SmartDC V100R021C00 Smart

Module Training Slides

www.huawei.com

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Foreword
 Since Huawei advocates the smart modular data center solution, vendors in the market have
promoted their smart module solutions. All the solutions are homogenized. Some traditional
solution vendors even copy each other to deliver projects. The industry environment is
deteriorated, becoming less technically professional. In addition, industry customers disassemble
the entire smart module during the centralized procurement process. As a result, the smart module
forms an assembled product. The coupling between smart modules is reduced, and every system
is isolated and cannot produce a joint effect. To further improve the competitiveness of the smart
module and lead the market trend, Huawei focuses on intelligence, the two core functions of power
supply and cooling, and perceivable and experienceable smart features, proposing iPower,
iCooling, and iManager solutions to find new niches.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Objectives
 On completion of this course, you will be able to:

Understand the major features of smart module 5.0.

Understand the changes in smart module 5.0 compared with earlier versions.

Understand the evolution of FusionModule2000.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Huawei Data Center Solution Portfolio
DCIM+ NetEco 6000 system

With buildings (indoor) Without buildings (outdoor)

Medium and large data center Small data center Medium and large data center Small data center
Scenario-
specific
solutions

Prefabricated modular data


Smart module AIO smart small data center center FusionDC Prefabricated AIO data center

Core
products UPS2000-A/G UPS5000-E UPS5000-S UPS5000-S-FP SmartLi
1–20 kVA 25–800 kVA 50–800 kVA 990–1600 kVA
NetCol5000-A NetCol5000-C NetCol8000-A NetCol8000-C NetCol8000-E
11–42 kW 30–80 kW 13–120 kW 62–253 kW 220–440 kW

Power supply and distribution Cooling

6
Copyright © Huawei Technologies Co., Ltd. All rights reserved.
Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Smart DC and Smart Module
Integrated Smart module
management
Traditional modules Micro module A/B Intelligent
controller
system
UPS, power IT equipment room
distribution, and
battery room

Intelligent DC1 DC2 DC3


UPS

management
system Battery

IT equipment room

DC controller

Traditional modules Aisle containment + Cabinets + PDUs


Intelligent
controller Busway
Micro module B Traditional modules + In-row air conditioners
Smart module Micro module B + UPS + Batteries deployed
Busway
Micro module A inside or outside the module
Smart module Micro module B/A + Intelligent controller

 Smart module: With the power supply and distribution module, cooling module,
and intelligent management as the core, the smart module contains the structure,
 Smart DC = Smart module + DC controller + Management system
network, cabling, and fire extinguishing (optional) units. It provides an intelligent,
 DC controller: links L0, L1, and L2 to provide an automatic control prefabricated, and integrated product solution with minimal PUE, minimal SUE, and high
system with low PUE, and uses BOX + control algorithm. availability.

Basic hardware: L0 outdoor (chiller and diesel generator); L1 indoor (smart module); L2 equipment (server and LAN switch)

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Smart DC Version Evolution

Smart DC 2.0 Smart DC 3.0 Smart DC 3.1 Smart DC 5.0

FusionModule2000 FusionModule2000 FusionModule2000 FusionModule2000


V100R001C00 V500R003C00 V500R003C10 V100R021C00
 New version of aisle door/cabinet
 PUE 1.6  New version of industrial design  New version of integrated UPS
 Intelligent and integrated power  Smart rPDU  New version of air conditioner  Lithium battery cabinet
supply and distribution  New version of air conditioner  Newly-added water-cooled module  New version of integrated power
 25 kW air-cooled in-row DC inverter  New version of light  Newly-added vertically integrated cabinet distribution frame (PDF)
air conditioner  New version of cabinet  New version of new main way (NMW)  Monitoring rPDU
 ECC800 bus architecture temperature sensor  New version of ECC800  New version of half-sized smart
 Intelligent O&M  U space identification  Newly-added facial recognition feature cooling product
 Intelligent features of iPower,  Newly-added atmosphere light  Three-in-one actuator
iCooling, and iManager  Smart large screen
 Robot

TR5 2015-10-30 TR5 2018-06-15 TR5 2019-06-30 TR5 2020-06-30

ECC800V100R001C10 ECC800V100R001C42 ECC800V100R003C00 ECC800V100R021C00

NetEcoV600R007C00 NetEcoV600R008C10 NetEcoV600R008C20 NetEcoV600R009C00

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


SmartDC V100R021C00 Smart Module System Composition
1. Structural system:
NetEco6000 centralized Local management over a AI-Robot intelligent O&M cabinets, skylights, end
management pad or large screen
doors, and cable troughs
2. Power supply and
 Automatic inspection
 Intelligent O&M distribution system:
 Fault viewing
integrated UPS cabinets,
integrated PDFs,
M-shaped cable modular precision PDFs,
trough/Stainless steel mesh In-row air-cooled smart cooling product
cable trough
 35/46 kW, horizontal air supply NMW, and lithium battery
 Adjustable positions of
 N+X redundancy, improving reliability

Cooling system
partition boards, facilitating
 Linkage between temperature, loads, and cooling cabinets
flexible cabling systems, ensuring the stable temperature field
 Dual cable trough design,
 AI self-optimization algorithm, reducing energy 3. Cooling system: in-row
separating electric and ELV consumption by 8% to 15%
optical fibers
 Refrigerant capacity check, avoiding cooling air-cooled air
attenuation

Aisle system
conditioners
 eLight module status
indicator Smart busway 4. Monitoring system:
Automatic lighting system
ECC800-pro, cameras,

 Aisle-level access control
 250 A/400 A
system
 Power distribution branch temperature monitoring
 Automatic sliding door Integrated UPS/Integrated PDF/Precision end cabinet
and multi-functional
 Panoramic skylight, good-
light aisles  Integrated UPS (60/125 kVA)
sensors
 Aisle containment to isolate Integrated PDF (160/250 A)
5. Management system:

cold air from hot air  Precision PDF (160/250/400/630 A)

Power distribution system


IT cabinet  Temperature monitoring for power distribution
NetEco and intelligent
Structural system

branches, avoiding fire risks



600/800 mm wide, 42 U/47 U
19-inch standard cabinet with
inspection robot
Lithium battery system

a static load of 1800 kg
Supporting electronic access
6. Integrated cabling

Monitoring system
control using IC cards Monitoring system  80 Ah/40.9 kWh system: internal power
 Standard cabinet-level fire protection
ECC800 ring network monitoring
and signal cables

 Local management and real-time
display on a pad or 43-inch
smart large screen 7. Auxiliary fire
 System-level facial recognition
extinguishing system

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Glass skylight
 Common (inherited)
 Maintainable
(inherited)

Control skylight
 Common (inherited) Small busway:
 Maintainable (inherited) 250 A/400 A
(inherited)

Top sealing
plate (inherited)

Network cabinet: round


holehexagonal hole

Aisle door:
aisle door of version 3.0 (inherited; can be used
with the large screen)
aisle door of version 21A (newly developed, low-
cost, not supporting a large screen)

43-inch large screen


(newly developed)

SmartLi inside Lithium battery IT cabinet: In-row smart cooling product:


Large-screen door (newly enclosure frame round  Full-sized cabinet: 46 kW
box (developed with developed) (newly developed hexagonal (inherited)
End cabinet hole
the large screen) for the lithium  Half-sized cabinet: 25 kW
 Integrated UPS: version Aversion
battery cabinet) (1100 mm)25 kW (1100
C, 25 kVA module30 kVA module,
mm) & 35 kW (1200 mm)
lead-acid batterylithium battery
 Integrated PDF: IT output switch:
40 A/1P40 A/1P, 63 A/1P, 40 A/3P
 Precision PDF: IT output switch: 40
A/1P40 A/1P, 63 A/1P, 40 A/3P

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cabinet Aisle System – Aisle Door

Aisle Door Picture Remarks

Incorporating the aisle doors of versions


Standard 2 m sliding door/revolving door 2.0 and 3.1;
configuration 2.2 m sliding door/revolving door not supporting eLight and large-screen
features

2 m sliding door/revolving door Aisle doors of version 3.0;


High-end 2.2 m sliding door/revolving door all doors supporting eLight;
configuration 2 m electric sliding door 2 m sliding doors and electric sliding
2.2 m electric sliding door doors supporting large screens

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cabinet Aisle System – Installing Large Screens

1. Installing the internal door frame 2. Installing guide rails 3. Installing rubber strips 4. Installing glass doors

5. Installing dampers 6. Installing door box hanging kits 7. Installing a magnetic lock 8. Installing door headers for the smart screen

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cabinet Aisle System – Installing Large Screens

9. Securing the external posts 10. Installing the external door frame 11. Installing bottom sealing plates
and door headers

Route cables for the


access control device,
alarm beacon, and
smart screen.

12. Installing the large screen door box 13. Installing the smart screen

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Integrated UPS

Function Configuration
Input subrack Function Configuration 60 kVA 125 kVA

Lighting output Input capacity 250 A 400 A


Monitor screen General input
Input system Single-route MCCB input; dual-route ATS input
Air conditioner
output
Input

UPS power distribution Output MCCB 160 A MCCB 250 A

IT output Maintenance bypass

Air conditioner power 40 A/3P x 8 40 A/3P x 8


distribution or 63 A/3P x 8 or 63 A/3P x 8
Precision power
Power distribution distribution Lighting power distribution 10 A/1P x 3
module
IT power distribution 40 A/1P x 48 40 A/1P x 48
Control module
Bypass module 2000 mm x 600 mm x 1100 mm
Mechanical specifications (H x W x D) 2000 mm x 600 mm x 1200 mm (with an enclosure frame)
2200 mm x 600 mm x 1200 mm (with a top frame)

 Multiple cabinets combined: four cabinets (UPS input cabinet, output cabinet, UPS cabinet, and precision PDF) + two PDBs (lighting PDB and air conditioner
Power module
PDB)
25 kVA→30 kVA
 Hot-swappable maintenance: The power module, control module, bypass module, and power distribution monitoring module are hot-swappable.
 Visual management: The voltage, current, load rate, efficiency, and circuit breaker terminal temperature are visual.
 2N and N+1 power supply architectures are supported.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – SmartLi 2.0

1 Monitoring unit
 Typical power backup time: 10 min/15 min/30
min/60 min
2 Battery switch  Electrochemical cell: lithium iron phosphate
(LFP)
3 Fuse  Nominal voltage: 512 V DC

Intelligent battery
 Nominal capacity: 80 Ah/40.96 kWh
4 management module  Discharge rate: 6C

5 Monitor screen
 Operating voltage range: 400–544 V DC
 Charge current: 0.1–1C (0.5C by default)
6 Lithium battery module  Cycle life: 5000 cycles at 50% DOD
 Cabling mode: top cabling
 Combined cabinets: a maximum of eight cabinets
 Standard cabinet-level fire extinguishing system
(excluding gas)
 Dimensions: 600 mm x 850 mm x 2000 mm

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Installing the SmartLi 2.0 Tail Frame

1. Installing beams 2. Installing the outer top cover 3. Installing the bottom and side panels

Injecting gas into the gas cylinder

4. Removing the rear door panel, rear door 5. Installing a tail frame 6. Installing the PVC panel
header, and rear door connecting kits

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Commissioning SmartLi 2.0

Manually changed
from Manual to
DHCP auto

SmartLi setting screen SmartLi system parameters

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Integrated PDF

Function Configuration
IT input
Function Configuration Scenario 1 Scenario 2

IT input Single/Dual: 160 A/250 A


Monitor screen
Input
Air conditioner input Single/Dual: 160 A/250 A
IT output

Branch IT output 40 A/1P x 48, 63 A/1P x 48, 40 A/3P x 16


monitoring
40 A/3P x 16
Air conditioner output
Output or 63 A/3P x 16

Air conditioner
input Lighting output 10 A/1P x 3

2000 mm x 600 mm x 1100 mm


Mechanical specifications (H x W x D) 2000 mm x 600 mm x 1200 mm
Air conditioner 2200 mm x 600 mm x 1200 mm (with a top frame)
output

Branch  Multiple cabinets combined: one cabinet (precision PDF) + two PDBs (lighting PDB and air conditioner PDB)
monitoring  Hot-swappable maintenance: The power distribution monitoring module is hot swappable.
 Visual management: The voltage, current, load rate, efficiency, and circuit breaker terminal temperature are visual.
 2N and N+1 power supply architectures are supported.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Precision PDF

Function Configuration

Function Configuration Description

Monitor Input IT input Single/Dual: 160 A/250 A/400 A; single: 630 A


监控 显示
IT IT输
input入 screen

40 A/1P x 144
Output IT output 63 A/1P x 144
40 A/3P x 48

IT输 出
IT output 2000 mm x 600 mm x 1100 mm
Mechanical specifications (H x W x D) 2000 mm x 600 mm x 1200 mm
2200 mm x 600 mm x 1200 mm

Branch  Hot-swappable maintenance: The power distribution monitoring module is hot swappable.
支 路 监 控
monitoring  Visual management: The voltage, current, load rate, efficiency, and circuit breaker terminal temperature are visual.
 A maximum of 48 IT cabinets are supported.
 2N and N+1 power supply architectures are supported.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – NMW
Item Technical Specifications

Power system 3Ph+N+PE (with an independent copper bar as the PE)

Input switch 250 A/400 A

Standard configuration: 40 A/1P (six switches for each power


Output switch distribution unit)
Optional: 16 A/1P, 40 A/1P, 63 A/1P, 16 A/3P, 40 A/3P

Rated voltage 380 V AC/400 V AC/415 V AC

Cable routing mode Routed in from the end

Cable connection capacity 4 x 185 mm2 + 1 x 95 mm2


Monitoring
port
Circuit breakers operated from the front, cables connected
O&M
from the left, and maintenance performed from the top
Output
branch
Output switch
connector
• Easy capacity expansion: Power distribution units can be directly added to implement online
capacity expansion and capacity change.
• Reliable: A foolproof structure is used with installation position marks and spacing measures, and
Power General can resist earthquakes of up to Mercalli intensity 9.
Busbar distribution unit input unit • Easy to network through an FE port to implement teleindication, telemetering, and teleadjusting.
trunking unit
• Flexible to manage and monitor the PUE and maintenance.
• Intelligently measures electric energy, current, voltage, power factor, total active power, total

End plug apparent power, total reactive power, and neutral wire current; detects terminal temperatures to
reduce power outage and fire risks.

Elbow
Support

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Air Conditioner PDB

Indicator Meter

Cabinet Dimensions
Category Mains Input Branch Output
(H x W x D)
8 x 63 A/3P + 2 x 10 A/1P
Single route: 400 A
Air conditioner + 1 x 32 A/1P
Mains 800 x 600 x 300
input PDB 8 x 63 A/3P + 2 x 10 A/1P
Single route: 250 A
+ 1 x 32 A/1P
Level
C SPD

Mains
output

Lighting
output

 A wall-mounted air conditioner PDB (8 routes) is configured for the N+1 scenario.
 Two wall-mounted air conditioner PDBs are configured for the 2N scenario.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Battery Cabinet

Battery cabinet configuration principles:


Master battery Slave battery
 The battery cabinet dimensions are 600 mm x 1200 mm x 2000 mm. A top frame is required
cabinet cabinet
for a 2200 mm high cabinet.
BCB board  Battery cabinets can be classified into master battery cabinets (with circuit breakers) and
slave battery cabinets (without circuit breakers).
Battery switch  Only the master battery cabinet is configured if the battery capacity is 26 Ah/40 Ah. The
iBOX master and slave battery cabinets are configured if the battery capacity is 65 Ah/100 Ah.
 It is recommended that the backup time be set to 15 minutes and a maximum of four battery
If the battery string is equipped with a slave
cabinets be configured. battery cabinet (no MCCB) and installed at the
side, verify that the side panel is relocated to the
 When the smart module works in 2N mode, batteries need to be configured accordingly. The outer side of the slave battery cabinet. Ensure
that there are panels on the outer side of the
Battery tray battery backup time of each side is calculated based on the half load. master and slave battery cabinets, but no panel
between the cabinets of a single battery string.
 This version supports only Shoto and EnerSys batteries of 26 Ah, 40 Ah, 65 Ah, and 100 Ah.

In the standard version, four side panels are


Battery configured for the master battery cabinet
and no side panel is configured for the slave

Battery Cabinet Capacity cabinet. When 65 Ah/100 Ah batteries are


configured, side panels are configured for
Number of both the master and slave battery cabinets.
Battery Type
Batteries/Cabinet

26 Ah 40
iBattery function description:
 Implements wireless communication with the
40 Ah 40
iBOX.
 Automatically identifies faulty batteries.
65 Ah 20
 Detects the battery voltage, internal resistance,
and pole temperature.
100 Ah 20
 Calculates the battery SOC and SOH.
iBattery  Powers off the battery cabinet in case of fire.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Connecting Cables for Battery Cabinets
26 Ah/40 Ah battery wiring diagram, covering 32 to 40 batteries

The battery wiring diagram covers 32


to 40 batteries in five configuration
scenarios. The battery positions vary
with scenarios. In this case, connect
cables based on the wiring diagram
delivered with the cables.

65 Ah/100 Ah battery wiring diagram, covering 32 to 40 batteries

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – rPDU
No. Specifications BOM Number Configuration Principle rPDU Type

2 PCS/cabinet; configured when the cabinet


1 Single-phase, 32 A, full height 02120837-009 Rack Power Distribution Unit,Basic Type-PDU2000-32-1PH-20/4-B9,20*C13+4*C19,7.3KVA
power is less than or equal to 7 kW.

2 PCS/cabinet; configured when the cabinet


2 Single-phase, 63 A, full height 02120643-002 power is greater than 7 kW and less than or equal Rack Power Distribution Unit,Basic Type,PDU2000-63-1PH-16/8-B1,16*C13+8*C19
to 10.5 kW
2 PCS/cabinet; configured when the cabinet
3 Three-phase, 32 A, full height 02121737-001 power is greater than 10.5 kW and less than or rPDU,Basic Type,PDU2000-32-3PH-12/9-B2,12*C13+9*C19,21kVA
equal to 21 kW

2 PCS/cabinet; configured when the cabinet


4 Single-phase, 32 A, full height 02122280 rPDU,Switch type,MD-1324-2004,20*C13+4*C19, two groups,7.3KVA
power is less than or equal to 7 kW

2 PCS/cabinet; configured when the cabinet


5 Single-phase, 63 A, full height 02122761 power is greater than 7 kW and less than or equal Rack Power Distribution Unit-Input Monitoring Type-PDU2000-63-1PH-18/6-M-14*C13+6*C19-22kVA
to 10.5 kW

2 PCS/cabinet; configured when the cabinet


6 Single-phase, 32 A, full height 02122118 Rack Power Distribution Unit,Basic Type,PDU2000-32-1PH-20/4-B10,20*GB 10A+4*GB 16A,7.3KVA
power is less than or equal to 7 kW

2 PCS/cabinet; configured in the NMW scenarios


7 Single-phase, 63 A, full height 02120643-003 when the cabinet power is greater than 7 kW and Rack Power Distribution Unit,Basic Type,PDU2000-63-1PH-16/8-B2-16*GB 10A+8*GB 16A
less than or equal to 9.25 kW
2 PCS/cabinet; configured when the cabinet
8 Three-phase, 32 A, full height 02121737-002 power is greater than 14 kW and less than or rPDU,Basic Type,PDU2000-32-3PH-12/9-B3,12*GB 10A+9*GB 16A,GB standard,21kVA
equal to 21 kW

Notes:
1. The mounting bracket is not required for the preceding rPDUs in 2000 mm high cabinets, but is required for the
rPDUs in 2200 mm high cabinets.
2. The mounting bracket is required for installing other manually inserted rPDUs. The rPDUs must be installed onsite.
3. Industrial connectors can be selected. For details, see the configuration manual.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Supply and Distribution System – Smart rPDU

Smart rPDU Smart rPDU


1. Single-phase, 7 kW, 20 x C13 + 4 x C19 with the 1. Single-phase, 10.5 kW, 14 x C13 + 6 x C19 with the socket-
socket-level remote power-on and power-off function, level remote power-on and power-off function, supporting
supporting total energy consumption and socket-level total energy consumption and socket-level monitoring.
monitoring. 2. Equipped with a residual current circuit breaker.
2. Equipped with a hydraulic circuit breaker. 3. Connects to the rack environment unit through the RS485
3. Connects to the rack environment unit through the port; delivered with the cable (a non-common network cable
RS485 port; delivered with the cable (a non-common can be used as a substitute).
network cable can be used as a substitute). 4. The ECC can control the socket-level remote power-on and
4. The ECC can control the socket-level remote power-on power-off and set the socket-level overcurrent tripping
and power-off and set the socket-level overcurrent function.
tripping function.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cooling System – Air Conditioner
The cooling subsystem uses two types of DC inverter air conditioners: air-cooled half-sized (NetCol5000-A035) and air-
cooled full-sized (NetCol5000-A050) air conditioners.
Configuration description of air conditioners:
1. Air conditioner configuration quantity: Take the outdoor working condition of 43°C as the standard working condition. Configure outdoor units according The clearance requirements on indoor units:
to different outdoor working conditions.  You are advised to place air conditioners
2. If the highest outdoor temperature exceeds 43°C, reduce the maximum IT load that can be supported in this configuration according to the cooling face to face. Full-sized ones can be placed
capacity attenuation coefficient listed in the following table. alternately.
3. Air conditioner redundancy principles: Provide redundancy of 20% of the air conditioner quantity: N+1 (N < 7); N+2 (N ≥ 7).  If the number of half-sized air conditioners
4. Configuration principle of air conditioners with heating: Two air conditioners with heating and humidification functions are configured inside each module is odd, an adaptive frame is required at the
in standard configuration. Other places are configured with air conditioners without the humidification function. side with fewer units.
(1) In-row precision air conditioner
5. In low-load scenarios, you are advised to configure a dehumidifier in each aisle. (2) Equipment

Netcol5000-A035 and Netcol5000-A050 configuration description


Indoor Unit Outdoor Unit
Cooling
Air Conditioner Type Applicable
Capacity BOM Number Power Supply Pipe Routing Function BOM Number Working Condition
Environment
52274254-003 Single power Cooling only 52273539-005 T1, T1 low temperature Class B
Bottom pipe routing
supply Heating and humidification 52273755-002 T1, including two outdoor units Class B
52274254-002
NetCool5000-A035 35 kW
52274254-001 Dual power Top and bottom pipe Cooling only 52273539-006 T1 Class C
supplies routing
52274254 Heating and humidification 52273539 T1 Class B
T1, T1 low temperature,
52273786 Single power Heating and humidification 52273539-002 Class B
Bottom pipe routing intelligent feature
supply
52273786-001 Cooling only 52273539-005 T1, T1 low temperature Class B

NetCool5000-A050 46 kW 52273788 Heating and humidification 52273539-006 T1 Class C


52273788-001 Dual power Top and bottom pipe Heating and humidification 52273539 T1 Class B
52273788-002 supplies routing Cooling only 52273755-002 T1, including two outdoor units Class B
52273788-003 Cooling only 52273541-005 T3 Class B

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cooling System – Air Conditioner Models
Indoor unit Outdoor unit
Technical specifications of outdoor units
Item NetCol5000-A035H NetCol5000-A050
Item NetCol500-A060 NetCol500-A080 NetCol500-A120
380 V AC/400 V Power supply
380–480 V AC; 50/60 Power supplied by the indoor unit
Power system AC/415 V AC; 50/60 mode
Hz; 3L+N+PE
Hz; 3L+N+PE
–20°C to 45°C (with a low- –20°C to 45°C (with a
Operating
Cooling mode Air cooling temperature low-temperature
temperature –5°C to +55°C
Refrigerant R410A component of –40°C to component –40°C to
range
Cooling 45°C) 45°C)
35 kW 46 kW
capacity Fan speed range 10%–100%

Humidification Number of fans 1 2 2


1.5 kg/h 3 kg/h
capacity
BOM number BOM number
Heating power 4 kW 6 kW 52273539: 1107 (677) x 52273755-002: 1107 (655) x

Airflow mode Horizontal airflow 1356 (1217) x 1094 1356 (1217) x 2188
BOM number
Compressor Dimensions H1 BOM number
DC inverter compressor 52273541-005: 1107
type (H2) x W1 (W2) 52273539-005: 1107 (655) x
(655) x 2186 (2047) x
Fan type EC fan x D (unit: mm) 1356 (1217) x 1094
1094
Air filter G3 G4 BOM number
52273539-006: 1156 (703) x
Air-cooled half-sized Air-cooled full-sized Dimensions (H 1356 (1217) x 1094
inverter air conditioner inverter air conditioner x W x D, mm) 2000 x 300 x 1200 2000 x 600 x 1200 Storage
–40°C to +70°C
Low-temperature temperature

Outdoor unit component Storage humidity 5%–95% RH (non-condensing)


Pipe and cable
Top/Bottom pipe and cable routing
routing IP rating IPX5

Net Altitude 0–4000 m, derated at above 1000 m. For detailed derating data, contact Huawei.
weight/Gross 230 kg/275 kg 350 kg/400 kg
CE, RoHS, RoHS 2.0, REACH, CQC, RoHS, RoHS 2.0,
weight Certification
WEEE REACH, CQC, WEEE
Outdoor –20°C to +55°C
ambient
operating –40°C to +45°C (requiring low-temperature
temperature components)

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cooling System – Low-Temperature Components and Ports

Low-temperature component information Port description for the NetCol5000-A035H/NetCol5000-A050 indoor unit
If the outdoor temperature is lower than the operating temperature range Item Netcol5000-A035H Netcol5000-A050

of a product, the condensing pressure of the outdoor unit may be lower Refrigerant liquid Reserved copper pipe: inner diameter of 5/8 inch, Reserved copper pipe: inner diameter of 5/8 inch,
pipe welded welded
than the safe operating pressure of the compressor, and a low- Refrigerant gas pipe
Reserved copper pipe: inner diameter of 3/4 inch, Reserved copper pipe: inner diameter of 7/8 inch,
welded welded
temperature component must be installed. The low-temperature
Reserved port: BSPP 1/2 inch, threaded
Reserved port: BSPP 1/2 inch, threaded
component supports the outdoor operating temperature of –40°C to connection connection
Water pump Recommended: PVC or PPR pipes, temperature
+45°C. drainpipe
Recommended: EPDM hose or PPR rigid pipe,
resistance of 85°C, pressure resistance of 1–7 kg,
Item Specifications temperature resistance of 85°C, pressure
inner diameter of 19 mm, outer diameter no greater
resistance of 1–7 kg, inner diameter of 12 mm,
BOM number 52271197 than 35 mm
outer diameter no greater than 30 mm

Refrigerant R410A Reserved port: BSPP 1/2 inch, threaded Reserved port: BSPP 1/2 inch, threaded
connection connection
Liquid pipe outer diameter 5/8 inch (15.88 mm) Humidifier water
inlet pipe Recommended: EPDM hose or PPR rigid pipe, Recommended: EPDM hose or PPR rigid pipe,
Gas pipe outer diameter 7/8 inch (22.22 mm) pressure resistance of 1–7 kg, inner diameter of pressure resistance of 0.1–0.7 MPa, inner diameter
12 mm, outer diameter no greater than 30 mm of 12 mm, outer diameter no greater than 16 mm
944 x 632 x 507 (with packaging)
Dimensions (H x W x D, mm) Reserved port: BSPP 1/2 inch, threaded
connection
828 x 470 x 300 (without packaging) Water tank Recommended: PVC or PPR pipes, temperature
N/A
automatic drainpipe resistance of 85°C, pressure resistance of 1–7 kg,
inner diameter of 19 mm, outer diameter no greater
Expansion bolt hole M12x60 than 35 mm

Storage temperature –40°C to +70°C Electric cable port Through hole: φ50 mm Through hole: φ50 mm

ELV cable port Through hole: φ25 mm Through hole: φ25 mm


Storage humidity 5%–95% RH (non-condensing)
Installation mode Installed on a concrete floor or an ESD floor. Installed on a concrete floor or an ESD floor.
Maximum operating pressure 4.35 MPa
Pipes and cables are routed from the top or
Pipe and cable
bottom. Automatic drainpipes can be routed only Top/Bottom pipe and cable routing
routing
from the bottom.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cooling System – Water-Cooled Module Specifications and Ports

Item Specifications

Refrigerant R410A

Liquid pipe outer diameter 5/8 inch (15.88 mm)

Gas pipe outer diameter 7/8 inch (22.22 mm)

Water inlet pipe port G1-1/2 inch internal threads

Water outlet pipe port G1-1/2 inch internal threads

Dimensions (L x W x H) 1510 mm x 262 mm x 530 mm (without packaging)

1637 mm x 434 mm x 743 mm (without packaging)

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Maximum operating pressure 4.35 MPa

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Architecture
 In the single-module scenario, the ECC800 serves as the core management component to manage devices and schedule functions.
25 kW teamwork control wiring 46 kW teamwork control wiring
 In the multi-module scenario, the NetEco is deployed to manage multiple smart modules in a unified manner.
Smart gateway Smart gateway
Monitoring Monitoring Monitoring
Monitoring/Teamwork Monitoring/Teamwork Monitoring/Teamwork
control control control

Air conditioner 1 Air conditioner 2 Air conditioner 3

NetEco Air conditioner 1 Air conditioner 2 Air conditioner 3

Smart module
LAN switch
WiFi Zigbee
ECC800
DO DI
ECC800 PoE bus FE
Socket Socket Socket
TCP/IP RS485
AI/DI
ETH ETH
Zigbee Zigbee Zigbee Zigbee
temperature sensor

Audible and visual

Battery monitor system x n


In-room lighting

Multi-functional sensor x 2
In-room access
In-room video

In-row air conditioner 1

In-row air conditioner n


alarm device
Smoke and

T/H sensor

conditioner
In-room air

Access actuator x 2
VESDA
control
Chiller

Skylight actuator
HVDC

Integrated UPS
UPS

Integrated PDF
PDF

Water sensor
AC actuator
Camera x 2
Busbar

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Functions and Features
Mobile app Dual power supplies PoE bus
Pad app
PoE/Zigbee dual-route backup


Rem
sen ote se
s
and or, sm nse: T
infr o /H Access control management
are ke se

Tele d n
Smart module PUE sky contro sen sor,
ligh l: sor

WiFi hotspot t

iCooling intelligent teamwork control



Battery

Access detection
control and warning
Battery monitoring

Three modules cascaded


Smart module controller

Access control Video access


for a maximum for a maximum
Access control

Camera
of four modules of two modules FusionModule
Peripheral devices of the
smart module

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Feature Description
Category Main Feature Feature Description Customer Benefits

Route backup, which provides high reliability and reduces


Zigbee wireless device access Supports wireless networking for sensors and actuators and provides backup routes to reduce cables.
cabling workload

Local management of smart module access


Supports access control by the facial recognition, card reader, password, and fingerprint. Multiple access control rights, which provide high availability
control
Sending alarm notifications by SMS, enabling remote
SMS message alarm Sends SMS messages based on the alarm severity.
maintenance

Allowing customers to know smart module energy consumption


Smart module PUE display Provides PUE statistics on a dashboard or in curves based on the smart module configuration.
in real time
High efficiency

Enables deployment of both communications cables and power cables, which features abundant bandwidth
PoE bus power supply and communication Good performance and fast deployment
resources and easy deployment.

Intelligently adjusts and controls the air conditioner cooling capacity based on the cabinet temperature and
iCooling management Energy saving and emission reduction
energy consumption changes, saving energy.

Remote upgrade, inspection data export, Provides interfaces for remote upgrade, black box data export, and configuration file import and export,
Good serviceability
and configuration copy facilitating maintenance.

WiFi hotspot Provides local WiFi hotspots, enabling easy mobile phone access management. Wireless access with high availability

Huawei pad is deployed for the smart module. Monitoring information can be viewed or inspected without
Smart module check over pad Query over pad, facilitating O&M
entering the aisle.
Easy to use
Mobile app Apps are installed in mobile phones for query and management. Easy O&M through mobile apps

When a device is connected to the PoE bus, it can be automatically discovered and registered without
Plug-and-play and self discovery Short delivery time and high maintainability
configuration.

Linkage management The lighting and fire extinguishing systems are linked. Linkage rules can be customized. Linkage management and intelligent O&M

AC and DC dual power inputs Supports 220 V AC or 240 V DC power input. Dual power supplies with high reliability
Reliability
Battery monitoring management Monitors the single battery voltage and internal resistance and locates faulty batteries in a timely manner. Real-time monitoring of battery SOH

Northbound interface Supports interworking with the NetEco, allowing centralized management. Centralized management

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (ECC800-Pro)

Ports on the front panel:


1. Silk screens of FE ports: WiFi

WAN_1 (upper left), WAN_2 (lower left), LAN_1 (upper right), LAN_2 SMS Zigbee

(lower right)
2. Silk screens of RS485 serial ports:
COM1/12V (upper left), COM2/12V (lower left), COM3/12V (upper right),
USB DO port FE ports
PSU 1 PSU 2 RS485 ports
AI/DI ports
COM4/12V (lower right)
3. Silk screens of AI/DI and DO ports:
AIDI_1 (upper left), DO (lower left), AIDI_2 (upper right), AIDI_3 (lower ECC800-Pro (front view)
right)
4. Silk screen of the USB port: USB
5. External antenna ports: 3G/4G (left), WiFi (middle), Zigbee and RF
(right)
6. Silk screens of indicators: RUN, ALM, and Zigbee (from top to bottom)

48 V DC output 220 V AC input 2 220 V AC input 1

ECC800-Pro (rear view)

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (Access Actuator)
The access actuator provides access control for Cascading
Installation position: inside the door head
smart module aisles, supporting PoE and Zigbee ports PoE

Installation mode: mounted on the guide rails


dual-route communication.

Port description
AC ac
t u at o r
Skylig
h t a ct
u a to r

Magnetic lock Ports connecting to the Card reader


Acces
switch and supporting fire
s a ct u
a to r
extinguishing linkage

Main Function Function Description

DI detection Three routes to detect the door status sensor, door open button, and fire linkage signals

Wiegand port Two Wiegand ports to connect to two card readers at the same time

DO output One 1.5 A 12 V output to power the electronic door lock

Communication One FE port, one Zigbee wireless port, and one RS485 port. The FE and Zigbee ports are used for backup and the RS485 port is reserved (physical port cascading supported).

DEBUG port One RS232 port

4-pin DIP switch One 4-pin DIP switch, used for setting the board address (1 by default)

Press the button for less than 1 second to start blinking. Hold down the button for 1–5 seconds to search for a network and start networking. Hold down the button for more than 6
Zigbee networking button
seconds to clear Zigbee network parameters.

Access control management Access permission management, access event record, and alarm record

Indicator Four LED indicators on the board

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (Smart ETH Gateway)
Port description Installation position: inside the door head
Installation mode: mounted on the guide rails

AC ac
Cascading the
tuator
To a 53.5 V DC Skylig
power port 48V_PWR port on a ht act
smart gateway uator
To a LAN port Cascading the FE
port on a smart
gateway

To devices such as the IT cabinet Acces


collector, ETH, UPS, FE-port air s actua
conditioner, three-in-one sensor, tor
battery detector, and camera
Smart gateway networking

Item Function Description

Adaptive frame
1 Six-port 10/100M Ethernet switch
IT IT IT IT IT IT
2 Four network ports, supporting IEEE 802.3af/at PSE power supply cabinet cabinet cabinet cabinet cabinet cabinet

Supporting IEEE 802.3af/at for PoE, IEEE 802.3 for 10BaseT, and IEEE 802.3u for
3
100BaseT (X), and IEEE 802.3x for flow control
4 MDI/MDIX automatic interconnection
5 Storage and forwarding functions to ensure adaptivity and data integrity
Battery Battery IT IT IT IT IT
6 Automatic address learning function cabinet cabinet cabinet cabinet cabinet cabinet cabinet

7 IEEE 802.3x full-duplex flow control and forcible half-duplex flow control
8 Cascading port supporting the ring network

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (Smart Module Actuator)

Installation position: inside


the door head
Installation mode: mounted
on the guide rails

Item Specifications
 AC IN: one AC input, 90 V AC to 240 V AC
Power input  48 V DC input: terminal, with an input voltage of 36 V DC to 60 V DC

 AC OUT1: two AC outputs, 90 V AC to 240 V AC. The maximum current of each output is 5 A.
Power output  AC OUT2: one AC output, 90 V AC to 240 V AC. The maximum current is 5 A.

LAN port FE communication with a communications rate of 10/100M


Wireless communications One wireless port that complies with IEEE 802.15.4, mutual backup with FE communication

COM1/COM2: two RS485 ports (one route) with a default communication rate of 9600 bit/s, physical
RS485 serial port port cascading (reserved)
COM3: southbound or northbound communication (reserved)

 Access: One DO output port is used to control the power output of the electronic door lock, and
one DI input port is used to connect to the door status switch. Both ports use terminals.
DO/DI port  Skylight: One DO output port is used to control the power output of the skylight magnetic lock,
and one DI input port is connected to the skylight open button. Both ports use terminals.

DO/12V One DO port with 12 V DC power supply (reserved)

(1) 48 V DC power (2) LAN port (3) RS485 port (4) RS485 port Six AI/DI ports, in which one is for detecting the exit button, two for detecting lighting buttons, and one
AI/DI port
input port COM1/2 (reserved) for detecting fire extinguishing linkage signals. One port is reserved.

Two Wiegand ports, 12 V DC card reader operating power output; two routes of card readers (not
Wiegand port
fingerprint readers) can operate at the same time.
(5) DIP switch (6) AC OUT power (7) Terminal cover (8) AC IN power input
output port port  Press the button for less than 1 second to start blinking.
BLINK button  Hold down the button for 1–5 seconds to search for a network and start networking.
 Hold down the button for more than 6 seconds to clear network parameters.

(9) Fuse (10) DO/DI port (11) DO/12V port (12) AI/DI port Address DIP switch 4-pin address DIP switch (reserved)
Fuse 16 A, 250 V AC
(13) Wiegand port (14) Spare fuse box (15) Indicator (16) BLINK button
Spare fuse box Two 16 A, 250 V AC fuses
E-label Supported

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (ETH Converter)

Installation position: magnetically mounted


Port description
on the cable trough
To the PoE port on a
smart gateway
Installation mode: magnetically mounted
or secured by screws
10/100M Ethernet to RS-485/CANBUS

To devices such as air


conditioners and meters

The ETH converter is required when ports


supporting the Modbus RTU protocol connect to
Main Function Function Description devices over the bus. One ETH converter can
One FE port and one RS485/CAN port (physical port cascading
Communication
supported) connect to only one device using the RTU
DEBUG port One RS232 port
protocol.
Installation mode Magnetically mounted or wall mounted
Indicator Three LED indicators on the board

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (Multi-Functional Sensor)
Installation position: installed on the
control skylight
Installation mode: mounted on the top of
the skylight

Smart ETH gateway

Main Function Function Description


Temperature and
Detects the temperature and humidity.
humidity detection
Smoke detection Detects the smoke density and generates alarms.
One Zigbee wireless port, one RS485 port, and one PoE port. The PoE and Zigbee ports are used simultaneously
Communication for mutual backup. Two RS485 ports are reserved (with 12 V power and supporting physical port cascading). PoE
power supply is supported.
4-pin DIP switch One 4-pin DIP switch, used for setting the board address
Indicator Three LED indicators on the component
Button A Zigbee networking button and a smoke sensor test button
Zigbee networking Press the button for less than 1 second to start blinking. Hold down the button for 1–5 seconds to search for a
button network and start networking. Hold down the button for more than 6 seconds to clear Zigbee network parameters.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring System – Monitoring Component (Smoke Sensor)

The smoke sensor detects the smoke density in the The smoke sensor is powered by the skylight Installation position: installed on the
aisle and generates fire alarms. controller. Alarm signals are reported to the control skylight
ECC800 by the actuator. Installation mode: mounted on the
top of the skylight

Red +12V power


input
Black –GND
Green Common
terminal
Yellow NC terminal
Blue NO terminal

Alarm clearing button


Test button

Main Function Description


Function
Power-on self- System startup and self-check upon
check power-on
Smoke Detects the smoke density and
detection generates alarms.
Two LED indicators on the
Indicator
component
Test button Manual alarm test in operating mode
Alarm clearing
Running in alarm status
button

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Management System – Architecture
NetEco HTTPS
Ethernet
Email Web

Fast Ethernet

SMS Web NVR

Fast Ethernet

Smart Smart
module 1 module N
WiFi

ECC800
平 板 电 脑 /手 机
ECC800

AI/DI DO COM DI

……
智 能 ETH插 座 智 能 ETH插 座
eLight 开窗按钮
水浸传感器 声光告警器
FE

RF_Z(1) RF_Z(1) RF_Z(2) RF_Z(1)


RF_Z(1)

交流执行器 iBOX 摄像机 一体化配电柜/ NetCol5000-A025


门禁执行器 天窗执行器 多功能传感器 一 体 化 UPS
精密配电柜 新干线 NetCol5000-A042

RF_Z(3) RF_Z(3) RF_Z(3)

RF_Z(2)

电磁锁 自动平移门 门 禁 机 出 门 /紧 急 开灯按钮 感烟探 天窗电 iBAT 无线水浸传感器 无线烟雾传感器 无线门磁传感器


测器 磁锁
按钮

The NetEco monitors and manages power, environment, security, and video systems in a unified manner. It can monitor and manage
a single modular and prefabricated data center, or modules or prefabricated data centers in multiple areas in a unified manner.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Management System – Overview NMS/L2 level Service
NMS

Integrated interface
SNMP JSON

Third-party system
Infrastructure Southbound NetEco
interface
Air conditioner
SNMP Building
SNMP
UPS

PDF Fire protection


Modbus
PDU
Security
Camera
YDN Modbus
Access control Power

Smoke sensor

Trouble ticket Energy efficiency


View management Alarm management Report management management
management

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Fire Extinguishing System
Working process of the fire extinguishing
system in an equipment room
Smart module
Description: fire extinguishing Equipment room
system fire alarm
1. The smart module does not contain any fire extinguishing devices. In case of fire, the
monitoring system performs the following actions:
(1) Triggers the alarm beacon to generate an alarm. Smoke sensor or temperature
sensor operating
(2) Opens the skylight, enabling the fire extinguishing system to detect smoke in the aisle.
(3) Reports an alarm to the fire extinguishing system in the equipment room.
Gas fire extinguishing host
2. The smart module skylight controller can receive instructions from the alarm system in the generating an alarm
Reporting the alarm to the
equipment room and open the skylight. management system Manual or remote control

3. An emergency exit button is configured inside the aisle to open the door in case of
emergency. Skylight controller Module alarm beacon

Automatically opening
the skylight

Notes: Smoke and temperature sensors in the Gas release indicator


equipment room operating turning on
 Equipment room fire extinguishing is a delivery item, which needs to be
accepted independently. Equipment room alarm
beacon
 It is recommended that the temperature sensor, smoke sensor, and fire detector Gas fire extinguishing host
Personnel leaving the site and closing
be deployed near the smart module to facilitate the detection and action of the the fireproof door

fire extinguishing system in the equipment room. Closing openings and turning
off ventilation devices and air
Discharging extinguishants conditioners
after 0–30s

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Integrated Cabling System – Architecture
Cabling principles: Electric and ELV cables must be separated and must
not be routed in parallel to facilitate maintenance.

Electric cable trough

ELV cable trough

(1) ELV cable trough (2) Electric cable trough

1. Route electric and ELV cables through holes at the bottom of cable troughs when the
cables are cross-connected.
Optical fiber
2. There are a large number of cables routed on end PDFs. In this case, route cables as
Network cable
shown in the preceding figure. Do not route cables from the bottom.
3. When the number of routed cables is not large (cables of less than 12 IT cabinets are
routed), route cables through skylights, with electric cables on the outer side and ELV
Cable routing plan cables on the inner side. When the number of routed cables is large, add cable trays.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Integrated Cabling System – Cable Routing
Integrated
Light
PDF Lighting actuator
Lamp 1

AC input
Lamp 2
1 LCU

AC input
2
ATS 380 V AC AC

220 V AC
rPDU
1
Cable routing in N+1 configuration Cable routing in 2N configuration
UPS rPDU IT cabinet 1
2
380 V AC
380 V AC
380 V AC 380 V AC
220 V AC 220 V AC
480 V DC rPDU 220 V AC 220 V AC
1 480 V DC 480 V DC
Battery IT cabinet 2
rPDU
A single battery of 2 rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU
12 V 1 2 1 2 1 2 1 2 1 2 1 2
iBattery iBattery iBattery iBattery iBattery

ĂĂ
iBattery iBattery iBattery iBattery
rPDU
1
rPDU IT cabinet 18 iBattery iBattery iBattery iBattery
2
Water sensor Air-cooled Chilled Air-cooled Chilled
Integrated PDF air water air Integrated PDF air water air
Battery cabinet IT cabinet IT cabinet IT cabinet Battery cabinet IT cabinet IT cabinet IT cabinet
Integrated cabling (PDF+UPS) conditioner conditioner (PDF+UPS) conditioner conditioner
Alarm beacon
cabinet 220 V AC cabinet cabinet cabinet cabinet
rPDU 12 V DC
1 iSCAN
rPDU controller IT cabinet
2 monitoring
48 V DC
Skylight
actuator

NetEco server Access


actuator iBOX
iBOX
220 V AC
Busbar branch
monitoring
220 V AC
Light
Light
NVR actuator
actuator
iBOX

Power supply and distribution Camera


Light tube
Light tube
Three-in-one

diagram in N+1 configuration


sensor (infrared/
smoke/temperature/
humidity)
Asile
Busbar branch
Three-in-one
sensor (infrared/smoke/
Access
Camera Skylight
Water Alarm
Asile
monitoring temperature/humidity) control sensor beacon Busbar branch Three-in-one sensor Access Water Alarm
(infrared/smoke/temperature/ Camera Skylight
monitoring humidity) control sensor beacon

12 V DC
Integrated PDF 1 12 V DC
Lighting Light Lamp 48 V DC
Light tube 48 V DC
1 actuator 1 Light tube
Lamp
2 IT cabinet IT cabinet
AC input 380 V AC AC 1 monitoring monitoring IT cabinet IT cabinet
MCCB iSCAN controller (1 U) iBOX
1 LCU monitoring monitoring
iSCAN controller (1 U)
NVR (2 U)
220 V AC NVR (2 U)
UPS 1 rPDU
NetEco server (1 U)
1
IT cabinet 1 NetEco server (1 U)
rPDU
2 Air-cooled Chilled
air water air Air-cooled Chilled
480 V DC IT cabinet IT cabinet IT cabinet IT cabinet Integrated cabling cabinet
conditioner conditioner Integrated PDF air water air
cabinet cabinet Battery cabinet IT cabinet IT cabinet Integrated cabling cabinet
Battery 1
(PDF+UPS) conditioner conditioner
rPDU cabinet cabinet
A single battery 1
of 12 V rPDU IT cabinet 2
2
iBattery
ĂĂ

rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU rPDU
Integrated PDF 2 1 2 1 2 1 2 1 2 1 2
Lighting rPDU
1
rPDU
2
rPDU
1
rPDU
2
rPDU
1
rPDU
2
2 rPDU 220 V AC 480 V DC
1 220 V AC 220 V AC
rPDU IT cabinet 18 380 V AC 220 V AC
2 380 V AC 380 V AC
AC input 380 V AC AC 2
Water sensor
380 V AC
MCCB
2 Integrated cabling
Alarm beacon
cabinet
220 V AC rPDU 220 V AC 12 V DC
UPS 2 1 iSCAN

Cable routing for the air conditioner outdoor unit:


rPDU controller IT cabinet
2 monitoring
48 V DC
480 V DC Skylight
actuator

Battery 2 NetEco server Access

For a 25 kW or 46 kW air conditioner, the outdoor unit is powered by the indoor


A single battery actuator
of 12 V

iBattery Busbar branch


monitoring

NVR
iBOX

Camera unit. The outdoor unit cables are routed along pipes.
Power supply and distribution Three-in-one
sensor (infrared/
smoke/
diagram in 2N configuration temperature/
humidity)

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Site Survey – Installation Environment Checklist
Item Requirement Check Result Item Requirement Check Result
Pre-installed in the equipment room for signal cables and
Cable tray □ Passed □ Failed
power cables

Operating temperature for indoor equipment (including all Power supply 380–415 V AC (±10%); 3Ph; 50/60 Hz □ Passed □ Failed
components): 5°C to 40°C (long term), –5°C to +50°C (short
Environment term); storage temperature: –40°C to +70°C Equipment room: 500 lx
□ Passed □ Failed
requirement Operating temperature for air conditioner outdoor units: –30°C to Lighting Monitoring center: 500 lx □ Passed □ Failed
+45°C (long term); storage temperature: –40°C to +70°C Test area: 500 lx
Humidity: 5% to 85% (long term), 5% to 100% (short term)
pH: 7–8.5
Water source □ Passed □ Failed
Conductivity at 20°C (σ20): 300–1250 μs/cm

Fire protection Indoor gas-extinguishing system □ Passed □ Failed

Floor drain DN50 or larger, made of cast iron or stainless steel □ Passed □ Failed
Standard live load of the main equipment room: 8–12 kN/m2 (If
the battery cabinet is placed inside the module, refer to the The equipment room grounding system must be a TN-S or
standard live load of the main equipment room.) Module TN-C-S system.
Floor load bearing □ Passed □ Failed
Hang load of the main equipment room: 1.2 kN/m2 □ Passed □ Failed grounding Ground bars must be deployed over the cable tray or under
capacity
Standard live load of the UPS room: 8–10 kN/m2 the raised floor.
Standard live load of the battery room: 16 kN/m2
Standard live load of the monitoring center: 6 kN/m2 Condensate drain outlet: for draining condensate from the air
□ Passed □ Failed
conditioner
Cooling port
Humidifier water pipe port: connects to external water pipes to
□ Passed □ Failed
supply water to the humidifier.
2000 mm high cabinet: ≥ 2600 mm; ≥ 2800 mm (NMW scenario)
Equipment room net One LAN switch Ethernet port: connects to the customer
2200 mm high cabinet: ≥ 2800 mm; □ Passed □ Failed □ Passed □ Failed
height subnet to monitor devices inside the module.
≥ 3000 mm (NMW scenario)
Monitoring port One skylight controller dry contact: connects to the fire
extinguishing system to link the fire extinguishing system and □ Passed □ Failed
Height and width of the the skylights.
Height: ≥ 2200 mm
equipment aisle and □ Passed □ Failed
Width: ≥ 1200 mm
door

Floor levelness Allowed deviation: 3 mm/2000 mm □ Passed □ Failed For details about the survey checklist, see the Survey Report.
Elevator bearing capacity: > 2 t
Elevator □ Passed □ Failed
Elevator door size: height > 2100 mm; width > 1500 mm

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Onsite Installation – Installation Process

Onsite installation process


Material stacking and Material receiving Installation tool Training before Installation and Site cleaning after
installation site survey and placement preparation installation guide installation

Perform site survey based Basic installation tools: Emphasize Install the smart Checking the installation:
on the survey guide, Phillips screwdriver; construction safety. module based on the Check whether the cabinets
especially the aisle, door, small-sized flat-head Provide training in process specified in and skylights are properly
elevator, and material screwdriver; the installation the one-page installed, whether gaps
placement plans. open-end wrench; process, installation guide, and between parallel cabinets are
ink fountain or laser documents, and connect cables based even, whether electric and
wire gauge fixtures. on the cabling diagram ELV cables are separately
Provide help- in package 0. routed and tightly bound, and
seeking channels. whether end doors are
smoothly opened and closed.

Package 0 Installation guide

One-page installation guide Layout


Tail frame

Battery Battery IT AC cabinet IT IT IT AC cabinet IT IT


cabinet cabinet cabinet A/C 01 cabinet cabinet cabinet A/C 02 cabinet cabinet

Enclosure Enclosure
frame frame

Control
skylight

Enclosure Enclosure

Fixtures
frame frame Skylight controller

Integrated
Battery Battery IT AC cabinet IT IT IT AC cabinet IT
cabling
cabinet cabinet cabinet A/C 03 cabinet cabinet cabinet A/C 04 cabinet
cabinet

Tail frame

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Onsite Installation – Key Points
Installation precautions
1 Place materials 2 Provide installation
in sequence,
1. Place materials in sequence. which greatly guide and tools to
reduces material improve efficiency.
2. Correctly use package 0 and the one-page installation guide. searching time
by more than
3. Use an ink fountain or laser wire gauge to mark installation 60%.

baselines.
4. Use marking-off templates to drill holes on the ground.
5. Level cabinets. Ink compression cotton
3 by opening the cover.
6. Use fixtures to adjust the aisle distance.
7. Install tail and enclosure frames (remove accessories and install
foolproof devices and ground cables). Pull out the ink
Leveling precautions: 5
line. Movable. Rotate the cover  Adjust the height.
8. Install and level aisle doors and adjust gaps between doors. to replace the line. Spool
Mark installation borders according to the  Level four angles.
9. Connect cabinet cables based on the cabling diagram for PDF cabinet installation guide.  Check height

power cables. consistency.


4 Provide
 Adjust gaps between
10. Connect signal cables based on the cabling diagram and cable list
guidance for parallel cabinets.
in package 0. drilling holes
onsite to
11. Sort cables and ensure that power cables and signal cables are improve
installation
efficiency.
6
not tangled.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Contents
1. Huawei Data Center Solution Portfolio
2. Version Evolution of the Smart DC and Smart Module
3. SmartDC V100R021C00 Smart Module System Introduction
4. SmartDC V100R021C00 Smart Module Site Survey Checklist
5. SmartDC V100R021C00 Smart Module Onsite Installation
6. Edge DC System Introduction and Installation

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Edge DC System Introduction – FusionModule500

ECC800-Pro Item 42 U

Cabinet dimensions (H x W x D, mm) Converged cabinet: 2000 x 600 x 1350

PDB Installation scenario Supports only a single cabinet.

Lithium battery The cabinet provides 42 U available space.


UPS The mounting bars are adjustable, and space
Installation space
is reserved at the rear of the cabinet for
installing half-height rPDUs vertically.
2000 mm

Built-in fire
extinguishing system 6 kVA UPS

Power distribution rPDU: half-height vertical rPDU

Lithium battery: 100 Ah/48 V DC


Lithium battery
module Operating temperature Indoor: 0°C to 40°C; outdoor: –20°C to +45°C

Operating humidity 5%–95% RH

IP rating IP20
Rack-mounted
Maximum power of a single cabinet 3 kW
cooling system
Installation mode Installed on a concrete floor or an ESD floor

≤ 1000 m (derated when the altitude ranges


1 35 Altitude
0m from 1000 m to 4000 m)
m
600 mm

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Edge DC System Introduction 2000- FusionModule800BC1 Lithium Battery
Type Item Specifications
Input voltage range 342–456 V
Power supply
Input frequency 50/60 Hz (±3 Hz)

 Normal temperature and low


IT load power temperature: 8.5 kW
 High temperature: 7 kW
Power
Maximum power  Normal temperature and low
consumption per IT temperature: 7 kW
cabinet  High temperature: 6 kW

Single route Supported


UPS model UPS2000-G-6 kVA
Power supply and
Power supply Normal temperature: N
distribution mode
mode
380 V/400 V/415 V; 50/60 Hz;
Power system
3Ph+N+PE

Input voltage range 187–264 V AC, 1Ph


PDU2000
Maximum input current 32 A
(1) Indicator module (2) UPS2000 (3) Power distribution
module
(4) ECC800-Pro (5) Control unit for the (6) Indoor unit of the
smart cooling product smart cooling product

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Power Distribution System – UPS + Lithium Battery
ESM-48100B1 Technical Specifications
UPS2000-G Technical Specifications
Positive electrode materials LFP
Rated capacity 6 kVA
Nominal voltage 48 V DC
Number of phases Single phase
Rated charge voltage 53.5 V DC

Input power factor ≥ 0.99 Maximum charge/discharge


100 A /100 A at 35°C
current

Output power factor ≥ 0.9 Maximum charge/discharge


4800 W
power

Rated input voltage 220 V AC/230 V AC/240 V AC Cycle life 3500 cycles at 0.5C, 85% DOD, 70% EOL, 35°C

Standard capacity 100 Ah at 0.2C, 35°C (4800 Wh at 0.2C, 35°C)


Input voltage range 110–280 V AC; < 176 V AC: derated; 110 V AC: 50% load Weight About 43 kg

Specifications (H x W x D) 130 mm x 442 mm x 396 mm (excluding mounting ears)


Rated input frequency 50 Hz/60 Hz
Self-discharge rate at 25°C < 5% (stored for 90 days)

 50 Hz: 46–54 Hz Communications port CAN/RS485 port


Input frequency range
 60 Hz: 56–64 Hz Maximum number of parallel
RS485 port: 16
ESMs

Maximum power of parallel


24 kW
Output frequency range 50 Hz±0.5% ESMs

(1) LCD (2) Maintenance bypass (MBS) port (3) BMS ports Wiring terminal M6, torque: 4 N·m

(4) RS232 communications port (5) RS485 communications ports (6) USB port (protected by a security Installation mode Installed in a 19-inch rack
(connect to northbound devices) protection mechanism) Normal mode: 93% (online mode)
Peak efficiency Overtemperature protection, overcurrent protection, short
(7) AC input and output terminals
(behind the cover)
(8) Battery input terminal (behind the
cover)
(9) 48 V DC output terminal (reserved) Normal mode: 90% Protection function circuit protection, overcharge protection, and overdischarge
protection
(10) Parallel current equalization ports (11) EPO ports (12) Parallel communications ports
(only for parallel UPSs) (only for parallel UPSs) Storage temperature② 0–40°C
Dimensions (H x W x D) 130.8 mm x 438 mm x 420 mm
Transportation temperature –40°C to +60°C

Weight 15 kg
Operating temperature③ Charge: 0–45°C; discharge: –20 to +45°C

Relative humidity 5%–95%

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Cooling System
Item Split-type air conditioner

Power system 220–240 V AC, 50 Hz, 1Ph

Refrigerant R410A

Cooling capacity 3.5 kWa

Airflow mode Front air supply and rear air return

Maximum air volume 600 m3/h

Power supply Single power supply

Dimensions (H x W x D)b 223 mm x 442 mm x 800 mm

Indoor unit: < 40 kg


Weight
Outdoor unit: < 50 kg

Servers, Indoor unit: IP20


batteries, and IP rating
UPSs Outdoor unit: IPX4

a: The cooling capacity is obtained when the indoor dry bulb temperature is 37°C, the indoor wet bulb
temperature is 24°C, and the outdoor dry bulb temperature is 35°C. The actual cooling capacity varies
Air depending on the indoor and outdoor ambient temperatures and relative humidity.
conditioner

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Monitoring Management System
 Monitoring functions
Server  Temperature and humidity monitoring: detects and collects statistics on the
ambient temperature and humidity inside the smart module.

Water sensor
LAN switch  Water leakage monitoring: detects water leakage at the bottom of the smart

Smoke sensor

SPD
module and provides real-time alarm signals.
T/H sensor
1
T/H sensor
2
 Smoke monitoring: detects smoke in the smart module and provides real-
Rack-mounted air time alarm signals.
conditioner
 Power distribution monitoring: monitors the UPS input voltage, frequency,
and current.
 Smart cooling product monitoring
 Video surveillance
 App view
WiFi module

extinguishing system
Generates a 2.5D layout diagram that matches the actual layout of the

Smart spring lock 1


Rack-mounted fire
smart module.

UPS
PAD  Displays the real-time status monitoring data and alarms of the aisle
temperature and humidity on the floor plan.
Smart spring lock 2  Supports facial recognition on the pad app.
Fe-lithium battery  Allows you to open the cabinet door on the corresponding screen after
logging in to the app installed on the pad.
 Linkage control
 Supports the linkage logic of aisle smoke alarms or high temperature
alarms. By default, the cabinet doors are opened through linkage.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Edge DC Installation
1 Installing a Cabinet 3 Exhausting Nitrogen from the Indoor Unit
1. Determine the cabinet position based on the engineering layout diagram. 2. Loosen the needle valve nut, connect a rubber hose
1. Open the gas pipe stop valve of the indoor unit.
2. Place the end cabinet at the correct installation position. and a pressure gauge, and slowly exhaust nitrogen.
3. Level the cabinet using a wrench. 3. After the airflow sound disappears, reinstall the needle
valve nut.

• Use a measuring tape to check that the


vertical distance between the top of the
2000 mm high cabinet and the floor is
2000 mm (+3 mm). Then use a level to
check that the cabinet is level.
• Do not remove the anchor bolts.
Otherwise, rework is required if the
cabinet height does not meet
requirements.
(1) Pressure gauge (2) Gas pipe needle valve
(3) Liquid pipe needle valve

4 Installing an Outdoor Unit

• To avoid fire disasters, install an outdoor unit in a dry and well-ventilated place without flammable gas leakage.
• Select a place away from direct sunshine and radiation from other heat sources. If the sunshine or heat radiation cannot
be avoided, cover the outdoor unit.
• Do not install an outdoor unit in a place with much salt or corrosive gas.
• When installing the outdoor unit, ensure that the air intake vent and air exhaust vent of the condenser are not dirty or
2 Installing an Indoor Unit blocked. Install an outdoor unit in clean areas that are away from residential areas.
• At a high place with strong winds, install the outdoor unit against a wall to ensure the normal operating of fans. Install
1. Remove filler panels. baffle plates when necessary to prevent wind from blowing down the outdoor unit.
• Try to install an outdoor unit against a wall. If the site conditions cannot meet the requirements and the local outdoor
2. Push the indoor unit into the bottom of the cabinet along the guide rails. temperature may be below –10°C, prepare and install an air baffle by referring to the space requirements. The air baffle
height and width should be greater than or equal to the outdoor unit height and width, respectively.
• If the site installation environment is complicated and the preceding conditions are not met, contact Huawei technical
support.

Space Requirements The distance between the


cabinet and the wall is greater
than 300 mm.

The distance between the The distance between the


cabinet and the wall is greater cabinet and the wall is greater
than 300 mm. than 500 mm.

Air exhaust side: > 2000 mm Air intake side: > 150 mm

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


6 Installing Monitoring Devices
Edge DC Installation 6.1 Installing the SIM Card and Antenna
6.4 Routing a Cable to a WLDS900 Water Sensor
1. Remove the ECC800 main control module.
2. Install a SIM card.
3. Attach the antenna to the middle of the
5 Installing Power Supply and Distribution Devices
cabinet top. Ensure that the water detection cable has no contact with

5.1 Installing Lithium Batteries 12.1


5.2 (Optional) Installing Busbars
4. Connect the antenna cable. metal. Otherwise, a false alarm will be generated. Take

protective measures when routing the water detection

1. Push a lithium battery onto the guide rails, and cable.

secure the battery to the mounting bars of the


cabinet using mounting ears and screws.

The water detector is bound to the 5 U


position on the left mounting bar of the
cabinet rear door.

6.2 Installing a Pad

5.3 Installing the PDU2000 1. Adjust the pad mounting support to match the dimensions of the pad to be installed.
2. Remove the nuts from the pad mounting support and install the support.
3. Route the pad power cable through the cable hole and connect the cable.
4. Clamp the pad.
5. Connect the ECC800 USB cable to the charging port on the pad.

Adjusting
screws

6.3 Installing T/H Sensors

1. Unpack the two T/H sensors and attach them to the posts on the front and rear doors of the cabinet.
2. Connect the T/H sensor monitoring cables to connect the T/H sensors to the NetCol control unit in series.

• The installation positions of the T/H sensors can be adjusted as required.


• The default device address is 1.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Edge DC Installation 4 Connecting Cables Between Lithium Batteries and the UPS 5.3
Connecting a Cable to a WLDS900
Water Sensor
System Cabling 1.
1. Connect cables between lithium batteries and busbars. 2. Connect cables between the busbars and the UPS.
Connect one end of the network cable that has been routed to the water detector to the AIDI_2 port on

the ECC800.

1 Grounding the Smart Module

2 Connecting the Power Cables of the Cabinet


Top Cabling Bottom Cabling

Connecting Cables to the Management System


5.4 Connecting T/H Sensor Cables
5
5.1 Connecting Cabinet Electronic Clasp Lock Cables 1. Connect the OUT port on the T/H sensor on the front door to the

RS485_IN port on the T/H sensor on the rear door in series.

Cabinet electronic clasp lock

Connect input power cables to the PDU. Connect input power cables to the PDU.
Connect one end of a network cable to the
Cabinet
3 Connecting PDU2000 Power Cables RS485_IN port on the electronic clasp lock
on the front door of the cabinet, and
connect the other end to the COM2 port on
the ECC800-Pro. Connect one end of
another network cable to the OUT port on
the electronic clasp lock on the front door of
the cabinet, and connect the other end of
the network cable to the RS485_IN port on
the electronic clasp lock on the rear door of
(Front) the cabinet.

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


60
Recommendations
Sales bookshelf: http://3ms.huawei.com/hi/index.php?app=group&mod=Core&act=showSectionData&gid=2031921&id=1447547

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Recommendations
Top-quality bookshelf: http://3ms.huawei.com/mm/msl/documentList.do?method=getTopicDocDetails&topic_id=1000420

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Recommendations

App Enterprise WeChat Carrier WeChat

Copyright © Huawei Technologies Co., Ltd. All rights reserved.


Thank You