GROUP SIX
GROUP SIX
a). The refrigerant leak caused by a failed O-ring, seal, hose, or any component
b). A clogged expansion tube or refrigerant charging hose
c). Failed compressor or compressor clutch
d). Failed blower motor or blower motor resistor
e). Damaged or failed condenser or evaporator
f). Vacuum leaks
g). Failed electrical component like switch, fuse, relay, control module, blend door, or solenoid
h). Blocked filter at the dryer or expansion valve.
i). Condenser fan motor issue, less heat transfer available for a given mass of refrigerant.
j). Compressor capacity control faulty leading to less coolant effect across the thermostatic expansion valve.
Troubleshooting & Diagnosis;
Diagnosing an air conditioning cooling problem is best done by connecting a gauge set to the high and low-pressure
service fitting on the system. Refer to the table below for the common remedies;
Low side High Side Cabin Temperature Possible Cause
Low Low Warm Low refrigerant charge
High High Warm Overcharge of refrigerant
High High Some cool Overcharge or Air in the system
Normal Normal Warm Too much oil or moisture in the system
Low Low Warm Expansion valve stack closely, orifice tube plugged
High Low Warm Compressor or control valve failed
2. Low refrigerant charge
• Low discharge and suction pressure. • Check for leaky points by halide torch or soap
solution or electronic leak detectors.
• Compressor motor getting tripped by low
pressure cut out trip. • Charge the system.
• Large bubbles in the liquid sight glass. • Achieve the correct pressure gauge reading.
• Compressor discharge temperature high.
3. Refrigerant Charging
b) Determine the correct ambient air temperature using the manufacturer’s manual or on the web. Do not charge
the vehicle if the temperature is below 55°F . Below is the Temperature pressure chart for R-134a.
4. Refrigerant overcharge
AC should not be overcharged as it may damage the compressor. Weigh the charge and use a gauge when
recharging.
Symptoms of overcharging;
Remedy:
Release the excess refrigerant into a recovery bottle and avoid any leaks directly into the atmosphere
5. Air in the Refrigerant Circuit
This air can cause;
a. Compressor overheating with high discharge pressure and normal condensing temperature.
b. The appearance of small bubbles in the sight glass.
c. Condensing pressure high.
d. Cooling capacity reduced.
e. Pressure gauge of the condenser jumps indefinitely
Remedy:
- Use a vacuum pump to purge the AC system prior to recharging Vaccum pump shpuld ru for about 30mins to
properly evacuate the system.
- Air in the system can be collected using the condenser. Close the condenser valve as the compressor is running.
Vent he collected air through the venting valve and immediately close the valve
6. Moisture in the Refrigeration Circuit
Moisture can cause;
a. Evaporator starving of refrigerant and rapid rise in condenser pressure causes a compressor to short cycle.
b. Icing at the expansion valve filter. When the expansion valve freezes, refrigerant flow is reduced, and cooling is
also reduced.
c. Moisture can cause corrosion and damage to the motor windings.
Remedy;
Remedy;
-Replace the air filter
-Add antibacterial solution to the evaporator area to kill mold.
Remedy;
- Check the system for any substances trapped like leaves
- Use the correct refrigerant and lubricants
- Check hoses and support brackets for proper positioning
- You may do a general check up of the whole system for failed parts, replace where necessary
10. The AC goes from cold to hot.
This could be a result of ;
- A blocked expansion valve preventing refrigerant from reaching the evaporator
- Compressor cycles quicky from on and off due to a faulty thermostat and low refrigerant
Remedy;
Test the system pressure
Check components for blockage and multifunction.
11. Problems with compressors and clutch.
a) Low suction pressure
Causes Repair
• Refrigerant shortage • Recharge
• Worn compressor piston • Replace compressor
• Compressor leakage ( in valve or gasket) • Replace gasket, change valve plate
• Flattened hose • Change hose or remold the flattened
• Moisture in system • Replace drier. ( Check previous chapter on how to
handle this)
• Trash in expansion valve
• Clean or replace valve
b) High suction pressure
Cause Remedy
Loose expansion valve Tighten it
Overcharged system Discharge extra refrigerant
Expansion valve stuck open Change valve
Compressor reed valve Change reed valve
Leaking head gasket on compressor Replace gasket
Frozen coil, switch set too high Adjust the thermostat switch
Drive belt slipping Tension the belt
Hot air leaks into the car Check for holes and open vents
Plugged receiver drier Replace drier
Broken Capillary tube Replace expansion valve
Low refrigerant charge Recharge
Defective expansion valve Replace with a new one
Frozen expansion valve Evacuate and replace drier
14. Common problems with metering devices
Metering devices are mainly orifice tubes and thermostatic expansion valve. Both have same symptoms which are indicated by
low gauge pressure caused by a clogged screens of the two components ( orifice tube screen, & inlet and outlet screens).
Examine the screens for any pieces of clogged material;
If the blockage is grey/ brown then its probably a ruptured discant bag in the receiver/ drier or accumulator
If its shiny metal chip then the compressor might be failing
If the blockage is a black granular then it’s a residue in the hose caused by a reaction between moisture and the refrigerant
forming an acid which breaks down hoses and seals