Standard Boiler Operation Course
Standard Boiler Operation Course
COURSE
BY LERRAVALE
ENGINEERING
compiled by R.HOVE
Course objectives
• 1) To achieve low fuel costs
• 2) To achieve low maintenance costs
• 3) To achieve low downtime and
factory/production loss
• 4) To reduce dangerous and expensive
accidents
• 5) To achieve reduced air pollution
• 6) To achieve a well run boiler plant
A boiler
• Definition
• A boiler is a pressure vessel designed to generate
steam at a pressure above atmospheric
• Or
• A boiler is a closed vessel in which water, under
pressure is transformed into steam by the application
of heat. In the furnace, the chemical energy in the
fuel is converted into heat, and it is the function of
the boiler to transfer this heat to the water in the
most efficient manner
A boiler
• INPUTS OUTPUTS
1)feed water Steam
2)Fuel
3)Air
4)Chemicals Effluent
Blowdown
• Refuse
(Ash)
Boiler types
• 1) Fire tube/shell boiler
• Is one of the of the most basic type of boiler.
• In the fire tube boiler, the fuel is burnt inside a furnace.
• The hot gasses produced in the furnace then pass
through the fire tubes
• The fire tubes are immersed in water inside the main
vessel of the boiler
• As the hot gasses are passed through these tubes, the
heat energy of the water surrounds them
• As a result steam is generated in the water.
Fire tube boiler
2) Water tube boiler
• Event
• Boiler water level has reached lowest legal water level
(LLWL)
• The ID and FD and stoker trip out/stop
• The low water siren and low water lamp on
• The feed pump running
• Possible damage
• Collapsed boiler flue due to water starvation
• Damaged guillotine door due to fire burn back
• Damage stoker due to stand still
Procedure
• Close the main steam stop valve immediately
• Remove the stoker movement indicator disc and move
forward 8 times away from the guillotine door
• Change over to the other feed pump if this fails
• Call the supervisor
• Between the two of you try to restore water level
within 15mins
• If water level is not restored within 15mins remove fire
from the boiler
• Record the event in a log book
3:Extra low water and boiler fails to trip out
• Event
• Boiler water at LLWL
• ID and FD fans running
• Low water level siren not sounding
• Possible damage
• Damage boiler flue and tubes due to water
starvation
• Damage to guillotine door due to collapsed boiler
flue
Procedure
• Stop the ID and FD fans
• Close the main steam stop valve immediately
• Close the feed check valve
• Close the coal cutoff door and spill door
• Open the guillotine door fully
• Remove the fire from the boiler
• Record the event in a log book
4:Shear pin breaks
• Event
• Stoker stops
• ID and FD fans running
• Possible damage
• Damage to guillotine door due to fire burn
back
• Damage to stoker due to stand still
Procedure
• Event
• Damper control motor fail
• Procedure
• Change over boiler control to manual control
Shutting down boiler on normal
circumstances
• Objectives
• To avoid wasting fuel
• To avoid sudden cooling of the boiler
Procedure
• 30 minutes before steam demand stops altogether do as
follows:
• Reduce stoker speed to minimum
• Close the coal cut off door
• Reduce coal bed thickness by every 8 turns of the stoker
movement indicator disc until it is down to 25mm
• When the last coal is about to pass under the guillotine door,
• Stop the ID and the FD fans
• Close the main steam stop valve
• Speed up the stoker to clear the grate
• When the grate is clear, stop the stoker
• Raise the guillotine door fully and remove any
clinker build up on the sides of the ignition
arch
• Clear the ashpot
• Raise water level to 100mm above normal and
close the feed check valve
• Switch off power on the control panel
• The order of starting the stoker, FD and ID
• Start the ID fan, followed by the FD fan and the
stoker last
• The ID fan is started first in order to create
suction in the furnace
• The FD fan is then started so as to supply air for
combustion and to balance the draught
• The stoker follows last to supply fuel, so that
combustion continues to take place
Placing the boiler on standby
• Definition
• Boiler standby means putting a boiler in a
position which allows it to resume operation
within 30mins
• Procedure
• Stop the ID and FD fans
• Reset the stoker speed to minimum
Diagnosing problems and following the
correct remedies
• Objectives
• To prevent a problem from degenerating into an
emergency
• 1) Runaway fire
• A run away fire is a fire bed igniting at a distance
greater than 50mm from the guillotine door
• Causes of run away fire
• a) Stoker speed too high
• b) Suction in the furnace being too high
• c) Coal bed too low for steam demand
• d) Coal bed with low volatile content
• e) Coal size too big/small with a lot of dust
• f) using smalls coal which is too wet
• g) Undergrate damper not set according to the
length of fire
• h) Coal segregation
Remedies