ATW - Modbus compatibility- Interface PCBs

UTW-KMBXJ

1
Contents

Product feature

Additional Modbus information

Installation

Parameter list

Settings

Installing QmodMaster and connection

Troubleshooting

Copyright 2022 FUJITSU GENERAL 2


Product feature
Building management system integration

Using the OCI351 communication module, boilers can be integrated into building management systems
via Modbus. Thus, LMS and RVS controllers can also be integrated into boilers with a higher
performance in commercial applications.

UTW-KMBXJ

Copyright 2022 FUJITSU GENERAL 3


Product feature
UTW-KMBXJ Gateway Modbus properties
Albatros2 controller (default value
in bold face)

3-pin screw connection (A+, B-,


Terminals
Product number UTW-KMBXJ (Siemens OCI351.01) REF) on Modbus clip-in OCI35x

Connection type RS485


Designation Modbus clip in Terminal resistance using DIP
Termination
switch on Modbus clip-in OCI35x
Links with Modbus controllers · "Modbus Application Protocol
Modbus version
Specification V1.1b"
www.modbus.org
Installation location On the controller · "Modbus over Serial Line V1.02"
Modbus mode RTU
Power 5V DC via RVS/LMS Depending on the controller:
Modbus role
Slave / Master
IP class IP00 Slave address 1...247

Operation condition -20…+50C Baud rate Adjustable: See controller manual

Start bit 1
Dimensions 75x55x20mm Data bit 8

Stop bit 1 or 2
Weight 45g
Parity Even/Odd/None

Documentation IM and Interface specification 0x03 Read Holding Registers


0x06 Write Single Register
Modbus function codes
(not for structured data types)
0x10 Write Multiple Registers
Data register 2 byte

Coding MSB (Most significant Byte) first

Telegram length Maximum 44 data bytes

Default: 300 ms
Response timeout
Adjustable from 100…10,000 ms

Copyright 2022 FUJITSU GENERAL 4


Additional Modbus information
Modbus RTU communication protocols
Modbus RS485 has been the most common protocol in the world. It supports communications speed up to 115kbps, but most devices support
only communication up to 19.2 kbps.
Modbus RS485 is a low cost communication implementation, and it has the largest installation base and supplier network. The weak point of
Modbus is the transmission speed (since it is limited by serial line speeds) and the relatively small number of devices that can be connected to
one network. However, Modbus-RTU is still an economical and reasonable choice to the majority of the systems.
Modbus is based on a Master/Slave concept. One device is the master and sends requests to read or write data to each slave in turn. Slaves
answer to requests from the Master. Even though you can have many devices connected to one serial line only one device can talk at a time.

1.Request
Modbus
Master device

Slave devices
2.Response

Up to 247 Modbus converters

Copyright 2022 FUJITSU GENERAL 5


Installation
The new 4th Generation Serial UART uses Connector X60 and CN21

For modbus connection: the X60 should be connected to related Optional Part
Therefore, the serial „UART“ Interface PCB  should be changed  into the Analog Version  next slide

X60

21
CN

Copyright 2022 FUJITSU GENERAL 6


Installation

1. Switch off the power supply to the heat pump system and wait for about 5 Minutes.

2. Change to Analog Interface PCB Version (spare part no 9708302034)

3. Use the wire bundle “Analog” (spare part no 109696)

4. Connect it to X75 on heat pump controller PCB

5. Additionally connect the Modbus clip UTW-KMBXE to X60 on heat pump controller

6. Switch back on the power supply to the heat pump system.

7. Execute once the Parameters 6201 [Configuration level] to "yes" and confirm the setting with ok

R32 Not compatible to connect to Modbus

Copyright 2022 FUJITSU GENERAL 7


Installation
When the analogue Interface PCB connected 
Main PCB (X75) will be connected to the The Interface PCB (CN22 & CN 7 and CN16 on)

Now the X60 is free for


Modbus

Analogue wire
bundle :
spare part no
109696
X75

CN
7
Analog
Interface
PCB

CN16
spare part
no:
CN
22 9708302034

Copyright 2022 FUJITSU GENERAL 8


Parameter list
Modbus slave applications  Modbus parameter list
Selectable values
Main Topic

Parameters

Copyright 2022 FUJITSU GENERAL 9


Settings
Prepare controller settings. Menu Engineer -> Modbus

1. Slave Address: Parameter 6651 3. Baud Rate: Parameter 6652

2. Baud Rate: Parameter 6652 4. Stop Bit: Parameter 6654

Copyright 2022 FUJITSU GENERAL 10


Troubleshooting
Modbus on RS485

Tip #1 – 3 Wires not 2


 RS485 is 3 conductor network. You take a huge risk by not installing the 3 rd
conductor. You risk blowing 485 ports, you risk unstable operation and finally
risk of re-installation. So called ground terminal is not connection to the
Ground. It is a common interface signal. The voltage level on Tx/Rx
conductors are measured relative to this voltage level.

Tip #2 – Connection order


 Always connect the ground reference conductor first, if the system is powered OR always choose devices that have optical
isolation.

Tip #3 – Shield
 You can get away without a shield. The twisted pair used for Tx and Rx is more effective at noise cancelation than the shield.

Tip #4 – Cable location


 Take care where you run your cables. It seems obvious not to wind your caböe around other cables or sources of electricity
magnetism. Worst induced noise are switching DC or/and Variable frequency drivers.

Copyright 2022 FUJITSU GENERAL 11


Troubleshooting
Modbus on RS485

Tip #5 – Cable type


 Cable impedance should be less independent of distance.
Example Cat5, Belden 3106A, Belden 3107A

Tip #6 – Number of devices per trunk


 The RS4858 standard is based on 32 devices, usually a repeater is
necessary to connect all devices.

Tip #7 - Cable length


 The main cable must be no longer than 700 (1200) m! This distance does not include the branches (which must nevertheless be
short).

Copyright 2022 FUJITSU GENERAL 12


Troubleshooting
Modbus on RS485
Tip #8 – Topology Tip # – Termination resistance
 Best topology is single trunk that in-outs on the terminal  In order to avoid signal reflections, 120Ohm resistance
blocks of each device it connects. must be fitted on each end of the main cable. If the
Best arrangement total length of the main cable is less than 50m
termination resistances can be avoided at the ends of
the main cable.
Tx Rx Gnd Tx Rx Gnd

Not recommended – Avoid star configuration

Copyright 2022 FUJITSU GENERAL 13


Troubleshooting
Connect Modbus USB interface to check connection with PC

Clip USB – RS 485 USB Cable


Convertor

X60

RVS21

Copyright 2022 FUJITSU GENERAL 14


Troubleshooting
Install and prepare QModMaster to check Modbus connection.
- Parameters should correspondent to settings in HMI controller
- Click connect to establish connection

- Use Function Code: Read Holding register to read


parameter settings

- Use Function Code: Write Single register to read


parameter settings

Copyright 2022 FUJITSU GENERAL 15


Troubleshooting
- Use Function Code: Read Holding register to read
parameter settings
Modbus register 1024 –> read 0 -> Protection mode

Modbus register 1025 -> read 1792 -> Comfort setpoint 28 C

Modbus register 1026 -> read 1216 -> Reduced setpoint 19 C

1024 10251026

Copyright 2022 FUJITSU GENERAL 16


Troubleshooting
- Use Function Code: Write Single register to change parameter

Copyright 2022 FUJITSU GENERAL 17


Troubleshooting
An error may occur after changing the IF PCB
516: Heat pump missing
Why happened:
RVS21 still looking for last connection X60 while we
connected that to X75

Solution:
It means that we should reset the RVS21 to find the correct
connection.

Parameter 6201: Reset sensors to "yes" and confirm the setting


with ok 18
Copyright 2022 FUJITSU GENERAL
19