Dc Measuring Devices
Dc Measuring Devices
3 Electrical parameters
5 Handling of abnormal
problems
www.nrec.com 2
Overview
Function of DC measuring equipment
High voltage isolation
Proportional transformation: transfer the primary high voltage and current
to DC control and protection system in proportion 。
www.nrec.com 3
Overview
Air-core
Used in neutral line in HVDC coil
Only Used for harmonic
Zero flux
current monitoring
CT
Photoelectric Shunt
Electroma
-gnetic CT
Used in resistance and inductance
branch of DC filter
www.nrec.com 4
Overview
Resistance-
Capacitance Used for measuring DC voltage
divider
VT in the
converter station
www.nrec.com 5
Overview
www.nrec.com 6
Overview
Qty Qty.
No. Model Specifications
.(Mutiari) (Lahore)
PCS-9250- ±660kV,3030.3A
1 EACD-660S- For the DC current measurement of 660kV pole line current 2 2
3030.3 at outdoor valve top
PCS-9250- ±660kV,3030.3A
2 EACD-660S- For the DC current measurement of pole line current at 2 2
3030.3 outdoor DC field
PCS-9250- ±660kV,3030.3A
3 EACD-660S- For the DC current measurement of outdoor DC filter high- 4 4
3030.3 voltage circuit current
PCS-9250- ±150kV,3030.3A
4 EACD-150S- For the DC current measurement of outdoor DC filter low- 4 4
3030.3 voltage circuit current
PCS-9250-EAC- ±350kV,1AAC
5 4 4
350S-1 For measuring unbalance current of DC filter
±660kV
PCS-9250-
6 For the measurement of pole line voltage at outdoor DC 2 2
EAVD-660
field
±100kV
PCS-9250-
7 EAVD-100
For the measurement of neutral busbar voltage at outdoor 2 2
DC field
www.nrec.com 7
1 Overview
3 Electrical parameters
5 Handling of abnormal
problems
www.nrec.com 8
Working principle _ DCCT
PCS-9250-EACD type
DC electronic CT
www.nrec.com 9
Working principle _ DCCT
PCS-9250-EACD DC electronic CT
(1)Primary sensor: it includes one shunt and one air-core coil (i.e. Rogowski coil, only
configured in pole line CT). The shunt is used to measure DC current, while the air-core
coil is optional and used to measure harmonic current only. 。
(2) Resistor borad: it functions as signal distribution, converts one analog signal to
multiple signal outputs physically.
(3) Remote terminal unit: also called primary converter, it is located at high-voltage side
and used for data acquisition, multiple RTUs can be configured in ECT.
(4) Optical fiber insulator: it is a solid composite insulator with embedded optical fibers.
(5) Merging unit: placed in the control room. It is used for providing laser energy to power
RTUs, receiving and processing the data from the RTUs and transmitting them to the
control & protection system according to IEC 60044-8 protocol.
www.nrec.com 10
Working principle _ DCCT
Shunt
Shunt is connected with primary current
circuit in series, used for transducing DC
current as a key component of DCCT.
It is equivalent to a high power, high
temperature resistance, low temperature
coefficient, precise, and low value resistor.
The rated output of the shunt is about 75mv,
for 3030.3A rated primary current, the
shunt resistance is designed to be 25uΩ.
The shunt is made of Manganese-Copper
alloy, and it is designed as “symmetric
squirrel-cage structure” to realize good
heat dissipation and anti-interference.
www.nrec.com 11
Working principle _ DCCT
Air-core Coil (i.e. Rogowski coil)
www.nrec.com 12
Working principle _ DCCT
Resistor box (Signal distribution box)
Used for converting one channel of analog signal output into multiple channels of analog signal
for RTUs. It receives the analog voltage signal output by the shunt, convert it into multi-channel
analog signal output, and connect to multiple remote modules for processing.
The resistance box and the RTUs are located in the closed metal box at the high voltage side .
www.nrec.com 13
Working principle _ DCCT
Remote Terminal Unit (RTU, or remote
module)
Receiving the analog signal output from the resistance box, after
filtering, sampling, electro-optical conversion, etc., it gives an output
of serial digital optical signal.
Located at high voltage side, its power supply is provided by the
merging unit through the laser light. An optical fiber receiving
connector(FC type) is used to receive laser, and an optical fiber
transmitting connector(ST type) is used to send digital signals.
low-power design and dual sampling.
www.nrec.com 14
Working principle _ DCCT
Remote Terminal Unit (RTU, or remote
module)
www.nrec.com 15
Working principle _ DCCT
Optical fiber Insulator
When installed in suspension type, using suspended optical fiber
Optical
insulator. And also could be support type. fibers
www.nrec.com 16
Working principle _ DCCT
typical configuration
1#RTU 1#MU
①
② 2#RTU 2#MU
③
④ 3#RTU
IN
⑤ 3#MU
⑥
⑦ 4#RTU
(spare)
⑧
5#RTU
(spare)
www.nrec.com 17
Working principle _ DCCT
Merging Unit (MU)
Sending laser to power the RTUs, and adjusting the
power supply in real time according to the working
condition of each RTU.
Receiving and processing the data sent by up to 9 RTUs,
packaging the output data of multiple RTUs, outputing
according to IEC 60044-8 protocol.
Self-monitoring function, monitoring parameters: laser
driving current, receiving data level, RTU temperature,
laser temperature, parity check error times. 。
www.nrec.com 18
Working principle _ DCCT
www.nrec.com 19
Working principle _ ACCT
PCS-9250-EAC type
electronic CT for AC
unbalance current in the
midpoint of the capacitor
banks in DC filters
www.nrec.com 20
Working principle _ ACCT
PCS-9250-EAC AC electronic CT
(1)Primary sensor: Low-Power CT (LPCT) is used to transduce AC current.
(2) Resistor box: it functions as signal distribution, converts one analog signal to multiple
signal outputs.
(3) Remote terminal unit: also called primary converter, it is located at high-voltage side
and used for data acquisition, multiple RTUs can be configured in ECT.
(4) Optical fiber insulator: it is a solid composite insulator with embedded optical fibers.
(5) Merging unit: placed in the control room. It is used for providing laser energy to
power RTUs, receiving and processing the data from the RTUs and transmitting them
to the control & protection system according to IEC 60044-8 protocol.
www.nrec.com 21
Working principle _ ACCT
Low-Power CT (LPCT)
Np
U s Rsh I p
Ns
www.nrec.com 22
Working principle _ ACCT
Resistor box
Expands one input to a maximum of 6 outputs.
www.nrec.com 23
Working principle _ ACCT
Remote Terminal Unit (RTU)
Working principle and structure is similar with PCS-9250-EACD DCCT,
different borads.
Optical fiber Insulator
Similar with PCS-9250-EACD DCCT.
Merging Unit (MU)
Different electronic CTs & VTs use the same MU which is PCS-221JB.
www.nrec.com 24
Working principle _ DCVT
PCS-9250-EAVD type
DC electronic VT
www.nrec.com 25
Working principle _ DCVT
PCS-9250-EAVD DC electronic VT
(1)DC voltage divider: it adopts resistor voltage divider with capacitor compensation,
the resistors and capacitors are located in a silicone rubber composite-insulation cylinder,
and the inside is filled with SF6 gas.
(2) PCS-9559 IO unit: it is used for analog quantity isolation, installed in cabinet at the
control room. The device is connected with the DC voltage divider through four-core
double-layer shielded cable. Each DC voltage divider is equipped with three sets of PCS-
9559 IO unit. The rated output signal of PCS-9559 is 5V
www.nrec.com 26
Working principle _ DCVT
DC voltage divider
DC voltage divider includes a high-voltage
arm and a low-voltage arm, the HV arm
consists of multiple links of modular RC units
in series.
The resistors and the capacitors of HV arm
of DC voltage divider are fixed in a silicone
rubber composite-insulation cylinder, and the
inside is filled with SF6 gas under a certain
pressure.
www.nrec.com 27
Working principle _ DCVT
PCS-9559 IO Unit
The main function of PCS-9559 IO unit is to divide
and isolate the output signal of DC voltage divider.
Each PCS-9559 is equipped with one resistor voltage
divider (NR1478) and two isolation output modules
(NR1411). Each DC voltage divider must be equipped
with three sets of PCS-9559 IO units. The rated
secondary output of the device is ±5V.
The configuration of the three sets of PCS-9559 is the
same, and three sets of voltage transformers (i.e. three
DC voltage measuring points) can be input. For each
DC voltage measurement point, it can output six
channels of independent differential voltages. To
facilitate connecting multiple loads of the latter stage,
each output can be extended to three channels, that is,
it can output 18 channels of differential voltages for
each DC voltage measurement point.
www.nrec.com 28
1 Overview
3 Electrical parameters
5 Handling of abnormal
problems
www.nrec.com 29
Electrical parameters
Model : PCS-9250-
EACD-660S-3030.3.
Used for measuring 660kV
pole line current at
outdoor
valve top, pole line current
at outdoor DC field,
outdoor DC filter high-
voltage circuit current, at
Matiari converter station
www.nrec.com 30
Electrical parameters
Model : PCS-9250-
EACD-660S-3030.3.
Used for measuring 660kV
pole line current at
outdoor
valve top, pole line current
at outdoor DC field,
outdoor DC filter high-
voltage circuit current, at
Lahore converter station
www.nrec.com 31
Electrical parameters
Model: PCS-9250-EACD-
150S-3030.3.
Used for measuring
outdoor DC filter low-
voltage circuit
current.
www.nrec.com 32
Electrical parameters
www.nrec.com 33
Electrical parameters
Model: PCS-9250-EAC-
350S-1, used for
measuring unbalance
current of DC filter at
Matiari converter station.
www.nrec.com 34
Electrical parameters
Model: PCS-9250-EAC-
350S-1, used for
measuring unbalance
current of DC filter at
Lahore converter station.
www.nrec.com 35
Electrical parameters
www.nrec.com 36
Electrical parameters
Model: PCS-9250-EAVD-
660, used for measuring
DC pole line voltage at
outdoor DC field.
www.nrec.com 37
Electrical parameters
Model: PCS-9250-EAVD-
100, used for measuring
neutral busbar voltage at
outdoor DC field.
www.nrec.com 38
Electrical parameters
www.nrec.com 39
1 Overview
3 Electrical parameters
5 Handling of abnormal
problems
www.nrec.com 40
Maintenance _ DCCT&ACCT
No. Item Cycle Requirements Remarks
www.nrec.com 41
Maintenance _ DCCT&ACCT
www.nrec.com 42
Maintenance _ DCCT&ACCT
www.nrec.com 43
Maintenance _ DCVT
No. Item Cycle Requirements Remarks
www.nrec.com 44
Maintenance _ DCVT
3 Electrical parameters
5 Handling of abnormal
problems
www.nrec.com 46
Handling of abnormal problems
1)Measurement value of CT is abnormal
Multiple Single measurement
measurement value value is abnormal
are abnormal
www.nrec.com 47
Handling of abnormal problems
2)Measurement value of DCVT is abnormal
Multiple Single measurement
measurement value value is abnormal
are abnormal
www.nrec.com 48
Handling of abnormal problems
3)Optical fiber transmission is abnormal ( DCCT , ACCT )
Optical fiber
transmission is abnormal
Optical fiber
failure, decay NR1125 RTU
or broken board failure
failure
Cross section of Fiber is
optical fiber is Fusion damaged
polluted or failure by force
scratched
Replace Replace
Inspect, clean the fiber when when
connector, replace when necessary necessary
necessary
www.nrec.com 49
Handling of abnormal problems
www.nrec.com 50
Thanks.
Version 2018
www.nrec.com
Copyright 2018 All Copyrights Reserved by NR Electric Co., Ltd.