Lesson 21_et332b.pptx 1
After this presentation you will be able to:
Lesson 21_et332b.pptx 2
Alternator Ratings
Alternators rated in kVA
or MVA at a specified
power factor
Generally
Pout Fp Srated
Lesson 21_et332b.pptx 4
Alternator Capability Curve
150
Operating
Reactive power output
100 Range limited by machine
excitation system
50 In this diagram
Reactive Power (kVAR)
50
100
80% lead
150
0 20 40 60 80 100 120
Active Power Into System (kW)
kVAR out 80% lag
kVAR in
0.8 Leading
0.8 Lagging
Lesson 21_et332b.pptx 5
Governor - electromechanical speed control used to
maintain constant speed as machine power load
changes
Power transfer between parallel alternators is controlled
by change in prime-mover power input and speed. If
speed remains constant, then torque increases as
developed power increases
Mechanical Power In
n= constant
Speed
Increasing Torque
Lesson 21_et332b.pptx 6
Governor Speed Regulation
n nl n rated f nl f rated
GSR
n rated f rated
Lesson 21_et332b.pptx 7
fnl and nnl
61.2 Hz
3672 rpm
rated f and n
60 Hz GD
3600
rpm
f (Hz)
n (rpm) rated P out
0
0 500 kW
P (kW)
Lesson 21_et332b.pptx 8
Example 21-1: Find the speed
61.2 Hz regulation and the governor droop
3672 rpm for the machine that has the curve
GD
shown
60 Hz
3600
rpm
f (Hz)
n (rpm)
0
0 500 kW
P (kW)
f 61.2 60 Hz
GD 0.0024 Hz/kW
P 500 kW
Lesson 21_et332b.pptx 9
ET 332b
Ac Motors, Generators and Power Systems
Lesson 21_et332b.pptx 10