s PROFIBUS PA
Date 09/19/00, Page 1
PROFIBUS PA
Physical Setup
Physical layer based on IEC 1158-2
Synchronous data transfer with Manchester coding
Power AND data are transferred via the same wire
Different components for the physical setup (cable,
connectors, termination…)
Rules regarding topology and length according to
IEC 1158-2
Transmission rate is 31.25kbaud
s PROFIBUS PA
Date 09/19/00, Page 2
PROFIBUS PA
s PROFIBUS PA
Date 09/19/00, Page 3
PROFIBUS PA
Message Structure
SD LE LEr SD DA SA FC DU.. FCS ED
P: 16 Bit Preample
SD: Start Delimiter
LE: Net Data Length (DU) + DA, SA , FC, DSAP, SSAP
LEr: Length repeated
DA: Destination Address (Where the message goes to)
SA: Source Address (Where the message comes from)
FC: Function Code ( FC=Type & Priority of Message)
DU: Data Unit (Up to 246 Bytes including 2 Bytes for SAP’s)
FCS: Frame Checking Sequence
CRC: 16 Bit Cyclic Redundancy Check
ED: End Delimiter
EOF: End Of Frame
s PROFIBUS PA
Date 09/19/00, Page 4
PROFIBUS PA
Character Format
Clock
Binary 0 1 0 1 0 0 1 1 0 0 1 1 0 0 0 1 0
+
„1“
NRZ 0
(PROFIBUS) „0“ 0
+
Manchester „1“ 0
Bitphase L 0 -
(PROFIBUS-PA) +
„0“ 0
-
s PROFIBUS PA
Date 09/19/00, Page 5
PROFIBUS PA
Network Addressing
1 1
PROFIBUS PROFIBUS
45.45kbaud up to 12Mbaud
PA Link
2 X PA Link
3 X
X PA X PA 24 V
PA
24 V
PA
24 V
Coupler
24 V
Coupler 1 Coupler
1 Coupler
2 3 4 3 4 3
PROFIBUS PA 31.25kbaud
s PROFIBUS PA
Date 09/19/00, Page 6
PROFIBUS PA
Network Topology
Spur
Line
PROFIBUS
Star
(Main) Line
24 V
s PROFIBUS PA
Date 09/19/00, Page 7
PROFIBUS PA
+
-
s PROFIBUS PA
Date 09/19/00, Page 8
PROFIBUS PA
Network Setup - Rules (continued)
PA
24 V Coupler
Up to 31 PA field
devices can be
connected to ONE
coupler
s PROFIBUS PA
Date 09/19/00, Page 9
PROFIBUS PA
= PA Link = PA Coupler
s PROFIBUS PA
Date 09/19/00, Page 10
PROFIBUS PA
Network Setup - Rules (continued)
PA Link PA
Coupler
24 V
Up to 31 PA field devices
can be connected to ONE
link - INDEPENDENT of the
number of couplers
s PROFIBUS PA
Date 09/19/00, Page 11
PROFIBUS PA
Network Setup - Rules (continued)
PA Link PA
Coupler
24 V
s PROFIBUS PA
Date 09/19/00, Page 12
PROFIBUS PA
24 V
Maximum segment length
per coupler = 1,900m
s PROFIBUS PA
Date 09/19/00, Page 13
PROFIBUS PA
Network Setup - Rules (continued) (Allowed Length
PER Drop/Spur Line)
140
120
120
40 30
30 30 30
20
0
1..12 13..14 15..18 19..24
s PROFIBUS PA
Date 09/19/00, Page 14
PROFIBUS PA
PA Profile
Definition on the application layer level
Profile defines variables, function blocks, meaning of
the data, mapping to communication services...
Devices with the same profile implemented can be
exchanged
Current version of PA Profile is V3.0
Available as official PROFIBUS International
document with order no. 3.042
Pre-defined GSD files for various PA field devices
available
s PROFIBUS PA
Date 09/19/00, Page 15
PROFIBUS PA
PA Profile (continued)
Status DP services
cyclic and
Measured value acyclic
Profile B
Measuring range
Filter time
(e.g. for
Alarm/warning limits pressure
DP Services transmitters)
Alarm summary acyclic
TAG
Manufacturer-specific DP services
parameters acyclic
s PROFIBUS PA
Date 09/19/00, Page 16
PROFIBUS PA
Electronic Data Sheets
GSD
PROFIBUS
Configuration Tool
DD PROFIBUS
Engineering Tool
PA Field
Device Device Description File for
specification of functionality
s PROFIBUS PA
Date 09/19/00, Page 17
PROFIBUS PA
Engineering Tool
PROFIBUS (up to 12 Mbaud)
Engineering Tool
(Diagnostic Master)
s PROFIBUS PA
Date 09/19/00, Page 18