Symmetrical Components
Symmetrical Components
31.01.25 1
Fault Analysis
Fault types:
balanced faults Percentage of total faults
three-phase <5%
unbalanced faults
single-line to ground 60-75%
2
Symmetrical Components
a 3 10 1 j 0
1 a a 2 0
3
Symmetrical Components
Positive sequence phasors
I a1 I a1 I a1
I c 0 I a 0 I a 0
I a 1 1 1 Ia0
I 1 a 2 a I a1
b
I c 1 a a 2 I a 2
or
1 1 1
I abc = A I 012 where A 1 a 2 a
1 a a 2
In component form
1
I a 0 ( I a Ib Ic )
3
1
I a1 ( I a aI b a 2 I c )
3
1
I a 2 ( I a a 2 I b aI c )
3
7
Symmetrical Components
Similar expressions exist for voltages
Vabc A V012
V012 A 1 Vabc
The apparent power of symmetrical components
T
S3 Vabc I*abc ( AV012 )T (AI 012 )*
T
V012 A T A*I*012
T *
3V012 I 012
31.01.25 9
Example 2
I a1 0.94 0.1
3
Ia2 0.6022.3
3
10
Example 2
11
Example 3
31.01.25 12
Example 4
31.01.25 13
Example 4
31.01.25 14
Example 5
Given a set of symmetrical components
15
Example 5
16
Example 6
31.01.25 17
Use of Symmetrical Components
31.01.25 18
Use of Symmetrical Components
31.01.25 19
Networks are Now Decoupled
31.01.25 20
Grounding
31.01.25 21
Grounding, cont’d
31.01.25 22
Sequence Impedances
23
Balanced Loads
Governing equaiton
Va Z S I a Z M I b Z M I c Z n I n
Vb Z M I a Z S I b Z M I c Z n I n
Vc Z M I a Z M I b Z S I c Z n I n
Matrix notation
I n I a I b I c
Va Z S Z n ZM Zn ZM Zn Ia
V Z Z ZS Zn Z M Z n I b
b M n
Vc Z M Z n ZM Zn Z S Z n I c
24
Balanced Loads
Sequence impedance
Vabc Z abc I abc A V012 Z abc A I 012
V012 A 1Z abc A I 012
Z012
Z 012 A 1Z abc A
1 1 1 ZS Zn ZM Zn Z M Z n 1 1 1
1
1 a a 2 Z M Z n ZS Zn Z M Z n 1 a 2 a
3
1 a 2 a Z M Z n ZM Zn Z S Z n 1 a a 2
Z S 3Z n 2 Z M 0 0
0 ZS ZM 0
0 0 Z S Z M 25
Transmission Line
Va1 Z S I a Z n I n Va 2
Vb1 Z S I b Z n I n Vb 2
Vc1 Z S I c Z n I n Vc 2
Vn 0 Z n I n
I n I a I b I c 0
Va1 Z S Z n Zn Z n I a Va 2
V Z ZS Zn Z n I b Vb 2
b1 n
Vc1 Z n Zn Z S Z n I c Vc 2
26
Transmission Line
Sequence impedance
Vabc1 Z abc I abc Vabc 2 A V012,1 Z abc A I 012 A V012,2
28
Generator Model
29
Generator Model
Wye-connected generator
30
Generator Model
Wye-connected generator
31
Generator Model
32
Generator Model
33
31.01.25 Sayasun 34
Generator Model
Wye-connected generator (with grounded
impedance)
Z S 3Z n 0 0
Z 012 0 ZS 0
0 0 Z S
35
Generator Model
36
Generator Model
Delta-connected generator
37
Generator Model
Delta-connected generator
38
Transformers
Series Leakage Impedance
the magnetization current and core losses are
neglected (only 1% of the total load current)
the transformer is modeled with the equivalent series
leakage impedance
Three single-phase units
the series leakage impedance is the same for all the
sequences Z 0 Z1 Z 2 Z l
Three-phase units
the series leakage impedance is the same for the
positive and negative sequence Z1 Z 2 Z l
39
Transformers
Wye-delta transformers phase shifting pattern
The positive sequence quantities rotate by +30 degrees
The negative sequence quantities rotate by -30 degrees
The zero sequence quantities can not pass through the
transformer
U.S. standard
Independent of the winding order ( Y or Y )
The positive sequence line voltage on the HV side leads
the corresponding line voltage on the LV side by 30
degrees
For the negative sequence voltages the corresponding
phase shift is -30 degrees
40
Transformers
Zero-sequence network connections of the
transformer depends on the winding connection
Grounded-wye/grounded-wye
Grounded-wye/wye
41
Transformers
Wye/wye
Grounded-wye/delta
42
Transformers
Wye/delta
Delta/delta
43
Transformer Sequence Diagrams
31.01.25 44
Sequence Networks
The zero-, positive-, and negative-sequence networks of system
components—generators, motors, transformers, and transmission
can be used to construct system zero-, positive-, and negative-
sequence networks. We make the following assumptions:
The power system operates under balanced steady-state conditions before the
fault occurs. Thus the zero-, positive-, and negative sequence networks are
uncoupled before the fault occurs. During unsymmetrical faults they are
interconnected only at the fault location.
Prefault load current is neglected. Because of this, the positive sequence internal
voltages of all machines are equal to the prefault voltage VF. Therefore, the
prefault voltage at each bus in the positive-sequence network equals VF.
Transformer winding resistances and shunt admittances are neglected.
Transmission-line series resistances and shunt admittances are neglected.
Synchronous machine armature resistance, saliency, and saturation
are neglected.
Induction motors are either neglected (especially for motors rated 50 hp or less)
or represented in the same manner as synchronous machines.
31.01.25 45
Example 5
31.01.25 46
Example 5
31.01.25 47
Example 6
Obtain zero-sequence network
31.01.25 48
Example 6
31.01.25 49
Example 6 (2011-2012 Final Exam)
31.01.25 50
Homework 1
Obtain the positive, negative and zero sequence network
31.01.25 51