12 Modbus - UTW-KMBXE - UTW-KMBXJ
12 Modbus - UTW-KMBXE - UTW-KMBXJ
UTW-KMBXJ
1
Contents
Product feature
Installation
Parameter list
Settings
Troubleshooting
Using the OCI351 communication module, boilers can be integrated into building management systems
via Modbus. Thus, LMS and RVS controllers can also be integrated into boilers with a higher
performance in commercial applications.
UTW-KMBXJ
Start bit 1
Dimensions 75x55x20mm Data bit 8
Stop bit 1 or 2
Weight 45g
Parity Even/Odd/None
Default: 300 ms
Response timeout
Adjustable from 100…10,000 ms
1.Request
Modbus
Master device
Slave devices
2.Response
For modbus connection: the X60 should be connected to related Optional Part
Therefore, the serial „UART“ Interface PCB should be changed into the Analog Version next slide
X60
21
CN
1. Switch off the power supply to the heat pump system and wait for about 5 Minutes.
5. Additionally connect the Modbus clip UTW-KMBXE to X60 on heat pump controller
7. Execute once the Parameters 6201 [Configuration level] to "yes" and confirm the setting with ok
Analogue wire
bundle :
spare part no
109696
X75
CN
7
Analog
Interface
PCB
CN16
spare part
no:
CN
22 9708302034
Parameters
Tip #3 – Shield
You can get away without a shield. The twisted pair used for Tx and Rx is more effective at noise cancelation than the shield.
X60
RVS21
1024 10251026
Solution:
It means that we should reset the RVS21 to find the correct
connection.