Types of Busbar Scheme
Types of Busbar Scheme
1.SINGLE BUS
2.MAIN BUS AND TRANSFER BUS
3.DOUBLE BUS DOUBLE BREAKER
4.DOUBLE BUS SINGLE BREAKER
5.RING BUS
6.BREAKER AND HALF
TYPES OF BUSBAR SCHEME
1.Single Bus
As the name implies, the single bus substation configuration consists of all circuits connected to
a main bus. A fault on the bus or between the bus and circuit breaker will result in an outage of
the entire bus or substation. Failure of a single circuit breaker will also result in an outage of the
entire bus.
Maintenance of any circuit breaker requires shutdown of the corresponding circuit/line and
maintenance of the bus requires a complete shutdown of the bus. A bypass switch across the
breaker should be used for maintenance of the corresponding breaker. Circuit protection is
disabled in this case.
The single bus substation configuration is the simplest and least expensive of all configurations.
This configuration requires less installation area and it can be easily expanded.
Single bus configurations are not considered reliable systems and they should only be
implemented in substations where high reliability is not required, such as large transmission
yards. Reliability and availability of this system can be improved by expanding and
sectionalizing the bus.
TYPES OF BUSBAR SCHEME
TYPES OF BUSBAR SCHEME
In the main and transfer bus configuration, the protective relay scheme is quite
complex due to the requirement of the tie breaker to handle each situation for
maintenance of any other circuit breaker. This bus scheme is more costly than the
single bus configuration but is more reliable and can be easily expanded.
The switching procedure is complicated for maintenance of any circuit breaker.
Failure of a breaker or fault on the bus results in an outage of the whole
substation.
TYPES OF BUSBAR SCHEME
TYPES OF BUSBAR SCHEME
5.Ring Bus
In the ring bus configuration, as the name implies, the circuit breakers are connected to form
a ring, with isolators on both sides of each breaker. Circuits terminate between the breakers
and each circuit is fed from both sides.
This scheme has good operational flexibility and high reliability, any of the circuit breakers
can be opened and isolated for maintenance without interruption of service.
If a fault occurs in this configuration, it is isolated by tripping a breaker on both sides of the
circuit. By tripping two breakers, only the faulted circuit is isolated while all the other
circuits remain in service.
The main disadvantage of the ring bus system is that if a fault was to occur, the ring is split
which could result into two isolated sections. Each of these two sections may not have the
proper combination of source and load circuits, this can be somewhat avoided by connecting
the source and load circuits side by side.
TYPES OF BUSBAR SCHEME
Ring bus schemes can be expanded to accommodate additional circuits, but its
generally not suited for more than six. Careful planning should be used with this
scheme to avoid difficulties with future expansion.
TYPES OF BUSBAR SCHEME
TYPES OF BUSBAR SCHEME
If a middle circuit breaker fails, the adjacent breakers are also tripped to interrupt
both circuits. If a breaker adjacent to the bus fails, tripping of the middle breaker
will not interrupt service to the circuit associated with the remaining breaker in
the chain.
Only the circuit associated with the failed breaker is removed from service. The
breaker and half configuration is very flexible, highly reliable, and more
economical in comparison to the Double Bus Double Breaker scheme.
Protective relay schemes in this configuration are highly complicated as the
middle breaker is associated with two circuits. It also requires more space in
comparison to other schemes in order to accommodate the large number of
components.
TYPES OF BUSBAR SCHEME