Earthing
Earthing
BY
M.DURGA PRASAD.,B.E.,
RETD.CHIEF ENGINEER.
The primary objectives of a grounding system are to:
5
PURPOSE OF
PROTECTIVE EARTHING
To ensure the safety of the
people and property
within the zone served by it.
6
Soil forming processes
Introduction
1. Equipotential bonding of conductive objects
(eg.metallic equipment,building,piping etc .)to
the earthing system prevent the presence
of dangerous voltages between objects.
2. The earthing system provides a low
resistance path for earth faults within the
plants which protects both personnel and
equipment.
contd
3. The earthing system provides a low
resistance path for voltage terminals such as
lightning and surges/ over voltages.
4. Equipotential bonding helps prevent Electro
static build up discharge,which can cause
sparks with enough energy to ignite flammable
atmosphere.
5. The earthing system provides a reference
potential for electronic circuits and helps reduce
electrical noise for electronic instrumentation
and communication system.
The objective of a grounding system are:
1. To provide safety to personnel during normal and fault
conditions by limiting step and touch potential.
2. To assure correct operation of electrical/electronic
devices.
3. To prevent damage to electrical/electronic apparatus.
4. To dissipate lightning strokes.
5. To stabilize voltage during transient conditions and to
minimize the probability of flashover during transients.
Earth Resistivity
Soil or Earth resistivity expressed in ohm-meter is the
resistance of cubic meter of earth measured.
The resistivity of Copper is 1.6 micro ohm-cm, whereas
the normal value of Soil will be 10000 ohm-cm.The
resistivity of Soil is determined by the quantity of water
held in itself.In otherwords, it can be said that conduction
of electricity through soil due to water content present in
it.
Poor grounding contributes to downtime and
increases the risk of equipment failure.
Corrosive soils with high moisture and salt
content and high temperature can degrade
ground rods and their connections. So even
though the ground resistance is less when
installed, it will increase, if the ground rods are
corroded.
So testing of ground rods are to be done once in
a year.If it increases by 20% the problem to be
investigated and rectified.
The PRIMARY goal of the grounding
system throughout any facilities is
SAFETY.
Why ground at all?
PERSONNEL SAFETY FIRST
EQUIPMENT PROTECTION SECOND
What are the three main types
of grounding?
Discharge grounding.
. 15
US National Fire Protection Agency & Institute of
Elec&Electronic Engineers(IEEE) recommended a ground
resistance value of 5ohms or less.
What effects the grounding resistance?
Four variables effect the ground resistance.
1. Diameter of the electrode.
2. No of ground electrodes.
3. Length of electrode.
4. Ground system design.
19
DISSOLVED SALTS
. 20
GRAIN SIZE & DISTRIBUTION
The grain size, distribution and
closeness of packing also contribute to
retention of moisture in the soil.
SEASONAL VARIATION
Increase or decrease of moisture
content determines the increase or
decrease of soil resistivity.
Thus in dry whether resistivity will be
very high and in monsoon months the
resistivity will be low.
. 21
REDUCTION OF EARTH RESISTIVITY:
METHODS.
Chemicals traditionally used for changing
resistivity are:
-- sodium chloride, NaCl (salt)
-- magnesium sulphate MgSo4,
-- Copper Sulphate CuSo4,
-- Sodium Carbonate,NaCo3, (Washing
Soda),
-- Calcium Chloride, CaCl.
Earth resistivity can be reduced to:
-- 0.2 ohm meter using NaCo3,or
-- 0.1 ohm meter using salt. 22
1.2 grams per liter of salt in dissolved water
has a resistivity of 5.0 ohm meter, while 6
grams per liter of salt in dissolved water has a
resistivity of 10 ohm meter.
GYPSUM:
has water retention property.
Low solubility.
Resistivity of 5 – 10 ohm meter.
Neither acidic nor alkaline with Ph value between 6.2
to 6.9.
BLAST FURNACE SLAG:
Use of blast furnace slag on the granulated form is
on an experimental stage.
. 23
BENTONITE:
-- Mixed in the ratio of 1 : 6 with black
cotton soil.
-- Is a volcanic product.
-- Is acidic by nature, with Ph value of
10.5.
-- Absorbs 5 times of water.
-- Swells upto 13 times its dry
volume.
-- Non corrosive.
-- resistivity is 5.0 ohm meter.
. 24
• MARCONITE:
25
• Connecting lead should have sufficient current
carrying capacity.
• L A s should have independent earth electrode which
should be inter connected to the station grounding
system.
• All paints, enamel, seals should be removed from the
point off contact of metal surfaces before earth
connections are made.
• The resistances of earth system should not exceed 2
ohms for 33/11 KV Sub Stations.
• But in the sub stations of Distribution companies
Earth resistance Maximum of 1 Ohm is maintained.
• Suitable grounding mat should be provided in the sub
station yard
26
In a Sub Station the following shall be earthed.
The neutral point of the systems of different
voltages which have to be earthed.
. 28
5. What are to be earthed
(a) Bodies of all the equipment's
(b) Neutral Point
(c) Battery mid point
(d) Tertiary winding
(e) Cable sheathe
(f) Structures
(g) Street Light Poles / LT / HT Poles
(h) Control Panel
(i) Lightning arrestor Dedicated earthing
with earth pits
(j) Computers / SCADA / Electronic
A safe grounding design has two objectives:
1. To provide means to carry electric currents
into the earth under fault conditions
without exceeding any operating and
equipment limits or adversely affecting
continuity of service.
Very 30 10 5 3 12 6 3
moist
soil
Farming 100 33 17 10 40 20 10
soil
Sandy 150 50 25 15 60 30 15
clay soil
Moist 300 66 33 20 80 40 20
sandy
soil
Moist 500 160 80 48 200 100 50
gravel
ssDry Sandy 1000 330 165 100 400 200 100
soil
Step potential
“Step potential” is the voltage
between the feet of a person standing
near an energized grounded object.
It is equal to the difference in voltage,
given by the voltage distribution curve,
between two points at different
distances from the “electrode.”
A person could be at risk of injury
during a fault simply by standing near
the grounding point.
Touch potential
“Touch potential” is the voltage between
the energized object and the feet of a
person in contact with the object.
It is equal to the difference in voltage
between the energized object and a point
some distance away.
The touch potential could be nearly the
full voltage across the grounded object if
that object is grounded at a point remote
from the place where the person is in
contact with it.
Mesh Potential :-- The mesh potential is defined
as the potential difference between centre of an
earthing grid mesh and a structure earthed to
the buried grid conductors.
Transferred Potential:-- This is special case of a
touch potential in which a voltage is transferred
into or out of a sub-station for some distance by
means of an earth metallic conductor.
Step and touch voltages
STEP AND TOUCH POTENTIAL
Basic Shock Situations in Substations
THE PERMISSIBLE LIMITS OF STEP POTENTIAL AND TOUCH
POTENTIAL SHALL BE
Maximum Acceptable step Voltage
Fault clearance times
44
PERMISIBLE EARTH RESISTANCE
As per IE Rules, one has to keep Touch Potential less than safe
value of 523V.
I fault = Max current in fault conditions.
Resistance= Touch Voltage/ If = Vf/If.
Max fault current for a 100kva Transformer:-
Full load current = 133Amps, Impedance =4.5%
If= 100x100 = 2900 say
1.732x4.5x.44
Therefore R = Vt/If = 523/2500=0.209.
As 0.209 ohms being quite low, quality work is to be done during
construction.
To obtain such a low value of Resistance of the earth system,the
expenditure will be very high.
The earth electrode resistance value also causes
importance in view of protection against lightning by
lightning arrester.
The earth electrode resistance value in that case is given by
R= Flashover voltage/ Lightning discharge current.
Flash over voltage of 11kv= 75kv.
LAS discharge = 40KA.
Therefore R= 75/40=1.9ohms.
Thus the earth electrode resistance for LAS of 11kv system
has to be < 1.9ohms.
However taking the fault current and implementation
difficulties in view, the DTR structure the earth resistance
value is to be maintained below 5 ohms.
Earth / Ground Basics
Types of Grounding Systems
Ground plate
Earth / Ground Basics
Types of Grounding Systems
Ground mesh
Soil Characteristics
Soil type. Soil resistivity varies widely
depending on soil type, from as low as 1
Ohm-meter for moist loamy topsoil to almost
10,000 Ohm-meters for surface limestone.
Moisture content is one of the controlling
factors in earth resistance because electrical
conduction in soil is essentially electrolytic.
Cable(Earthing conductor)
Clamp
Test link
Rod(Earthing electrode)
Rod coupler
Recommended values of earth resistance
33 / 11 kv SS 2.0
EHT SS 1.0
Gen.Station 0.5
Substation earthing system
•Grounding grids
calculations
Touch potential limit :-- The maximum potential
difference between the surface potential and the
potential of an earthed conducting structure during a
fault due to ground potential rise)
_
50kg person : E touch50 = (1000+1.5 Cs ps)x0.116/ v ts.
70kg person : E touch70 = (1000+ 1.5cs ps)x0.157/v– ts
Where E touch is the touch voltage limit.
Cs is the surface layer derating factor.
Ps is the soil resistivity(ohm.m)
ts is the maximum fault clearing time
Cs = 1- 0.09 ( 1- p/ps)
2hs + 0.09
Where p
is soil resistivity, p s is the resistivity of the surface layer , hs is the
contd
Step potential limit:--
E step 50 : -- [ 1000+ 6Cs- ps]0.116/v-t1
E step 75 :-- [ 1000 + 6 Cs – ps] 0.157/ v- t1
68
13. Earth Electrodes sizes
33 KV Substation - 75 x 8 / 50 x 6
132 KV Substation - 100 x 16 / 50 x 8
Used to determine
which KIND of
earthing should be
used, so BEFORE
placing earth stakes
Ground Testing
Methods (1)
Resistivity Measurement
E = 2 . a . R E
8l
R ln d 1
2 l
where: ρ Soil Resistivity in m
l Buried Length of the electrode in m
d Diameter of the electrode in m
The rod is assumed as carrying current uniformly along its rod.
Examples
(a) 20mm rod of 3m length and Soil resistivity 50 Ω-m .....R=16.1 Ω
(b) 25mm rod of 2m length and Soil resistivity 30 Ω-m .....R=13.0 Ω
The resistance of a single rod is not sufficiently
low.
A number of rods are connected in parallel.
They should be driven far apart as possible to
minimize the overlap among their areas of
influence.
It is necessary to determine the net reduction in
the total resistance by connecting rods in
parallel.
The rod is replaced by a hemispherical
electrode having the same resistance.
Rod Electrodes in Parallel
AT-090H AT-090H
Earth clamping 2
Extremely conductive
Easy installation
Permanent
Installing an EARTHLINK 101 earthling strip is
simple:
140
•
Steps to be taken for
Finalize lay out plan of the substation.
design
purpose:
• Obtain the earth resistivity of the location where
substation is to be located.
141
Steps to be taken for design purpose:
A uniform corrosion allowance of 0.12 mm
per year is considered for steel as ground
conductor.
142
Steps to be taken for design purpose:
. 143
Steps to be taken for design purpose:
• The number of electrodes is given by the following
thumb rule:
N = If / 250,
for a earth resistivity of 500 ohm meters.
N = If / 500,
for a earth resistivity of 5000 ohm meter.
146
Steps to be taken for design purpose:
• 100 X 16 mm and 75 X 8mm size MS steel
flats form the earthing system for EHT Sub
station and 33/11 KV Sub Stations
respectively
147
Steps to be taken for design purpose:
• The intermediate earthing conductors forming
the earth mat shall be of 75 x 8 mm size flat.
148
Steps to be taken for design purpose:
All the equipments, structures, conduits, cable
sheaths shall be solidly grounded at least at two
places.
149
• All paints, enamel and scale shall be removed from
point of contact in metal surfaces before giving
ground connections.
. 150
Soil resistivity ‘’ may be obtained from the
following formula :
= 2 LR where,
151
Choosing the cross section of
S=(I √t)/k earth flat.
S= Cross sectional area in Sq mm.
I= Fault current which can flow in the earth mat.
t = Disconnection time not exceeding 5 sec.
k=Constant Factor dependent on protective
conductor
K for the Copper Aluminum Steel
Material
1 Sec 131 86 47
3 Sec 76 50 27
. 162
MAINTENANCE FREE EARTHING (cont’d )
163
MAINTENANCE FREE EARTHING (cont’d )
• Long Life.
• Easy Installation.
164
MAINTENANCE FREE EARTHING (cont’d )
TECHNICAL DETAILS :
165
MAINTENANCE FREE EARTHING (cont’d )
u. 167
MAINTENANCE FREE EARTHING (cont’d)
u. 168
MAINTENANCE FREE EARTHING (cont’d)
169