PROFIBUS Basics

Active Stations

PC
PLC

PROFIBUS

Passive Stations (Field Devices)

s PROFIBUS Basics
Date 09/06/00, Page 1
PROFIBUS Basics

 All PROFIBUS services


 High Speed Data Exchange
 Peer to Peer
 Hazardous Area

 can be used together in one network


 Therefore Communication is Transparent for
the User
 Same Cable and Components for High Speed
Data Exchange and Peer to Peer

s PROFIBUS Basics
Date 09/06/00, Page 2
PROFIBUS Basics
 High-Speed Data Exchange Features
 Same priority for all field devices
 Communication is permanent & cyclic
 Amount of data specified during configuration
 Only one master can write to outputs (safety aspect)
 Acyclic communication to field devices possible by
using extended functions (DP Extended/DPV1)
 Alarm acknowledgment
 Up to 244 bytes input AND 244 bytes output data per
field device
 Fastest fieldbus system (up to 12Mbaud)

s PROFIBUS Basics
Date 09/06/00, Page 3
PROFIBUS Basics

 Plug & Play With Electronic Device Data Sheets


PROFIBUS
rat ion Configuration Tool
n fi gu
Co
t em
Sys

PLC
GSD GSD GSD GSD GSD GSD

Electronic Device Data Sheets (GSD, GSE, GSF, GSG, GSI, GSP, GSS Files)
PROFIBUS

s PROFIBUS Basics
Date 09/06/00, Page 4
PROFIBUS Basics
 High-Speed Data Exchange - Startup Sequence

Power ON/ Power ON/Reset of Master or Slave


Reset

Download of Parameters into the Field


Parameterization Device (selected during Configuration
by the User)

Download of I/O Configuration into the


I/O Configuration Field Device (selected during
Configuration by the User)

Cyclic Data Exchange (I/O Data)


Data Exchange
and Field Device reports Diagnostics

s PROFIBUS Basics
Date 09/06/00, Page 5
PROFIBUS Basics

 High-Speed Data Exchange - Parameterization


Parameter Download (up to 244 bytes)

Master Slave

 Features Implemented in Device


 Described in GSD File
 Processed by Configuration Tool
 Selected at Configuration
 Examples:
 Enable Channel Diagnostic
 Operation Range for Analog Channels
 (e.g. ±10V or 0..10V)
 Fail Safe Behavior (e.g. Hold Last
 Value)

= Parameterization Data = Confirmation (Data Received)

s PROFIBUS Basics
Date 09/06/00, Page 6
PROFIBUS Basics

 Parameterization (continued)
 Parameter selection with Configuration Tool

jsdfehrgihw[orijth]ewj]ypokjeky jsdfehrgihw[orijth]ewj]ypokjeky
gadfgsadfhsfghjjsffghsfgh gadfgsadfhsfghjjsffghsfgh
fdhsdldajhtviertivetvert fdhsdldajhtviertivetvert
34524 34524
575687356nj8467knggnhngjt 575687356nj8467knggnhngjt
rby5yik57859mnnbvt456hn, rby5yik57859mnnbvt456hn,
g76nkbvijyuftisdt0iewryt9eiuoriy g76nkbvijyuftisdt0iewryt9eiuoriy
rywkrowrgowrtohworthorthwrth rywkrowrgowrtohworthorthwrth
rthwrthrwthtryjtyjyuky rthwrthrwthtryjtyjyuky
tyjy7u79jtyu568566ut tyjy7u79jtyu568566ut
rtjhyuiuikujkhyjiyuiyuii rtjhyuiuikujkhyjiyuiyuii
thjyukiuio7ujtyujytuoiuky thjyukiuio7ujtyujytuoiuky
tyjyukuikyukuiluiliuioliuiluiil tyjyukuikyukuiluiliuioliuiluiil
6buhyijtiu8o67m8m747567n8 6buhyijtiu8o67m8m747567n8
567n75567nm78m78,om87o, 567n75567nm78m78,om87o,
56nu78m,,9o,0p.90.p;0;.;’-;/ 56nu78m,,9o,0p.90.p;0;.;’-;/

Fewer DIP Switches - NO Handheld - NO Extensive Additional Documentation


User defines every Function in ONE Tool.

s PROFIBUS Basics
Date 09/06/00, Page 7
PROFIBUS Basics

 High-Speed Data Exchange - Configuration


Configuration Download (up to 244 bytes)

Master Slave

 Possible I/O Selections described in GSD File


 Processed by Configuration Tool
 Selected at Configuration
 Examples
 8DI (1 Byte), 8DO (1 Byte)
 2AI (2 Words), 2AO (2 Words)
 RS232 Interface, Counter Module

= Configuration Data = Confirmation (Data Received)

s PROFIBUS Basics
Date 09/06/00, Page 8
PROFIBUS Basics

 Configuration Tool (continued)


 I/O selection with Configuration Tool

s PROFIBUS Basics
Date 09/06/00, Page 9
PROFIBUS Basics

 PROFIBUS Demo

i o nn
t
ccti o
l ee
SSeel
I/IO
/O
&
rr &
t
eetee
m
rraam
a
PPa

s PROFIBUS Basics
Date 09/06/00, Page 10
PROFIBUS Basics

 High-Speed I/O - Data Exchange & Diagnostics

Data Exchange (up to 244 bytes)

Master Slave

Slave indicates diagnostics to report

Master Slave

= Output Data = Input Data = Diagnostic Indicator

s PROFIBUS Basics
Date 09/06/00, Page 11
PROFIBUS Basics

 Data Exchange & Diagnostics (continued)

Diagnostic Request and Response (up to 244 bytes)

Master Slave

Data Exchange (up to 244 bytes)

Master Slave

= Diagnostic Request = Diagnostic Response

s PROFIBUS Basics
Date 09/06/00, Page 12
PROFIBUS Basics

 Diagnostic Response (continued)

Up to 244 Bytes

Header Header Header

6 Bytes Device Identifier Channel


Mandatory Related Related Related
(Optional) (Optional) (Optional)

g
. w ron n load le #
4 ak o
r
e.g uratio no u r e
fig e.g. wer mo d
s tic ire b rcuit
con po e.g. diagno . w
e.g ort ci
has sh

s PROFIBUS Basics
Date 09/06/00, Page 13
PROFIBUS Basics
 High-Speed Data Exchange - Fail Safe

What happens if my bus fails:


valve open, valve closed,
valve 1/2 open…???

v i or roof f
beehhaavsio
i f i ee
ss b Loosss
c i n
f e ssppeecniifcaatitoion L
Fa ililSSaafoemmmuunic
e a t uurere Fea oof fCCom
n a l lf featn caasse
i o a i c
OOppt tiountppuutsts in
OOut
s PROFIBUS Basics
Date 09/06/00, Page 14
PROFIBUS Basics

 Fail Safe (continued)


 Optional Feature for Field Devices
 Defined in Electronic Device Data Sheet
 Manufacturer has the capability to allow the End
User to specify the action on loss of communication
 Hold outputs at the last value received (e.g. valve 1/2 open)
 Set outputs to a specified value (e.g. open or close valve
completely)
 User defines action during Parameterization

s PROFIBUS Basics
Date 09/06/00, Page 15
PROFIBUS Basics

 Fail Safe (continued)

s PROFIBUS Basics
Date 09/06/00, Page 16
PROFIBUS Basics

 PROFIBUS Demo

affee
i l SSa
FFaail
s &&
t i cics
oosst
n
i aiaggn
DD

s PROFIBUS Basics
Date 09/06/00, Page 17
PROFIBUS Basics

 High-Speed Data Exchange Timing


 10 Stations With 2 Byte I/O (160 In/Output Signals)
 Bus Cycle Time 0.8ms

s PROFIBUS Basics
Date 09/06/00, Page 18
PROFIBUS Basics

 High-Speed Data Exchange Timing


 10 Stations With 128 byte I/O (10,240 In/ Output Signals)
 Bus Cycle Time 2.0ms

s PROFIBUS Basics
Date 09/06/00, Page 19
PROFIBUS Basics

 High-Speed Data Exchange Timing


 Typical Cycle Time - Each Station With 2 Byte I/O

20.0
20.5

18.0

16.0
14.1
14.0 12MBaud
12.0 1.5MBaud
[ms]

10.0 7.7 500kBaud


8.8
8.0
6.1
4.6
6.0
3.3
4.0
0.9 2.0
2.0 2.0 1.5 2.1
0.8
0.0 0.3 0.5
1 5 10 20 30 [Number of
Slaves]

s PROFIBUS Basics
Date 09/06/00, Page 20
PROFIBUS Basics

 PROFIBUS Summary
 Extensive Parameterization Features
 Extensive Diagnostic Features
 Fail-Safe Behavior
 Deterministic
 Fast (Up to 12 MBaud)
 Safe and Reliable
 Easy Configuration
 Capabilities for Complete Plant Solution from
Cell to Bit Level

s PROFIBUS Basics
Date 09/06/00, Page 21