Chapter5 2way Slabs
Chapter5 2way Slabs
AHMAD MALKAWI
DESIGN OF 1
REINFORCED
CONCRETE II
(RCII)
Chapter 5
Design of Two-way Slabs
Two-way Slabs
Deflect occurs in two directions, and the loads are transferred to all
four supports.
Slab should be supported on all four sides and the ratio of the long
side to the short sides . (The slab have almost a squared shape).
The bending moments and deflections in such slabs are less than
those in one-way slabs; the same slab can carry more load when
3
RC1 By Dr. Ahmad Malkawi supported on four sides.
5.1.1 Classification of
Slabs Based on Load-
Transfer Direction
4
RC1 By Dr. Ahmad Malkawi
Flat Plate
Is a 2-way slab system
consisting of a uniform slab that
5.1.2 Types rests directly on columns and
does not have beams or column
of Two-way capitals.
Slabs The column tends to punch
through the slab. Therefore, a
general increase in the slab
thickness is required or special
reinforcement is used.
Commonly used where spans
are not large and loads not
particularly heavy.
Advantages: Low-cost formwork,
Exposed flat ceilings, Fast
Disadvantages: Low shear
capacity, Low Stiffness (notable
deflection) 5
RC1 By Dr. Ahmad Malkawi
Flat Slabs
Is a 2-way slab reinforced in 2
directions that usually does not
have beams or girders, the
loads are transferred directly to
the columns.
The column tends to punch
5.1.2 through the slab, which can be
Types of treated by the use of:
1.Drop panel
Two-way 2.Column capital (not
Slabs common).
3.Drop panel and a column
capital.
Advantages: Low-cost
formwork, Exposed flat ceilings,
Fast
Disadvantages: Need more
formwork for capital and panels 6
RC1 By Dr. Ahmad Malkawi
Two-way Ribbed (Joist) or Waffle Slabs
• It consists of a floor slab, usually 50-
100mm thick, supported by reinforced
concrete ribs (or joists).
• The ribs are spaced at about 50-75cm
and are supported on beams that rest on
columns.
• Ribbed slabs can be used as one-way
and two-way slabs:
• One-way: If the ribs are provided in two
5.1.2 Types of directions and , OR ribs are provided in
only one direction regardless of the
Two-way ratio.
Slabs • Two-way: If the ribs are provided in two
directions and .
• As in flat plates, shear can be a problem
near columns. Consequently, waffle
floors are usually made solid in those
areas to increase shear resistance.
5.1.3 Flat Slabs: Most suitable for spans of 6-9m and for live loads of 4-7 kN/m 2.
Economical They need more formwork than flat plates, especially for column capitals.
Choice of Waffle Slabs: Suitable for spans of 9-15m and live loads of 4-7 kN/m2. They
carry heavier loads than flat plates and have attractive exposed ceilings.
Concrete Formwork, including the use of pans, is quite expensive.
One-Way Joist Slab: Most suitable for spans of 6-9m and live loads of 4-6 kN/m 2.
Floor Because of the deep ribs, the concrete and steel quantities are relatively low, but
expensive formwork is expected. The exposed ceiling of the slabs may look attractive.
Systems Slabs on Beams: Suitable for spans between 6-9m and live loads of 3-5
kN/m2. The beams increase the stiffness of the slabs, producing relatively
low deflection. Additional formwork for the beams is needed.
One-Way Slabs on Beams: Suitable for spans of 3-6m and a live load of 3-5
kN/m2. They can be used for larger spans with relatively higher cost and
higher slab deflection. Additional formwork for the beams is needed.
RC2 By Dr. Ahmad Malkawi 8
A theoretical elastic analysis of two-way slabs is a very complex because of
their highly indeterminate nature.
5.2 Numerical techniques such as finite elements are required, such methods
require sophisticated software to be practical in design.
Analysis The empirical methods described in this chapter can be done by hand or
with simple spreadsheets.
Slabs
The total amount of reinforcement in a slab seems more important than
its exact placement.
If the supporting edge beams are shallow or are omitted as they are for
flat plates and flat slabs, deformation of the slab system along the column
lines significantly alters the distribution of moment.
the ACI • Method uses a set of coefficients to determine the design moment.
• The method involves a single-cycle moment distribution analysis based on (a)
Code the estimated flexural stiffnesses of the slabs, beams (if any), and columns
and (b) the torsional stiffnesses of the slabs and beams (if any) in the
transverse direction.
Equivalent Frame Method (EFM)
• A 3D building is divided into a series of 2D equivalent frames by cutting the
building along lines midway between columns.
• The resulting frames are considered separately in the longitudinal and
transverse directions of the building and treated floor by floor.
• The same stiffness values used for the DDM are used for EFM.
• This method is very satisfactory for symmetrical frames as well as for those
EFM with unusual dimensions or loadings.
of Two-way • In all cases, the minimum thickness must not be less than:
Without drop panels → 125mm & With drop panels → 100 mm
Slabs 5.4.2 Slabs with Beams on All Sides
17
RC2 By Dr. Ahmad Malkawi
5.4
Minimum
Thickness of
Two-way
Slabs
19
RC2 By Dr. Ahmad Malkawi
5.4.1 Effective
Beam and Slab
Sections for
calculation of a
α Figure 13.10: Portion of slab to be included with beam
• If beams are presented, due to its greater stiffness, its moment portion will be
larger, and the slab moments must be correspondingly less.
• In the case of monolithic construction, beams are defined to include that part of
the slab on each side of the beam extending a distance equal to the projection of
the beam above or below the slab (whichever is greater) but not greater than 4
times the slab thickness.
RC2 By Dr. Ahmad Malkawi 20
5.4.2 ACI • To find h using the previous Equations, at discontinuous edges, for the
edge beam ; otherwise, h must be increased by at least 10% for the
Code panel with the discontinuous edge.
• When drop panels are used without beams, h may be reduced by 10%.
limitations The drop panels should extend in each direction from the centerline of
support by ≥1/6 span length in that direction and also project below
on Slab the slab by ≥ h/4. This reduction is included in Table 9.5(c).
Thickness • The thickness of two-way slabs shall not be less than the following:
1. For slabs without beams or drop panels → 125mm
2. For slabs without beams but with drop panels → 100mm
3. For slabs with beams on all four sides with 90mm
4. For slabs with beams on all four sides with →125mm
• The thickness of a slab also may be governed by shear.
Corner Panels
Slab thickness, from table for fy = 420 MPa and no edge beams
Interior Panels
Slab thickness, from table for fy = 420 MPa and no edge beams
for
The floor system consists of solid slabs and beams in two
Example – α directions supported on 50 cm square columns. Determine the
minimum slab thickness required for an interior and exterior
calculations panels. Use fc = 28 Mpa, fy = 420 MPa, and E=4700√28=24.87
GPa
To find h, need to find afm therefore Ib, Is and af for each beam & slab in long
& short direction. Assume slab thickness h= 17 cm so that x = y=38 < 4t f
Interior Panel
Compute the moment of inertia and centroid for the interior T-beam
Moments in two-way slabs can be found using DDM, subject to the following
restrictions:
1. Minimum of 3 continuous spans in each direction, 9 panel structure (3x3 ).
2. Rectangular panels, with the ratio within a panel.
3. Successive span in each direction shall not differ by more than 1/3 the
longer span.
4. Columns may be offset from the basic rectangular grid of the building by
up to 10% of span parallel to the offset.
5. Loading due to gravity only and uniformly distributed over an entire panel.
6. The unfactored L.L ≤ 2 times the unfactored D.L. (in this case, it is
unnecessary to check the effects of pattern loading).
7. For panels with beams between supports on all sides, relative stiffness of
the beams in the 2 perpendicular directions, should be given by the ratio .
Section A-A: 𝑙1
Moment per m width in slab 𝑙2
Total slab Moment
Uniform load on each beam
Moment in one beam (Sec: B-B)
Total Moment in both beams
Full load was transferred east-west by the slab and
then was transferred north-south by the beams.
The same is true for a two-way slab or any other floor
system.
1
𝑀 𝐶𝐷 𝑀 𝐴𝐵 8 ¿
RC2 By Dr. Ahmad Malkawi 33
5.5.3 Determination of the total factored statice
moment
• The total factored statice moment in a panel , for a strip bounded laterally by the panel centerline is:
Where:
factored load per unit area
clear span from face to face of the columns, capitals, brackets, or walls but it should be , circular or regular
polygon-shaped supports should be treated as square supports with the same area
is perpendicular to and equals the length of the direction between c/c of supports (width of strip). If the
transverse span of panels on either side of the centerline of supports varies, shall be taken as the average,
In the case of an edge panel, use
Ext Neg
Int Neg
Pos
C: torsional rigidity of the effective transverse beam and equals largest of:
1.A portion of the slab having a width equal to that of the column, bracket, or
capital in the direction in which moments are taken.
2.The portion of the slab specified in 1 plus that part of any transverse beam
above and below the slab.
3.The effective transverse beam defined as in Fig. 13.10.
Figure 13.10: Portion of slab to be • C: Cross sectional constant defines torsional properties for T- or L- section found by
included with beam dividing the section into its component rectangles, each having: x and y as the
smallest and largest dimension in the section of edge beam, respectively.
5.5.5
Assignment
of and to the
Column and
middle strips
• When α and βt are found, factors for moment that is assigned to the
column strips can be found from Table 13.4.
• Linear interpolations are to be made between the values shown in
Table 13.4.
• α l2/l1 = 0, when there is no interior beams in the direction of strip
under consideration.
• βt = 0, when there is no exterior “edge” beams perpendicular to the
strip under consideration.
47
RC1 By Dr. Ahmad Malkawi
5.7 Minimum Minimum Reinforcement Ratio
Reinforcement The minimum amount of reinforcement shall not be less than
Ratio and the shrinkage and temperature reinforcement:
Spacing
Requirements Slabs where G40 or G50 deformed bars are used it should be not less than:
Slabs where G60 deformed bars are used it should be not less than:
48
RC1 By Dr. Ahmad Malkawi
5.8 Bar
Cutoffs and
Anchorages
49
RC1 By Dr. Ahmad Malkawi
The extension of the –M bars is based on the longer span length.
The +M steel perpendicular to a discontinuous edge shall extend to
5.8 Bar the edge of slab at least 150mm in support.
50
RC1 By Dr. Ahmad Malkawi
5.8 Bar
Cutoffs and
Anchorages
51
RC1 By Dr. Ahmad Malkawi
5.9 Openings in
Slabs
Opening sizes:
• 1 → Any size is allowed
• 2 → 1/8 of column strip width in
each span is allowed.
• 3 → 1/4 of the smallest strip width
is allowed
Reinforcement:
• In all cases an amount of
reinforcement equivalent to that
interrupted by an opening shall be
added on the sides of the opening.
53
RC1 By Dr. Ahmad Malkawi
5.10.1 Tributary Areas for Shear in Two-Way Slabs
with Beams
54
RC1 By Dr. Ahmad Malkawi
Two-Way Slabs Without Beams
Two types of shear stresses must be investigated:
1. One-way shear (beam shear): The critical sections is at a distance d
from the column face and determined using the same previous
equation, where slab is considered to act as a wide beam with equal
to the panel width :
56
RC1 By Dr. Ahmad Malkawi
b
a
𝑎
𝛽=
𝑏
57
5.10 Shear Strength
of Two-way Slabs
The side faces of the
critical perimeter may
be extended to the
edge of the slab if the
distance from the face
of the column to the
edge of the slab does
not exceed the larger
of:
4h OR 2ld, of the
flexural reinforcement
perpendicular to the
edge.
58
RC1 By Dr. Ahmad Malkawi
5.10.1 Tributary Areas
for Shear in Two-Way
Slabs
• The shear tributary areas
are bounded by lines of
zero shear.
• For interior panels, the
lines pass through the
center of the panel.
• For edge panels, the lines
pass through the half of
the span (c/c).
• For the first interior
support, the shear force
must be increased by
15%. The tributary length
will be 1.15x0.5l=0.575l
(c/c).
59
RC1 By Dr. Ahmad Malkawi
Note: If L1≠L2, the
shorter critical
section is controlling
5.10.1 Tributary because it has
Areas for Shear shorter length of
in Two-Way Slabs wider area.
One-way shear
62
RC1 By Dr. Ahmad Malkawi
5.10.2 Increasing
the Shear
Strength of Slab
Conventional Stirrup
Cages
(Integral Beams with Vertical
Stirrups)
64
RC1 By Dr. Ahmad Malkawi
5.10.2 These devices are
composed of vertical
Increasing the bars with anchor heads
Shear Strength at their top, welded to a
steel strip at the
of Slab bottom.
These devices are more
Headed Shear Studs
effective, according to
tests, than either the
bent bar or integral
beam reinforcement.
Also, they can be placed
more easily, with less
interference with other
reinforcement.
is the area of the studs on a The overall height of the
peripheral line and S is the spacing shear stud may not be
between the peripheral lines less than:
The between the shear stud rails≤2d
ACI Code 11.11.3 requires the slab effective depth d to be at least 150 mm to use Stirrups→ OK
, Shear reinforcement can be used
• The No. 10 (No. 3) vertical closed hoop stirrups will be used since .
• For interior column, the stirrups will be arranged along 4 integral beams .
• At the 1st critical section, the required
• The required perimeter of the second critical section, at which the concrete
alone can carry the shear, is found from the controlling Eq. by setting
Total length=a+d=269+150=419 mm
#of stirrups=419/75=5.6 → Use 6φ10mm@75mm c/c
The first stirrup is placed at S/2 = 38 mm ≤ d/2 = 75 mm from the column face,
this provide a total length in each direction of 38+6x75=488 mm
265x163x2
RC2 By Dr. Ahmad Malkawi 72
Example 5.1 (cont.):
4- Moments on the column Strip :
0.69x0.35Mo
5- Moments on the Middle Strip:
"The remain moment":
180mm 180mm
4 1
320mm 2 320mm
3
350mm 350mm
RC2 By Dr. Ahmad Malkawi 78
Example 5.2 (Cont.):
3
For
• With , , and , Table 13.4 indicates that the column strip will take 91% of the exterior –M, 81% of the +M, and 81% of the
interior –M.
• As before, the column-line beam will account for 85% of the column-strip moment. The results of applying these moment
ratios are as follows: