800A Power CB
w/STD = 6 cycles 65,000A RMS Sym. Available
800A MCC with
3 cycle 65kA Bracing
• The top design meets 110.10 of the NEC because a 65kA fault would be
cleared in ½ cycle or less and the MCC is rated for 3 cycles.
• The bottom design violates 110.10 because a 65kA fault could continue
for 6 cycles, but the MCC is only rated for 3 cycles.
… must all be rated to safely withstand the energy of the fault let-through
current without “extensive damage” to any of the circuit components.
480 V 600 V
UL 1008
Ampere Specific Specific
Rating Any Breaker Breaker Any Breaker Breaker Fuse
40, 80, 100 10,000 30,000 10,000 22,000 100,000
150, 200 10,000 30,000 22,000 35,000 100,000