POWER-POINT-EESD-512_MODULE-2
POWER-POINT-EESD-512_MODULE-2
PREPARED BY:
15 x 80% = 12 A
`
13.64 A > 12 A
15 AT is not
sufficient.
20 x 80% = 16 A
13.64A < 16 A
Therefore, 20
AT is sufficient.
Solution:
1. General Lighting = 13.64 A for branch circuit
• USE 20 AT/AF, 2.0mm2 THW Cu, 16mmØ PVC
Note: [See Table 3.10.2.6(B)(16) Conductor Ampacities, Page 174]
WIRE SIZING
Preferred Wire Type: THW, CU CB: 20 AT/AF
Instructions: Use the Circuit Breaker current trip as reference. If the exact current
is not present, use the higher available current.
VA1 = 6000 VA 0 VA
VA2 = 3000 VA 3,000 VA
3001 VA
VA3 = 1500 VA
10,500 VA
VA123 = 10,500 VA
Applying Demand Factor for loads 1-3
First 3000 VA @ 100% = 3000 VA
Next 7500 VA @ 35% = 2625 VA
I123 = 5625 VA / 220 V =5625 25. 57
VA A
for main
4. Clothes Dryer 3000 watts
5000 W / 220 V = 22.73 A for Main and for branch circuit
• USE 30AT/AF, 5.5mm2 THW Cu, 16mmØ PVC
[See Table 2.20.3.115 for Demand Factor p. 57]
The load for household electric clothes dryer in a dwelling unit (s)
shall be 5000 W or the nameplate rating whichever is larger. The
use of the demand factors in Table 2.20.3.115 shall be permitted.
Design Analysis
I123 = 25.57 A ISEC = IBL + 25 % (Highest Rated Motor)
I4 = 22.73 A ISEC = 127.64 A + 25 % (12 A)
I5 = 29.09 A ISEC = 130.64 A
I6 = 13.64 A
I7 = 9 A
I8 = 7.5 A IACB = IBL + 100 % (Highest Rated Motor)
I9 = 12 A IACB = 127.64 A + 100 % (12 A)
I10 = 8 A USEIACB175
= 139.64
AT/AF,A 2# 80mm2 THW Cu, 53mmØ EMT
I11 = 0.11 A
IBL = 127.64 A
SCHEDULE OF LOADS
16mmØ 20
1 Lighting Outlet 3000 220 13.64 2# 2.0 mm2 THW Cu
PVC AT/AF
16mmØ 20
2 Lighting Outlet 3000 220 13.64 2# 2.0 mm2 THW Cu
PVC AT/AF
16mmØ 20
3 Small Appliance 1500 220 6.82 2# 3.5 mm2 THW Cu
PVC AT/AF
16mmØ 20
4 Small Appliance 1500 220 6.82 2# 3.5 mm2 THW Cu
PVC AT/AF
16mmØ 15
5 Laundry 1500 220 6.82 2# 2.0 mm2 THW Cu
PVC AT/AF
16mmØ 30
6 Clothes Dryer 3000 220 22.73 2# 5.5 mm2 THW Cu
PVC AT/AF
21mmØ 50
7 Electric Range 8000 220 36.36 2# 8.0mm2 THW Cu
PVC AT/AF
16mmØ 15
8 Water Heater 2000 220 6.82 2# 2.0mm2 THW Cu
PVC AT/AF
16mmØ 15
9 Water Heater 2000 220 6.82 2# 2.0mm2 THW Cu
PVC AT/AF
16mmØ 30
10 Water Pump 2 HP 220 12 2# 5.5mm2 THW Cu
PVC AT/AF
16mmØ 20
11 Booster Pump 1.5 HP 220 10 2# 2.0mm2 THW Cu
PVC AT/AF
16mmØ 20
13 ACU 1 HP 220 8 2# 2.0mm2 THW Cu
PVC AT/AF
16mmØ 15
14 BELL SYSTEM 24 0.12 2# 2.0mm2 THW Cu
PVC AT/AF
ONE LINE DIGRAM
SAMPLE DESIGN
SAMPLE DESIGN
EESD 512
Electrical System Design
MODULE 3
Single Family Dwelling
PACKET 2
Single phase, 3-Wire System
PREPARED BY:
Most homes in USA are wired for three-wire service. Since electric
ranges and air conditioners are designed for three-wire operation, any
home which is to be provided with these appliances must have three-
wire service. The three wires terminate in the residence at the load
center panel so that most individual circuits carried through the house
are at 110 volts, thus eliminating the dangers with 220-volt circuits.
When sizing the load for a 3-wire circuit, the grounded neutral
conductor must carry the unbalanced load of the two ungrounded
phase conductors. This type of installation has an unbalanced load -
unless both ungrounded conductors pull the same amount of current
on each ungrounded phase conductor.
SINGLE FAMILY DWELLING 1Ø, 3 –WIRE SYSTEM
Use ACB for protection, THHN Cu for all conductors and PVC-40
for conduit of feeders and for main.
20 x 80% = 16 A
13.64A < 16 A
Therefore, 20
AT is sufficient.
I1 = 13.64 A
• Use: 20 AT/AF, 2# 2.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See Table
C.11 page 1027 for Conduit size
At 20 AT (nearest
25 A), THHN, CU,
the recommended
wire size is 2.0 mm2
I1 = 13.64 A
• Use: 20 AT/AF, 2# 2.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See Table
C.11 page 1027 for Conduit size
VA2 = 3000 VA
1500VA / 220V = 6.82A
I2 = 6.82 A
• Use: 20 AT/AF, 2# 3.5-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See Table C.11
page 1027 for Conduit size
3. Laundry Circuit – 1 branch, 220V
1500VA x 1 = 1500 VA
VA3 = 1500 VA
1500VA / 220V = 6.82A
I3 = 6.82 A
• Use: 15 AT/AF, 2# 2.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See Table
C.11 page 1027 for Conduit size
VA123 = 5625 VA
I123 = 5625VA / 220V = 25.57A
I123 = 25.57A Since the load is less than
5000W (3000W<5000W), then
4. Clothes dryer – 3 kW, 220V we will use 5000W.
I5 = 13.64 A *
2kW / 110V = 18.18A
• Use: 25 AT/AF, 2# 2.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See
Table C.11 page 1027 for Conduit size
6. Water heater – 2.5 kW, 110V
2.5kW / 110V x (75% demand factor) = 17.05A
[See Sections 2.20.3.14 Appliances Load – Dwelling Units(s). Page 57]
I6 = 17.05 A *
2.5kW / 110V = 22.73A
• Use: 30 AT/AF, 2# 3.5-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See
Table C.11 page 1027 for Conduit size
I8 = 48 A *
24A x 2 = 48 A
• Use: 50 AT/AF, 2# 8.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See
Table C.11 page 1027 for Conduit size
I10 = 29.09 A
8kW / 220V = 36.36A
• Use: 50 AT/AF, 2# 8.0-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See
Table C.11 page 1027 for Conduit size
I11 = 12 A *
16A x 2 = 32A
• Use: 40AT/AF, 2# 5.5-mm2 THHN Cu, 16 mm PVC 40
[See Table 3.10.2.6(B) (16) page 174 for Conductor size] and [See
Table C.11 page 1027 for Conduit size
L1 N L2N
I5 13.64 0
I6 0 17.05 A
I8 24 A 24 A
I11 12 A 0
I12 0 5.4 A
49.64 A 46.45 A
IBL = I220V + I110V (HIGHEST)
IBL = 94.21A + 49.64A
IBL = 143.85 A
Sizing of Service Entrance Conductor:
ISEC = IBL + 25 %( HRM)
[See section 4.40.1.7 Highest Rated Motor. Page 375]
ISEC = 143.85A + (0.25) (24)
ISEC = 149.85 A
Use: 200 AT/AF, 2 # 80-mm2 THHN Cu, 41 mm PVC 40 (tentative)
Sizing of Neutral Conductor:
IN = (70%) (IBL)
IN = (0.70) (143.85A)
IN = 100.70 A
• Use: 1 # 30-mm2 THHN Cu
2# 2.0mm2 16mmØ 20
1 Lighting Outlet 3000 220 13.64
THHN Cu PVC 40 AT/AF
2# 2.0mm2 16mmØ 20
2 Lighting Outlet 3000 220 13.64
THHN Cu PVC 40 AT/AF
2# 2.0mm2 16mmØ 15
5 Laundry circuit 1500 220 6.82
THHN Cu PVC 40 AT/AF
2# 3.5 mm2 16mmØ 30
6 Clothes Dryer 3000 220 22.73
THHN Cu PVC 40 AT/AF