power systetm stability
power systetm stability
1
Outline of
Presentation
Introduction
Swing equation
2
Introduction
3
Introduction
(contd…)
POWER SYSTEM
STABILITY
Steady state
stability Transient state
stability
Static Dynamic
stability Stability
4
Introduction
(contd…)
Steady state stability : It is defined as the ability of a
power system to remain stable (i.e., without losing
synchronism) for small disturbances ( gradual changes in
load).
Static stability refers to inherent stability that prevails
without the aid of automatic control devices
Dynamic stability refers to artificial stability given to
an inherently unstable system by automatic control devices.
It is concerned with small disturbances lasting for 10 to 30
sec.
EV 2
Pe jQe sin δ j E V cos δ V ........( 3)
Xd X X
d d
EV
Pe=Real Power of sin δ .........
(S)= X s (4)
6
Power Angle Curve
(contd…)
Plotting
(4)
7
Power Angle Curve
(contd…)
The max steady-state power transfer occurs when
δ=90;
EV
P max ..................(5)
X
The value of Pe,max is called the pull-out or steady-state stability limit.
E V
Pr P P cos δ ………………….(6)
d
δ δ
Where
X
Pr synchronizing power coefficient
8
Power Angle Curve
(contd…)
Case (ii): Generator connected to Infinite
bus.
EV
The real power output of this system Pe sin δ Pmax sin δ ........
X
is (8)
The maximum steady state power transfer Pmax occurs when ,δ=900
and
equals EV
to X EV
Pmax X ..........
(9)
Transfer reactance(x): The total reactance X between two
voltage sources V and E is called the transfer reactance. The
maximum power limit is inversely proportional to the transfer
reactance.
9
Power Angle Curve
(contd…)
Case (iii) :Power transfer through Impedance
In all electrical machines and transmission lines, the resistance
is negligible as compared to inductive reactance.
Active power received by infinite bus is given by
V2 V 2R
2 ........(10)
Pe,max X2 R 2
R2
X
For Pe,max to be maximum (i.e. for max. power transfer), the
above equation is to be differentiated w.r.t ‘ X’
X 3R.......(11)
The practical application of (11) is limited. It that if X=0,
10
Worked Example 1
Sol. D
11
Worked Example 2
12
Worked Example 3
E
P max X /
V 2
13
Methods of Improving Steady State Stability
Limit
The stability limit is the max. power that can be
transferred in a network between source and load without
loss of synchronism.
• The steady state stability limit is the max. power that
can be transferred without the system becoming
unstable, when the load is increased gradually, under
steady state condition.
• Transient stability limit is the max. power that can be
transferred with out the system becoming unstable when
a sudden or large disturbance occurs.
The transient stability is lower than the steady-state stability.
Methods of Improving Steady State Stability
Limit
The steady state limit is given by SSSL= X
E
P max V
• Series capacitors
• Double circuit
• Bundle conductors
•
Dynamics of synchronous
machine
1
KE 2 Mωs ...........(12)
H
M sec2 / elec rad............(13)
180 f
Swing
Equation
Thebehavior of a synchronous machine during
transients is described as swing equation.
Let,
J = Total moment of inertia of the rotor mass in kg - m2
θm= Angular displacement of the rotor with respect to a stationary
axis in mechanical radians.
t = Time, in seconds.
Tm= The mechanical (or) shaft torques in N-m.
Te= Net electrical (or) electromagnetic torque in N -
m. Ta= Net accelerating torque in N - m.
Under steady state
conditions, Te = Tm , N =
constant
17
Swing equation
(contd…)
d 2θ
Ta m
..........
J dt 2 (15 )
Swing d 2δ
Pm Pe .......(18)
Equation M ( p.u ) dt 2
18
Swing equation
(contd…)
δ1 δ 2
δ
19
Swing equation
(contd…)
The two machines swing coherently are thus reduced to a
single
machine
as H eq H1mach G1mach H 2mach G2mach
G sys G sys ............(21)
The above results are easily extendable to any no. of
machines swinging coherently.
Swing Curve: The graph between load angle and time is
called Swing Curve.
If δ increases continuously with time the system is unstable.
if δ starts decreasing after
reaching a maximum value it is
said that the system will remain
stable.
Analysis Of Steady State
Stability
It is determined based on SSSL with
power
21
Analysis Of Steady State
Stability(Contd…)
P Pe
Pmax cos δ0 δ 0 ..........(25)
δ
For a torque angle of δ=δ0+Δδ,
M d2 δ 0 δ P m (Pe0
dt
P)
Since δ0 is constant and Pm=Pe0,
d2
M P
δ2
dt
Further solving, we obtain the following differential equation
d 2
M δ P cos δ δ
0 max
0
dt
Let d cos δ0
M dt δ x , max c
P
P Pmax
cosδ e
0 δ
x 0
.............(26)
M M
22
Analysis Of Steady State
Stability(Contd…)
P
Case (i) : When C is +ve( i.e.
0 or Pmax
e
δ 0
cosδ0>0)
Roots are purely imaginary and conjugate.
The system behavior is oscillatory about
δ0.
Case (ii) : When C is –ve P 0 or Pmax
e
(i.e δ
The roots are real and equal in cosδ 0<0)
0
magnitude.
One of the root is +ve and other is –ve.
Due to the +ve root the torque angle increases without bound.
23
Analysis Of Steady State
Stability(Contd…)
Pe
δ is known as synchronizing coefficient. This is also
0
called
stiffness of synchronous machine.
Assumptions
• Generators are represented by constant impedances in
series with no load voltages.
• The mechanical power input is constant.
• Damping is negligible.
• Load angle variations are small.
• Speed variations are negligible.
24
Transient
stability
Transient stability limit is the maximum power that can be
transferred without the system becoming unstable when a sudden
or large disturbance occurs.
Assumptions:
• In transmissions line & synchronous machine resistance is
neglected.
• Damping term contributed by synchronous machine damper
winding is neglected.
• Rotor speed is assumed to be synchronous.
• Mechanical power input to machine remains constant.
• Voltage behind transient reactance is assumed remains constant.
• Loads are modelled as constant admittances.
25
Transient
stability(Contd….)
The transient stability can be analysed by following methods
i) Equal Area criterion.
ii) Point by point method
iii) Runga-Kutta method
Equal area criterion
The stability of a single machine connected to
an infinite bus can be studied by the use of equal area
criterion.
If Pe1=Pe0+∆P then the accelerating power Pa decreases
from ∆P
(when δ =δ0) to zero (when δ =δ1).
During the time taken by the load angle to increase
from δ0 to
δ1, the rotor absorbs KE. This KE equals to the shaded 26
Equal Area
criterion
The load angle δ 2 can be obtained from the condition that the
27
Mathematical way of expressing Equal area
Criterion
Multiplying eq (18) dδ and integrating, we
2
by dt get.
δ
dδ 2 P a
dδ ...........(27)
δ 0
dt M
For a stable system (i.e. the load angle will have minimum
dδ
value when 0)
dt δ
i.e. Pa dδ
δ
0 0
28
Sudden change in Mechanical
Input
Let the mechanical input to the generator
Pa=Pm1-Pe
In this new steady state Pm1 = Pe1
A1 δ (Pm1
0
………….(28)
δ1
Pe )dδ
A2 (Pe
Pm1 )dδ
δ 2
29
Sudden change in Mechanical Input
(Contd…)
As pm increases, a limiting condition is finally reached
at a
δ 2 max Pm1,max
1
sin Pmax
30
Critical clearing angle & Critical clearing
time
Critical clearing angle (δcc): It is the maximum
allowable change in the power angle δ, before clearing the
fault, without loss of synchronism.
P a 1 Pm
δ δ δ cos cos δ max P (δ δ 0 )..............(29)
t2M
2 max
0 cc
Critical clearing max
time(tcc): It can be defined as the
maximum time delay that can be allowed to clear the fault
synchronism.
without loss of 2H (δ cc δ 0)
t cc .................(30)
fPm
31
Sudden Loss of one of the parallel
line
When both of the lines are operating the power
transfer EV
is given by e1 sin δ Pmax I sin δ .........
X X
P Xd 1 2 (31)
X1 X
1
to (π-δ1) radians.
32
Fault and Subsequent circuit
isolation
When fault develops at any point F on line2 it is
subsequently cleared by cleared by opening the CBS at
both the ends of faulted line.
3 power angle curves are involved,
δmax
33
Fault and Subsequent circuit
isolation(Contd….)
An expression for δcc can be derived
as
δcc 1 Pm
max δ 0) Pmax III cosδ max Pmax II cosδcc
( δ Pmax III P max II .........(33)
cos
Where
, δ max Pm
1 δ0 Pm
1
34
Fault, Circuit isolation and
reclosing
The transmission lines are provided with automatic quick
reclosing circuit breakers, because most of the faults are
transient in nature
When fault occurs, operation shifts to curve for faulted condition.
When the load angle is δc, the faulted line is isolated and
36
Solution of swing equation by point by point
method(Contd….)
The increments of speed and angular displacement
during the nth interval
ωn n ωn1
M
t
Pa n1 ...........(38)
ω
δn (t) 2 (Pan1 Pan2 )...........(39)
n1 2M
δ
37
Methods of improving
stability
By increasing inertia constant(M)
Breaking resistors
38
Methods of improving stability
(Contd…..)
Short circuit current limiters
39
Worked Example
40
Worked Example
Q. No.5) A lossless single machine infinite bus power system
is shown in the fig. The synchronous generator transfers 1.0pu
of power to infinite bus. The critical clearing time of circuit
braker is
0.28 s. If another identical synchronous generator is connected
in parallel to the existing generator and each generator is
scheduled to supply 0.5pu of power, the critical clearing time
of the circuit breaker will be
Sol. d
δ2
M ( p.u ) 2dt
Pa
41
Worked Example
𝛿=
Pa 𝛿o
δ0
2M (0)
2H (Aδcc δ0 )
tcc
fPm
42
Worked Example
43
Worked Example
Sol)
44
Worked Example
δ1 δ2
45
Worked Example
46
Worked Example
47
Previous years GATE
Questions
48
Previous years GATE
Questions
49
Worked Example
50
Worked Example
51