom with knock acrylic door. 8 8+24
outs & suitable for fixing four pole RCD/MCB/isolator as 12 8+36
incoming . 3 DP RCD/MCB/Isolator as sub incomer & single pole
MCB as outgoing with separate neutral bars.
Per Phase isolation DBs.
Different Types of distribution boards available (Contd)
Type description No of Protection Number No of
Phases class of ways MCB
modules
Phase Selector DBs as per IS-8623, Universal mounting with 100 Three IP20 & IP42 4 6+12
A Copper bus bar , neutral bar, earth bus, cable ties and Phase with metallic 6 6+18
removable gland plates at top & bottom with provision for 3 Nos door. 8 6+24
of 63 A selector Switches, 3 Nos of Piano type indicating lamp 12 6+36
switch, 4 Pole RCD/MCB/Isolator as incoming and SP MCBs as
out going
Seven segment DBs confirming to IS-8623 , with 100A copper Three IP20 & IP42 4 4+12+12
bus bar, neutral bar, earth bar, top & bottom removable gland Phase with metallic 6 4+12+18
plates with provision for fixing four pole RCD/MCB/isolator as door. 8 4+12+24
incoming ,DP RCDs/MCBs/isolator as sub incomer & SP MCBs as 12 4+12+36
outgoing .(These DBs provide Phase segregation & separation
between incomer & outgoing)
VTPN DBs as per to IS-8623 , with 200A copper bus bar, neutral Three IP20 & IP42 4 8+12
bar, earth bar, top & bottom removable gland plates with Phase with metallic or 8 8+24
provision for fixing four pole RCD or RCBO/MCB/isolator as acrylic door. 12 8+36
incoming and SP/TP MCBs as outgoing(The advantage of this DB
is that both single & 3 Phase outgoings can be taken from this
DB)
Phase Selector DBs
Seven segment DBs
VTPN DBs
Types of wiring systems
PVC Insulated & PVC sheathed wires on teak wood batten.
Economical -Old type wiring system – For low cost housing- Can
be taken up after the completion of the building structure work.
PVC insulated wires in steel /PVC surface conduits.
Functional & easy to maintain – Suited for shop floors and industries. – Can be
taken up after the completion of the building structure work.
1 7 13 20
1.5 6 10 14
2.5 5 6 10 14
4 3 6 10 11
6 2 5 9 11
10 4 7 9
16 2 4 4 12
25 2 2 6
General rules applicable for conduit wiring using rigid PVC conduits. (Contd)
6. Conduits interconnection – Threaded or pasted as the case may be.
7. For long straight runs, inspection type of couplers should be used at regular intervals.
8. Conduits shall be separated by saddles with a minimum spacing of 600 mm.
9. Necessary conduit specials like bend, inspection bend, elbow & T’s shall be used
wherever appropriate.
10. Concealed wiring- Chase in the walls should be of correct size to lay the conduits
correctly. If the building is under construction, the chase shall be made before
plastering of the walls.
11. Conduits in ceiling shall be laid while concreting the ceiling slabs.
12. Inspection box – For periodical inspection and for removal of wires if necessary.
Minimum size – 75x75 mm.
13. Switch, socket, ceiling rose etc – Either surface type or flush type.
14. All flush mounting outlets shall be made of mild steel or aluminium boxes with a
cover plate of insulating material and with provision for earthing.
Selection of Conductor size (IS 732)
1. Should be PVC insulated copper or aluminium.
2. Light & Fan circuit – should not be less than1.00 Sq mm or 1.5 Sq mm.
3. Power Circuit - should not be less than2.5 Sq mm copper or 4 Sqmm
Aluminium.
4. Minimum cross section of flexible cords – 0.5 Sqmm Copper.
Selection of Conductor size (IS 732)
Flexible house wiring single core cables (copper conductor –
240/415V)
Selection of Conductor size (IS 732)
Selection of Conductor size (IS 732)
Typical schedule of quantities for the electrical installations of a residential building.
Typical schedule of quantities for the electrical installations of a residential building. (Contd)
Typical schedule of quantities for the electrical installations of a residential building. (Contd)