Fault Analysis 3
Fault Analysis 3
Fault Analysis – 3
Faults
3
Faults
4
Occurrence of Faults
(3% - 2%)
(10% - 8%)
On overhead lines :
• most faults are one-phase-to-ground faults resulting primarily from
→ lightning-induced transient high voltage
→ falling trees and tree limbs
→ momentary tree contact caused by wind
• Ice, freezing snow, and wind during severe storms can cause many
faults and much damage
• Open circuit faults, such as a broken conductor or a blown fuse, are
not too common, except perhaps in the lower-voltage system in
which fuses are used for protection
5
all three phases of the system are all three phase of the system are
short-circuited to each other earthed
• The single line diagram can be used, as all three phases carry
equal fault currents displaced by 120o
7
Fault Level
• A fault represents a structural network change
→Equivalent with that caused by the addition of an impedance
at the place of fault
→If the fault impedance is zero, the fault is referred to as the
bolted fault or solid fault
3 . Vnominal. I sc Vnominal,pu
Fault Levelpu I sc, pu
3 . Vnominal. I base Z pu
• The per unit voltage for nominal value is unity (1), so that
1
Fault Levelpu
Z pu
1
Fault LevelMVA Fault Levelpu .MVAbase .MVAbase
Z pu
10
• The strength of a busbar (or the ability to maintain its voltage) is directly
proportional to its SCC
→ An infinitely strong bus (or Infinite bus bar) has an infinite SCC, with a
zero equivalent impedance and will maintain its voltage under all
conditions
• The SCC is a better indicator of the stress on circuit breakers than the
short circuit current
→ Because a circuit breaker has to withstand the recovery voltage across
the breaker following an arc interruption
11
• Simplifying Assumptions:
→ Pre-fault voltages are at 1pu (All generators are running at their
rated voltage and rated frequency with their emfs in-phase)
→ Negligible line resistances
→ Negligible load currents compared to fault currents
→ Effect of shunt capacitances is negligible
12
R3
Vth .V1
R 1 R3
R1 R3
Z th R2
R 1 R3
13
Example 1
• The single-line diagram of a simple three-bus power system is
shown in the following figure. Each generator is represented by
an emf behind the transient reactance. All impedances are
expressed in per unit on a common 100 MVA base. Determine the
fault level at
a) Bus 3.
b) Bus 2.
c) Bus 1.
d) Determine the fault currents of the two generators during
the fault when a balanced three-phase fault with a fault
impedance Zf = 0.16 pu occurs on Bus 3.
j0.1 j0.2
1 2
j0.4 j0.4
3
14
Solution – Example 1
DC Component
24
Synchronous Generator
25
• Reference: P. Kundur, “Power sys. stability and control,” USA: McGraw-Hill, 1994.
28
Symmetrical Components
c1
c b2
a
a1 a2 c0
a0 b 0
c2
b
b1
Unbalanced System Positive Sequence Negative Sequence Zero Sequence
3 unknown magnitudes 1 unknown magnitude 1 unknown magnitude
1 unknown magnitud
3 unknown angles 1 unknown angle 1 unknown angle 1 unknown angle
• a = a 1 + a2 + a0
• b = b1 + b2 + b0
• c = c 1 + c2 + c0
30
• a complex operator
Some Properties of α
• α = 1∠2π/3 or 1∠1200
• α3 = 1∠2π or 1∠3600 or 1
→i.e. α3 - 1 = (α - 1)(α2 + α + 1) = 0
→Since α is complex, it cannot be equal to 1, so that α - 1
→∴ α2 + α + 1 = 0
cannot be zero.
• This also has the physical meaning that the three sides of
an equilateral triangles must close as in the following
figure
32
Analysis of decomposition of
phasors
b2 = αa2
C1=αa1
c
a
a1 a2
c2= α a2
a0 = b0= c0
b 1 = α 2 a1
2
b
• a = a 0 + a1 + a2
• b = a0 + α2 a1 + α a2
• c = a0 + α a1 + α2 a2
33
a 1 1 1 a0
b 1 2 a
1
c 1 a2
2
Ph A Sy
34
a0 1 1 1 a
a 1 1 2 b
1 3
a2 1 2
c
Sy A Ph
-1
35
1 1 1 1 1 1
1 2
A 1
2
A 1
1
3
1 2 1 2
1 *
A1
A
3
36
Sequence Impedances
1 *
Z s A
1
Z p A A Z p A
3
1
Z AZ A
p s
-1
AZ s A
3
*
37
Rb Mca Lb Mab
Rc Lc Mbc
38
• Mutual coupling
→ When a current passes in one phase
conductor, there would be induced
voltages in the other two phase
conductors.
→ In practice all three phase conductors
behave similarly, so that we could
consider the mutual coupling between
phases also to be equal
→ Mab = Mbc = Mca
39
R j L j M j M z s zm zm
Z
p jM R j L jM z m zs z m
jM j M R jL z m zm z s
40
Use of Sequence Impedance Matrix
cont.
• Symmetrical component impedance matrix
1 *
Z s A
1
Z p A A Z p A
3
1 1 1 zs zm z m 1 1 1
1 2
Z s 1 z m zs z m 1 2
3
1 2 z m zm z s 1
2
( zs 2 zm ) 0 0 z0 0 0
Z s 0 ( zs zm ) 0 0 z1 0
0 0 ( z s z m ) 0 0 z 2
41
Use of Sequence Impedance Matrix
cont.
• Comparison of phase and symmetrical component
matrix
zs zm zm ( zs 2 zm ) 0 0
Z p z m zs z m
Z s 0 ( zs zm ) 0
z m zm z s 0 0 ( z s zm )
S V s A A I s V s A 3 A I s
T T * * T T 1 *
* * *
S 3(Va 0 I a 0 Va1 I a1 Va 2 I a 2 )
P 3(Va 0 I a 0 cos 0 Va1 I a1 cos 1 Va 2 I a 2 cos 2 )
44
Ec
Ea
Eb
45
Z0 Ia0
Va 0 0 Z 0 I a 0 Zero
sequence
Va0 network