5_RC-10 Measurement and Data Logging Capability

The document outlines the RC-10 measurement and data logging system, detailing its capabilities to measure various electrical parameters such as current, voltage, power, and frequency across multiple phases. It also describes the data logging features, including logs for close/open operations, events, changes, load profiles, and lifetime counters, with specific details on the types of data recorded and their accessibility. The system is designed for comprehensive monitoring and analysis of electrical performance and protection operations.

Uploaded by

RachidBaroudi
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

5_RC-10 Measurement and Data Logging Capability

The document outlines the RC-10 measurement and data logging system, detailing its capabilities to measure various electrical parameters such as current, voltage, power, and frequency across multiple phases. It also describes the data logging features, including logs for close/open operations, events, changes, load profiles, and lifetime counters, with specific details on the types of data recorded and their accessibility. The system is designed for comprehensive monitoring and analysis of electrical performance and protection operations.

Uploaded by

RachidBaroudi
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 15

RC-10 Measurement and

Data Logging
Measurement

• 3 x CTs and 6 x CVSs allows to measure and calculate:


– Current in each phase
– Residual Current
– Phase-To-Earth Voltage
– Phase-To-Phase Voltage
– Single and 3 phase Total, Active and Reactive Power
– Single and 3 phase Total, Active and Reactive Energy
– Single and 3 phase Power Factor
– Frequency on each side of the recloser
– Phase Sequence on each side of the recloser
• Available for viewing on LCD, CMS and reporting in DNP3
• Measurement coefficients are programmed in the Relay for each
recloser
Measurement
Applicability
Measured value Designation Measured range Resolution
Protection Indication
Phase currents Ia, Ib, Ic 0 – 16000A 1A  
Residual current1 In 0 – 16000A 1A  
Phase to earth voltages Ua, Ub, Uc, , Us, Ut 0.5 – 22kV 0.1kV  
Line to line voltages Uab, Ubc, Uca 0.5 – 38kV 0.1kV  
Positive sequence current I1 0 – 16000A 1A  –
Positive sequence voltage U1 0.5 – 38kV 0.1kV  –

Residual voltage2 Un 0.5 – 22kV 0.1kV  –


Phase shift between positive A1 0 – 359o 1o  –
sequence voltage and
current
Phase shift between residual A0 0 – 359o 1o  –
voltage and current

Single and three phase total, A, B & C kVA / kW / kVAr 0 – 65535 1 – 


active and reactive power 3 phase kVA / kVAr / kW

Single and three phase total A, B & C +/ – kVAh 0 – 999999999 1 – 


and reactive energy related A, B & C +/ – kVAhr,
to forward and reverse
power flow directions 3 phase +/ – kVAh
3 phase +/ – kVArh

Frequency from ABC and Fabc, Frst 46 – 65 Hz 0.01Hz  


RST recloser sides
Phase sequence from ABC Phase seq. ABC / ACB / ?3 NA – 
and RST sides RST / RTS / ?3
Single phase and three Power factor: 3phase, A 0 – 1 0.01 – 
phase power factor phase, B phase, C phase
Measurement

• Measurement Settings configured:

– System Voltage U_sys: 3 – 38 kV, 0.1 kV resolution


– System Frequency F_rated: Auto/50/60 Hz
– LSD Level: 0.5 – 6.0 kV, 0.1 kV resolution
Data Logging
• Following data is logged in the controller:

– Close/Open (CO) operations log with pre-fault history


– Event Log
– Change Messages Log
– Load Profile
– Lifetime and Fault Counters
Data Logging: CO Log
• This log registers last 1,000 Close/Open operations of the recloser
– Date and time event registered
– Event title (Open/Closed)
– Source of event
– Relevant state (O1-Lockout, O2, O3, O4 and C1, C2, C3 and C4)
– Critical parameter
– Phase and residual currents at time of initiation of trip command.
• CO log is visible on Operator Panel and in CMS
• Can not be reset from Panel or CMS
Data Logging: CO Log
• State Status diagram
Applicable sources
Event Relevant state Critical parameter
of event
Open Any protection element O1 (Lockout) Values registered between pickup start and open events
Operator by means of or Maximum phase current (Max(Ia) / Max(Ib) / Max(Ic)) for OC
Panel, CMS, I/O, O2 / O3 / O4 elements
SCADA or mechanical (waiting to reclose) Maximum residual current (Max(In)) for EF elements
trip ring
Minimum positive sequence voltage (Min(U1)) for UV1
Minimum line to line voltage (Min(Uab) / Min(Ubc) /
Min(Uca)) for UV2
Maximum positive sequence voltage (Max(U1)) for OV1
Maximum line to line voltage (Max(Uab) / Max(Ubc) /
Max(Uca)) for OV2
Minimum frequency (Min(F)) for UF
Maximum frequency (Max(F)) for OF

Closed Any Auto Reclose C2 / C3 / C4 for AR NA


element, ABR, Panel, OCEF, AR SEF, AR
SCADA, PC, I/O V.
C1 for others
Data Logging: Fault Profile
• Includes records for last 8 protection operations
• Each Record is provided with up to 50 readings of Currents, Voltages,
Frequency and angles. Full list of parameters:
– Ia, Ib, Ic, In, Ua, Ub, Uc, Uab, Ubc, Uca, U1, F, A0 and A1
• Values recorded for each cycle. The record with the highest sequential
number is the time at which the OSM tripped.
• Available for access through PC only
Data Logging: Fault Profile
Data Logging: Event Log
• The event log registers up to 10,000 events recording:
– Date and time registered
– Event title
– Source of event
– Relevant phase
– Critical parameter
• Event log is visible on Operator Panel and in CMS
Data Logging: Change Messages Log
• The event log registers up to 1,000 events associated with changes of
settings, protection status, External load status, control mode or erasing
energy meter readings, fault counters readings, CO Operations, event log,
load profile or change messages:
– Date and time registered
– Changed Parameter
– Old Value
– New Value
– Source of change
• Change messages log is visible in CMS only
Data Logging: Load Profile
• Load Profile can registers up to 10,000 records
• Fully configurable. Up to 30 items can be selected for recording
• Configured and viewable using CMS only
• Logging Interval ΔT: 1,2,5,10,15,30,60,120 min
• Can be viewed in CMS only
• Load Profile can not be erased from panel or CMS
Data Logging: Load Profile
• Load Profile configurable parameters
Data Logging: Lifetime Counters

• Includes
• Total number of Open/Close Operations
• Mechanical and Contact Wear
• Values are calculated and updated after each Close/Open operation
• Number of Operations and Contact Wear can not be reset
Data Logging: Lifetime Counters

• Fault Counters record the number of protection trips by each of the


following:
– Phase Overcurrent (OC) for each phase
– Earth Fault (EF)
– Sensitive Earth Fault (SEF)
– Under Voltage (UV)
– Under Frequency (UF)
• Fault Counters are resettable from Operator Panel, CMS or SCADA
• Event logged when Fault Counters are reset