Transformers
Transformers
Presented by
Dr. S.RAJENDRA PRASAD
1.TRANSFORMER CONSTRUCTION
A transformer is a static device and its construction is simple as there are no moving
parts. The main parts of the transformer as shown in figure are
1) Magnetic core
2) Windings
3) Conservator tank
4) Transformer oil
5) Radiators
6) Bushings
7) Breather 8)Container
9) Buchnolz relay.
1. Magnetic core
•It is made of silicon steel or sheet steel with low reluctance.
•In addition to this, the sheets are laminated and are coated with an oxide layer to reduce
the iron losses.
•The thickness of lamination is 0.35mm for 60 Hz operation and 5mm for 25 Hz operation.
•core common part between the two windings. It helps both the wi-
ndings to link through the magnetic flux.
2. Windings
• A conventional transformer has two windings. The windings which receives the
electrical energy is called the primary winding and winding which delivers the electrical
energy to the load is known as secondary winding. The two windings are electrically
separated but magnetically coupled through magnetic core. The windings are usually
made of copper or aluminum with enamel coating.
•The low voltage winding carries high current so the wire diameter is more the high
voltage winding.
3. Conservator tank
•It is an oil tank provided on the transformer. It is also filled with oil and connected to the
transforms tank. The main tank is completely filled with oil.
When the is oil filled and self-cooled, the oil in the tank is subjected to heat and thus will
naturally expand or contract due to the variations in load current and is also subjected to
seasonal variations. The function of the conservator tank is to take up contraction and
expansion of oil without allowing it to come in contact with outside air.
4. Transformer oil
It is a mineral oil obtained by refining crude petroleum. It serves the following purposes.
i) Provides additional insulation
ii) Protects the paper from dirt and moisture.
iii) Carries away the heat generated in the core and coils i.e it is used for cooling
purpose.
5. Radiators
Radiators help in cooling the transformer oil by increasing the surface area. The number of
radiators required is independent on the capacity of the transformer and rate of cooling.
6. Bushings
The bushings are employed for insulating and bringing out terminals of the winding
from the container to the external circuit. Number of bushings is equal to number of phases.
These are generally of two types
i) Porcelain type which are used for voltage ratings up to 33 kV.
ii) Oil filled or condenser types which are used for voltage higher than 33 kV.
7. Breather
•Transformer oil should not be exposed directly to the atmosphere because it may absorb
moisture and dust from the environment and may loose its electrical properties in a very
short time. To avoid this problem a breather is provided on the top of the conservator.
•It mainly consists of a silica gel. The silica gel absorbs the moisture content of air so that
the oil contamination can be prevented.
•Colour of silica gel is blue at good condition and it becomes violet then pink as it absorbs
moisture.
8. Container
Cast iron or cast steel air lighted containers are provided with radiators. The
container contains the core windings and oil.
9. Buchholz relay
It is a relay, provided in between conservator task and transformer tank. It helps in
identify incipient faults. Its use for oil immersed transformers of rating less than 750kVA
is generally uneconomical.
2. E.M.F. Equation of a Transformer
Consider that an alternating voltage V1 of frequency f is applied to the primary The sinusoidal flux ɸ produced
by the primary can be represented as
It is clear from the above equation that maximum value of induced e.m.f. in the primary is
Voltage Transformation Ratio (K)
(ii) there are no losses. Therefore, volt-amperes input to the primary are equal to the output volt-amperes
i.e.
Practical Transformer
(i) iron losses (ii) winding resistances and (iii)magnetic leakage, giving rise to leakage reactances.
the iron core is subjected to alternating flux, there occurs eddy current and hysteresis loss in it. These two
losses together are known as iron losses or core losses. The iron losses depend upon the supply frequency,
maximum flux density in the core, volume of the core etc.
3. IDEAL TRASFORMER PHASOR DIAGRAM
+
3.2 Pratical Transformer under Load
N1Iµ = Primary mmf and the corresponding flux due to this MMF is Φ
=
=
=
=
=
5. LOSSES IN TRANSFORMER
Transformer Losses
1) Copper losses 2) Iron losses
I1 R01 I1
X
E1 I1
I12 R01
E1 I1
PU FULL LOAD CU LOSSES
A) HYSTERSIS LOSSES
• It is due to reversal of magnetization in transformer core whenever it is
subjected to alternating nature of magnetizing force.
WH ηBmax
x
fυ
η stenmetz coefficient
f frequency
x stenmetz exponent(1.5 to 2.5)
volume of core
B) EDDY CURRENT LOSSES
Eddy current loss is basically I2R loss present in the core due to production of
eddy current in the core.
We KB2max f 2 t 2
2
K
6
f frequency
t thickness of lamination
Bmax maximum flux density
5.3 VOLTAGE AND FREQUENCY EFFECT ON LOSSES
A) HYSTERSIS LOSSES
CASE 1:
V1/f = constant Bm=constant
Wh f
Wh = Af
CASE 2:
V1/f constant Bm constant
Wh V1/f x f
Wh
1.6
0.6V1/f x f
WH α V1 f A V1 f 1.6 -0.6
(x 1.6)
CASE 3:
V1 = constant , f , Bm (V1/ f)
Wh f -0.6
Wh = Af -0.6
CASE 4:
f = constant, V1
Bm (V1 / f)
Wh V11.6 = A V11.6
B) EDDY CURRENT LOSSES
CASE 1:
V1/f = constant Bm=constant
We f 2
We = Bf 2
CASE 2:
V1/f constant Bm constant (V1/f )
We K V21/f 2 f 2 t2
We α V1
CASE 3:
V1 = constant , f , Bm (V1/ f)
We α V12
CASE 4:
f = constant, V1
Bm (V1 / f)
2
We α V 1
6.VOLTAGE REGULATION
V11 V2
%V .R 1
and V11 E2
V1
Knowing the equivalent resistance and reactance referred to
primary/secondary
I1R 01 cos φ1 I1X 01 sin φ1
%Voltage Regulation X 100
V1
I 2 R 02 cos φ 2 I 2 X 02 sin φ 2
X 100
E2
"" sign for lagging p.f and "-" sign for leading p.f
7.EFFICIENCY OF TRANSFORMER
KVA RATING AT MAXIMUM EFFICIENCY CONDITION
……………………(2)
8. ALL DAY EFFICIENCY
DISTRIBUTION
BASIS OF DIFFERENCE POWER TRANSFORMER
TRANSFORMER
Type of network It is used in transmission It is used in the distribution
network of higher voltages network for lower voltages.
Availability of ratings 400 kV, 200 kV, 110 kV , 66 kV, 11 Kv, 6.6 Kv, 3.3 Kv, 440
33 kV. V,230V
Maximum rating of usage Power transformers are used for Distribution transformers are
rating above 200 MVA used for rating less than 200
MVA
Size Larger in size as compared of Smaller in size
distribution transformers
Designed Efficiency Designed for maximum Designed for 50-70% efficiency
efficiency of 100%
Efficiency formula Efficiency is measured as the Here All Day Efficiency is
ratio of output to the input considered. It is the ratio of
power output in kilowatt hour (kWh)
or watt hour (Wh) to the input
in kWh or Wh of a transformer
over 24 hours.
Application Used in generating stations and Used in distribution stations,
transmission substations also for industrial and domestic
purposes
Losses Copper and iron losses take Iron losses take place for 24
place throughout the day hours and copper losses are
based on load cycle
Load fluctuation In power transformer the load Load fluctuations are very high
fluctuations are very less
Operating condition Always operated at full load Operated at load less than full
load as load cycle fluctuates
Considering time It is independent of time It is time dependent
Flux density In power transformer flux As compared to power
density is higher transformer the flux density is
lower in distribution transformer
Designing of the core Designed to utilize the core for As compared to power
maximum and will operate near transformer the flux density is
to the saturation point of the B-H lower in distribution transformer
curve, which helps to bring
down the mass of core
Usage Used to step up and step down Used as an end user connectivity
voltages
Losses Copper and iron losses take Iron losses take place for 24
place throughout the day hours and copper losses are
based on load cycle
9.OC TEST AND SC TEST
IO
WO
VO
Parameters finding by conducting OC test:-
1) To find out constant losses(or) iron losses(or) core losses in
transformer.
2) To find the Ro, Xo, Io (5% of rated current), Iu and Iw
WSC ISC
VSC
Parameters finding by conducting SC test:-
1) To find out variable losses(or) Cu losses in transformer.
V
Bm f rated
applay
f rated
Bm week flux Iron loss is less due to week flux
VSC I SC Z O1
VSC I SC Z O1
PU Impedence drop of trnsformer
E1 E1
VSC
%Z x100
E1
10. SUMPNERS TEST
W1 W2 I2
I1
V3
V1 V2
HEAT RUN TEST:-
•we run this test for certain period of time instaneously
temperature rise cannot be obtained.
Difficulty in sumperners test:-
•Two identical single phase transformer are needed.
Connection:-
•Two primary of the transformer should be connected in parallel
and excited from main supply source at rated voltage and
frequency (Similar to OC test).
•Secondary's of two transformer should be connected in series
subtractive polarity. This series combination should be supplied
from auxiliary source(Similar to SC test).
PROCEDURE:-
1. The DPST1 switch is closed and input voltage is adjusted until
the voltmeter indicates the rated value of LV winding of
transformer by means of variac 1
2. The secondary voltmeter (V3) reading is observed. If it’s greater
than zero volts, the secondary terminals of one of the
transformers must be reversed, such that V 3 reads zero.
W1
Iron loss of each T/F Wi
2
W2
full load cu losses of each T/F Wcu
2
X KVA RATING cos
η x100
X KVA RATING cos X Wcu Wi
2
11.SEPARATION OF CORE LOSSES IN SINGLE PHASE
TRANSFORMER
•In order to separate iron losses into hysteresis and eddy current
losses, OC test should be conducted with variable voltage and
frequency.
V
such that Bm constant
f
Wh f , We f 2
Wi Af Bf 2
Wi
A Bf
f
m tanφ slope of straight line B
Hystersis loss Af rated
Eddy current loss Bf rated
2
PROCEDURE
12.AUTO TRANSFORMER
V2 N2
V1 V2 N1 N 2
V2 N1 N 2V1 (N1-N2), (V1-V2)
V2 N2
K
V1 N1
I1 N2
K
I 2 I 1 N1 N 2
I1 N
K 2
I2 N1
V2 N2 I1
K
V1 N1 I2
a) Part of the winding is common to both primary and secondary.
b) Transformation ratio of auto transformer is
LV
K 1
HV
% Tappings
c) The feasibility of auto transformer depends on the tapping
point.
N1:N2=3:1 then K=33.3% (Breaking point)
N1:N2>3:1 then K<33.3% (Auto T/F is not feasible)
N1:N2<3:1 then K>33.3% (Auto T/F is feasible)
d) In auto transformer power is not only transferred by induction
process but also by conduction process.
KVA induction V2 I 2 I1 V2 I 2 KI 2
V2 I 2 1 K V1 I1 1 K
Input KVA V1I1
KVA induction 1 - K x Input KVA
weight of cu
AT N1 N 2 I1 N 2 I 2 I1
2N1I1 2N 2 I1
weight of cu
TW N1 I 1 N 2 I 2 2 N1 I 1
weight of cu
AT
2N1I1 2N 2 I1
1 K
weight of cu
TW 2 N1 I 1
weight of cu
AT 1 - K weight of cu TW
f) Saving of cu AT WTW WAT WTW (1 K )WTW KWTW
1
g)(KVA) AT (KVA) TW
1 K