Load Frequency Control
Load Frequency Control
VIGNAN’S
Institute of engineering for women
LOAD FREQUENCY
CONTROL
Presented by
Dr.B.T.RAMAKRISHNA RAO
Assoc.Professor
Department of EEE
RECAP
Hydrothermal Scheduling
Unit Commitment
OBJECTIVE
Modeling of Turbine
OUTCOME
N
W E E
Factors that led to the initiation of the Grid Disturbance on 30th & 31st July, 2012
Weak Inter-regional Corridors due to multiple outages: The system was weakened by multiple
outages of transmission lines in the WR-NR interface. Effectively, 400 kV Bina-Gwalior-Agra (one
circuit) was the only main AC circuit available between WR- NR interface prior to the grid
disturbance.
High Loading on 400 kV Bina-Gwalior-Agra link: The over drawl by some of the NR utilities,
utilizing Unscheduled Interchange (UI), contributed to high loading on this tie line.
Inadequate response by SLDCs to the instructions of RLDCs to reduce over drawl by the NR
utilities and under drawal/excess generation by the WR utilities.
Loss of 400 kV Bina-Gwalior link: Since the interregional interface was very weak, tripping of 400
kV Bina-Gwalior line on zone-3 protection of distance relay caused the NR system to separate
from the WR. This happened due to load encroachment (high loading of line resulting in high line
current and low bus voltage). However, there was no fault observed in the system.
Department of Electrical & Electronics Engineering
Course : Power System Operation & Control
Unit – 3 :: Load Frequency Control
VIGNAN’S
Institute of engineering for women
Brief Sequence of Events leading to the Grid Collapse on 30th and 31st July 2012
On 30th July, 2012, after NR got separated from WR due to tripping of 400 kV Bina-
Gwalior line, the NR loads were met through WR-ER-NR route, which caused
power swing in the system. Since the center of swing was in the NR-ER interface,
the corresponding tie lines tripped, isolating the NR system from the rest of the
NEW grid system. The NR grid system collapsed due to under frequency and further
power swing within the region.
On 31st July, 2012, after NR got separated from the WR due to tripping of 400 kV
Bina-Gwalior line, the NR loads were met through WR-ER-NR route, which caused
power swing in the system. On this day the center of swing was in the ER, near ER-
WR interface, and, hence, after tripping of lines in the ER itself, a small part of ER
(Ranchi and Rourkela), along with WR, got isolated from the rest of the NEW grid.
This caused power swing in the NR- ER interface and resulted in further separation of
the NR from the ER+NER system.
Subsequently, all the three grids collapsed due to multiple tripping attributed to
the internal power swings, under frequency and overvoltage at different places.
The WR system, however, survived due to tripping of few generators in this
region on high frequency on both the days.
The Southern Region (SR), which was getting power from ER and WR, also
survived on 31st July, 2012 with part loads remained fed from the WR and the
operation of few defense mechanisms.
On both the days, no evidence of any cyber attack has been found by the committee
Department of Electrical & Electronics Engineering
Course : Power System Operation & Control
Unit – 3 :: Load Frequency Control
VIGNAN’S
Institute of engineering for women
Steam
Lower
Speed changer
B C D
Raiser l2 l3 E To Turbine
l1
l4
A Steam valve
Pilot valve
Hydraulic amplifier
Hydraulic amplifier
Linkage mechanism
Speed changer
Linkage mechanism:
ABC is a rigid link pivoted at B, CDE in another rigid link pivoted at D.
This link mechanism provides a movement to control value in
proportion to the change in speed.
Speed Changer:
It provides a steady state power output setting for the turbine.
Its downward movement opens the upper pilot value so that more
steam is admitted to the turbine under steady state condition.
The reverse happens for upward movement of speed changer.
Speed Governor
The governor compensates for changes in the shaft speed
Changes in load will eventually lead to a change in shaft speed
Change in shaft speed is also seen as a change in system frequency
Turbine model
The prime mover driving a generator unit may be a steam turbine or a hydro
turbine.
The models for the prime mover must take account of the steam supply and
boiler control system characteristics in the case of steam turbine on the penstock
for a hydro turbine
The dynamic response of steam turbine in terms of changes in generator power
KT / (1+S TT )
amount ΔPG .
The net surplus power (ΔPG - ΔPD ) will be absorbed by the system in two ways.
By increasing the kinetic energy in the rotor at the rate
As the frequency changes, the motor load changes being sensitive to speed, the rate of
change of load w.r.t frequency f
D can be treated as constant for small changes in frequency & (δPD / δf) Δf = D.Δf
Department of Electrical & Electronics Engineering
Course : Power System Operation & Control
Unit – 3 :: Load Frequency Control
VIGNAN’S
Institute of engineering for women
2 H Pr d
PG p.u PD p.u . f Dp.u.f
f 0 dt
𝛥 𝑃𝐷 ( 𝑠 )
𝛥 𝑃𝐺 ( 𝑠 ) - 𝐾𝑝𝑠 𝛥 𝐹 (𝑠 )
+
( 1+𝑠 .𝑇𝑝𝑠 )
Kps
F s [PG s PD s ]
(1 s.Tps )
-
Department of Electrical & Electronics Engineering
Course : Power System Operation & Control
Unit – 3 :: Load Frequency Control
VIGNAN’S
Institute of engineering for women
Speed-load characteristics
THANK YOU