Per Unit System
Per Unit System
Per-Unit System
In the per-unit system, the voltages, currents,
powers, impedances, and other electrical
quantities are expressed on a per-unit basis by
the equation:
Actual value
Quantity per unit =
Base value of quantity
Vb Vrated
Sb S rated
Then compute base values for currents and
impedances:
Sb Vb V 2
Ib Zb b
Vb Ib Sb
3
Per-Unit System
The per-unit system (for a single-phase system)
is:
Vactual I actual
V p.u . I p.u .
Vb Ib
S actual Z actual
S p.u . Z p.u .
Sb Zb
Solution:
(1) Compute lamp resistance
2 2
V V
(120) 2
P R 28.8
R P 500
5
Example 1 Continued
(2) Select base quantities
Sb 500 VA
Vb 120 V
VS 10 p.u.
o Z 10o p.u.
7
Example 2
An electrical lamp is rated 120 volts, 500 watts. If
the voltage applied across the lamp is twice the
rated value, compute the current that flows
through the lamp. Use the per-unit method.
Solution:
Vb 120 V
V 240
Vp.u. 20o p.u.
Vb 120
Z p.u. 10o p.u.
8
Example 2 Continued
The per-unit equivalent circuit is as follows:
Vp.u. 20
I p.u. 20o p.u.
Z p.u. 10
Sb 500
Ib 4.167 A
Vb 120
I actual I p.u. I b 20o 4.167 8.3340o A 9
Per-unit System for 1- Transformer
Consider the equivalent circuit of transformer
referred to LV side and HV side shown below:
R p jX p R p jX p a 2
Z b1 Vb21 Vb21 1
2 2
2
Z b 2 Vb 2 (a Vb1 ) a 11
Per-Unit System for 1- Transformer
Per-unit impedances are:
R p jX p
Z p.u .1
Z b1
Z p.u .2
R p jX p a 2
R p jX p a 2
R p jX p
2
Zb2 a Z b1 Z b1
Per-unit equivalent
circuits of transformer
So:
Z p.u .1 Z p.u .2 referred to LV side and
HV side are identical !!
12
Example 3 Transformers Per Unit
A transformer is rated 2000 VA, 200V/400V, and has
an internal impedance of j4.0 as seen from the low
voltage side.
Solution:
Zs = j4.0 x (400/200)2 = j 16Ω
Low-Voltage Side: High-Voltage Side:
Sbase = 2000 VA Sbase = 2000 VA
Vbase = 200 V Vbase = 400 V
Ibase = Sbase / Vbase = 10 A Ibase = 5 A
Zbase = Vbase / Ibase = 20 Ω Zbase = 80 Ω
S3 3V I 1
Sb S3
3
Vb V 1 VL L / 3 (Y cct.)
Vb V 1 VL L ( cct.) 14
Example 4: Per-Unit System for a 3-
Transformer
A three-phase 25-kVA, 34500/277-V transformer is
connected in -Y. Its equivalent series impedance
referred to the high-voltage side is 191.48 + j
900.86 Ω (ignoring shunt branch).
Sb 8333.3
I b , HV 0.242 A
Vb , HV 34500
Vb , HV 34500
Z b , HV 142562
I b , HV 0.242
191.48 j 900.86
Z pu, 0.0013 j 0.0063 pu
142562
16
One-Line (Single-Line) Diagrams
Almost all modern power systems are three-phase systems with the phases of equal
amplitude and shifted by 120˚. Since phases are similar, it is customary to sketch
power systems in a simple form with a single line representing all three phases of
the real system.
Example 5: A power system containing two synchronous machines, two loads, two
busses, two transformers, and a transmission line to connect busses together.
All devices are protected by oil circuit breakers (OCBs). We notice that the diagram
indicates the type of connection for each machine and transformer, and also the
points in the system connected to the ground.
The ground connections are important since they affect the current flowing in
nonsymmetrical faults. These connection can be direct or through a resistor or
inductor (they help reducing the fault current that flows in unsymmetrical faults,
while having no impact on the steady-state operation of the system since the current
through them will be zero). Machine ratings, impedances, and/or consumed (or
supplied) powers are usually included in the diagrams.
One-Line (Single-Line) Diagrams Continued
M
Impedance Diagram
•In power system fault calculations it is often that a single-line diagram
representing a typical power network in 3- be converted into its per phase
impedance diagram.
• Some assumptions for converting from single-line diagram into its equivalent
impedance diagram needed to be considered:
(i) A generator can be represented by a voltage source in series with an
inductive reactance. The internal resistance of the generator is assumed to be
negligible compared to the reactance.
(ii) The loads are usually inductive represented by resistance and inductance.
(iii) The transformer core is assumed to be ideal, and the transformer may
be represented by a reactance only.
(iv)The transmission line is represented by its resistance and inductance, the
line-to-ground capacitance is assumed to be negligible.
Impedance Diagram Continued
G2 G4
Load Load
L1 L2
Transmission
Transformer Line Transformer
T1 TL T2
Station A Station B
j XT1 RTL j XTL j XT2
j X1 j X2 RL1 RL2 j X3 j X4
G1 G2 j XL1 j XL2 G3 G4
21
Example 6
Determine the per-unit values of the following single-
line diagram and draw the impedance diagram.
5 MVA 100 MVA 50 MVA
275 kV/132 kV Transmission line 132 kV/66 kV
Xg = 16%
j 3.48
Z b, g 756.25
I b, g Sb, g 100x106
3
Calculate actual genetaor impedance from old per unit value (0.16 16%) :
For this, we need first to calculate old base impedance of the generator (on 5 MVA and 275kV basis).
Thus,
2
275x103
Z b , g ,old
Vb , g ,old
Vb , g ,old
2
3 15125
6
I b , g ,old Sb , g ,old 5x10
3
Now,
Zg,actual Zg, pu, old Z b , g ,old j 0.16 15125 j 2420
2420
Z g , pu j j 3.2 pu
756.25
23
Example 6 Continued
Transformer T1: X T 1 ( pu ) 0.1 pu ( why ?)
Transmissi on Line :
100 MVA 132kV Sb ,TL
Sb ,TL ; Vb ,TL ; I b ,TL ;
3 3 Vb ,TL
2
132 x103
Vb ,TL Vb ,TL
2
3
Z b ,TL 6
174.24
I b ,TL Sb ,TL 100 x10
3
Z TL,actual j 3.48
Z TL j 0.02 pu
Z b ,TL 174.24
24
Example 6 Continued
Transformer T 2 on 66 kV side ( why ?) :
100MVA 66kV S
Sb ,T 2 ; Vb ,T 2 ; I b ,T 2 b ,T 2 ;
3 3 Vb ,T 2
2
166x103
V V 2
Z b ,T 2 b ,T 2 b ,T 2
3
43.56
I b ,T 2 Sb ,T 2 100x106
3
We need to calculate actual transformer T 2 impedance from old base (50 MVA, 66 kV ) :
2
66x103
Z b ,T 2,old
Vb ,T 2,old
Vb ,T 2 ,old
2
3
87.12
6
I b ,T 2,old Sb ,T 2,old 50x10
3
Now,
ZT2,actual ZT2,pu,old Z b ,T 2,old j 0.04 87.12 j 3.485
3.485
Z T2,pu j j 0.08 pu
43.56
25
Example 6 Continued
Load :
40MW 66kV
P1 phase ; Vb , Load ;
3 3
Now,
40x106 66 x103
P1 p V p I p cos x 0.8xI p I p 437.4 A
3 3
Now,
Load impedance is calculated as :
66x103 0
Vp 3
Z Load 87. 1136. 87 o
I p 437.4 36.87 o
Now,
87.1136.87 o
Z Load,pu 236.87 o 1.6 j 1.2 pu
43.56
26
Example 6 Continued
Now, we have all the impedance values in per-unit with a common base and we
can now combine all the impedances and determine the overall impedance.
5 MVA 100 MVA 50 MVA
275 kV/132 kV Transmission line 132 kV/66 kV
Xg = 16%
j 3.48
Generator Load
G j 1.2 p.u.
27
Problem 1
j100
28