AIR CONDITIONING FOR LARGE MULTISTORY BUILDINGSPREPARED BYNOOR AZILA BINTI JAMARILECTURERCIVIL ENGINEERING DEPARTMENT
Most large multistory buildings use highly centralized air conditioning equipment.  The roof and basement are the usual choice for these central station systems.  The basement has the advantage of easy utility connections, noise isolation, not being valuable rental area and the fact that structural loads are not a problem.INTRODUCTION
The roof is the ideal location for fresh air intakes and heat rejection to the atmosphere.Cooling tower are noisy, produce very hot and humid exhaust air, so the best location for cooling rower is placed on the roof.SECTION OF A TYPICAL MULTISTORY BUILDING WITH A ROOFTOP CENTRAL STATION MECHANICAL SYSTEM
In most buildings, the mechanical equipment is shown to be on the roof.  This section shows an all-air system served by a single central air handling unit on the roof.To avoid the large vertical ducts, separate air handling units can be placed on each floor and only water circulates vertically.  This saves much energy because moving air great distances requires much power.  MECHANICAL EQUIPMENT IS STILL ON THE ROOF, EACH FLOOR HAS A SEPARATE AHU
The advantage of all-air system is complete control over air quality is possible.  The disadvantage is that all-air systems are very bulky and a significant part of the building volume must be devoted to them.  There are 5 system in all-air system categories.i.   Central Plants     ii.  Variable Air Volume (V.A.V)    iii.  Terminal Reheat System     iv.  Multizone System      v.  Double Duct System  ALL-AIR SYSTEM
The central air conditioning system has the limitation of the same air quality being delivered throughout the building.If the structure is zoned or divided and compartmented into several different functions such as offices, workshops, canteen.The temperature of each element can be controlled with zoned thermostats.The fan precedes the chiller and reheater coils and blow air through the air-handling unit.Several ducts radiate from the unit to designated zones within the building. CENTRAL PLANTS SYSTEM
CENTRAL PLANTS SYSTEM
This is a single duct system that can easily have many zones.  A variable air volume control box is located wherever a duct enters a separate zone.A thermostat in each zone controls the air flow by operating a damper in the V.A.V control box.  More cooling is required, more cool air is allowed to enter the zone.   ii. VARIABLE AIR VOLUME SYSTEMS
VAV system.Floor plan of a VAV system.VAV control box.
At the first the terminal reheat system looks just like the V.A.V system but in fact it is very different.  This system has terminal reheat boxes in which electric strip heaters or hot water coils reheat air previously cooled.All others zones will reheat the cold air to the desired temperature.iii. TERMINAL REHEAT SYSTEMTerminal reheat system.
In this system, every zone receives air at the required temperature through a separate duct.These ducts are supplied by a special multizone air handling unit that custom mixes hot and cold air for each zone.  This is accomplished by motorized dampers located in the air handling unit but controlled by thermostats in each zone. Depending on the temperature, the ratio of hot and cold air varies but the total amount of air is constant.  iv. MULTIZONE SYSTEM
The multizone unit is supplied with hot water, chilled water and a small amount of fresh air.Each multizone unit can handle about 8 zones.Because moderate air temperatures are created by mixing hot and cold air, this system also wasteful of energy.Disadvantage this system are costs relatively high while the thermal control is relatively poor.
Like the multizone system, the double duct system mixes hot and cold air to achieve the required air temperature.Instead of mixing the air at a central air handling unit, mixing boxes are dispersed throughout the building.The double duct system creates a high level of thermal comfort and allows for great zoning flexibility, it is very expensive, requires much building space and its wasteful of energy.v. DOUBLE DUCT SYSTEMDouble duct system.
To reduce the size of the ducts, a high-velocity version of this systemHigh-velocity air systems (6000 feet/minute) consume more fan power than normal velocity systems(2000 feet/minute).Because of these problem and because V.A.V system are a good alternative, dual duct systems are not used much anymore.
These system supply both airand water to each zone of a building.It greatly decreases the size of the equipment because of the immense heart-carrying capacity of water as opposed to air.Air is supplied mainly because of the need for ventilation.There are 2 system in air-water system categories.i.  Induction System     ii.  Fan- coil with supplementary airBut in this topic is cover induction system onlyAIR-WATER SYSTEM
A small quantity of high-velocity air is supplied to each zone to supply the required fresh air and to induce room air to circulate.Most induction terminal units are found under windows where they can effectively neutralize the heat gain.  As the high-velocity air shoots into the room it induces a large amount of room air to circulates.This combination of room air and fresh air, then passes over heating or cooling coils.INDUCTION SYSTEM
Local thermostats regulate the temperature by controlling the flow of either hot or cold water through the coils.It takes a lot of fan power to circulate air at high velocity throughout a building.Because of the high cost of energy and the expense of high-velocity ductwork, the use of induction systems is limited.Induction system.
Induction system. Induction unit with cooling or heating coils
These systems supply no air.There are 2 system in all-water system categories.i.  Fan-coil System     ii.  Water Loop Heat Pump SystemBut in this topic is cover Fan-coil system only.ALL-WATER SYSTEM
The fan-coil unit basically consists of a fan and a coil within water circulates. The units are in the form of cabinets for placement under windows.The fan blows room air across coils containing  either hot or cold water.Thermostatically controlled valves regulate the flow of water through the coils.  A 4 pipe system, which is has 2 pipes for hot water supply and return and another 2 pipes for cold water supply and return.FAN-COIL SYSTEM
Condensation on the cooling coils must be collected in a pan and drained away.When the fan-coil unit is on an outside wall, it is possible to have an outdoor air intake connected to the unit.A three-speed fan switch allows occupants of the zone to have some control over the temperature.Fan-coil units are most appropriate for air conditioning buildings with small zones (eg. Apartments, condominiums, motels, hotels, hospitals and schools).Fan coil units also located above windows, in small closets or in the dropped ceiling above a bathroom.
Fan Coil System.Schematic diagram of an under window FCU ( 4 pipe system).
FCU placed in a small closet.FCU placed above a dropped ceiling.

More Related Content

PPTX
Air Conditioning system and types
PPTX
Architecture - Centralized Air Conditioning System
PPTX
Centralized ac system
PPTX
Packaged air conditioners
PPTX
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
PPTX
Airconditioning ppt
PDF
HVAC System Analysis of two-storey hospital building
PPTX
A.C. Duct
Air Conditioning system and types
Architecture - Centralized Air Conditioning System
Centralized ac system
Packaged air conditioners
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
Airconditioning ppt
HVAC System Analysis of two-storey hospital building
A.C. Duct

What's hot (20)

PDF
Case Study of Building Services in Multi-Purpose Buildings involving Public Use
PPT
BS5 - Lecture 1 Mechanical and Natural Ventilation
PDF
H.V.A.C building service in b.arch ciriculam
PPTX
Report on High Rise buildings.
PDF
Building Service Chapter 5
PPTX
Basements light and ventilation
PPT
Vertical transporation systems in building
PPTX
Fire fighting system in buildings
PDF
Window ac
PPT
PDF
Natural ventilation
PDF
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
PPTX
building service - lift and escalators
PPTX
Air conditioning system
PDF
Elevators and its types
PPTX
Ventilation Systems
PPTX
Vertical Circulation and Services of Highrise
PPTX
Human thermal comfort
Case Study of Building Services in Multi-Purpose Buildings involving Public Use
BS5 - Lecture 1 Mechanical and Natural Ventilation
H.V.A.C building service in b.arch ciriculam
Report on High Rise buildings.
Building Service Chapter 5
Basements light and ventilation
Vertical transporation systems in building
Fire fighting system in buildings
Window ac
Natural ventilation
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
building service - lift and escalators
Air conditioning system
Elevators and its types
Ventilation Systems
Vertical Circulation and Services of Highrise
Human thermal comfort
Ad

Similar to Air conditioning for large multistory buildings (20)

PPT
hvac-systems.ppt
PPT
Heat Ventilation and Air Conditioning system
PPTX
Air conditioning of small buildings
PPTX
Air conditioning of small buildings
PDF
Design options for hvac distribution systems
PPTX
2.AIR AND WATER AND ALL WATER SYSTEMS.pptx
PDF
Week 3- Comprehensive Analysis and Exploration of Air-Conditioning and HVAC S...
PPTX
prniciple of ACS.pptx
PPTX
Air Conditioning Systems in Refrigeration and Air Conditioning
PDF
Design of an Air Distribution System for a Multi Storey Office Building
PPTX
Week 6a HVAC Types jjj.pptx
PPTX
Air conditioning (1)
PPTX
Air Conditioning and Security Installations
PPTX
heat ventilation and Air conditioning.pptx
PPTX
Week 6a HVAC Types jjj (1).pptx
PPTX
INTRODUCTION TO HVAC SYSTEMS-Hospitality Engineering
PPTX
key Components of Air Distribution Systems.pptx
PPTX
Air Conditioning case study
PPTX
Air conditioning system
PPT
Cem 350 hvac air side systems 10-2016
hvac-systems.ppt
Heat Ventilation and Air Conditioning system
Air conditioning of small buildings
Air conditioning of small buildings
Design options for hvac distribution systems
2.AIR AND WATER AND ALL WATER SYSTEMS.pptx
Week 3- Comprehensive Analysis and Exploration of Air-Conditioning and HVAC S...
prniciple of ACS.pptx
Air Conditioning Systems in Refrigeration and Air Conditioning
Design of an Air Distribution System for a Multi Storey Office Building
Week 6a HVAC Types jjj.pptx
Air conditioning (1)
Air Conditioning and Security Installations
heat ventilation and Air conditioning.pptx
Week 6a HVAC Types jjj (1).pptx
INTRODUCTION TO HVAC SYSTEMS-Hospitality Engineering
key Components of Air Distribution Systems.pptx
Air Conditioning case study
Air conditioning system
Cem 350 hvac air side systems 10-2016
Ad

Air conditioning for large multistory buildings

  • 1. AIR CONDITIONING FOR LARGE MULTISTORY BUILDINGSPREPARED BYNOOR AZILA BINTI JAMARILECTURERCIVIL ENGINEERING DEPARTMENT
  • 2. Most large multistory buildings use highly centralized air conditioning equipment. The roof and basement are the usual choice for these central station systems. The basement has the advantage of easy utility connections, noise isolation, not being valuable rental area and the fact that structural loads are not a problem.INTRODUCTION
  • 3. The roof is the ideal location for fresh air intakes and heat rejection to the atmosphere.Cooling tower are noisy, produce very hot and humid exhaust air, so the best location for cooling rower is placed on the roof.SECTION OF A TYPICAL MULTISTORY BUILDING WITH A ROOFTOP CENTRAL STATION MECHANICAL SYSTEM
  • 4. In most buildings, the mechanical equipment is shown to be on the roof. This section shows an all-air system served by a single central air handling unit on the roof.To avoid the large vertical ducts, separate air handling units can be placed on each floor and only water circulates vertically. This saves much energy because moving air great distances requires much power. MECHANICAL EQUIPMENT IS STILL ON THE ROOF, EACH FLOOR HAS A SEPARATE AHU
  • 5. The advantage of all-air system is complete control over air quality is possible. The disadvantage is that all-air systems are very bulky and a significant part of the building volume must be devoted to them. There are 5 system in all-air system categories.i. Central Plants ii. Variable Air Volume (V.A.V) iii. Terminal Reheat System iv. Multizone System v. Double Duct System ALL-AIR SYSTEM
  • 6. The central air conditioning system has the limitation of the same air quality being delivered throughout the building.If the structure is zoned or divided and compartmented into several different functions such as offices, workshops, canteen.The temperature of each element can be controlled with zoned thermostats.The fan precedes the chiller and reheater coils and blow air through the air-handling unit.Several ducts radiate from the unit to designated zones within the building. CENTRAL PLANTS SYSTEM
  • 8. This is a single duct system that can easily have many zones. A variable air volume control box is located wherever a duct enters a separate zone.A thermostat in each zone controls the air flow by operating a damper in the V.A.V control box. More cooling is required, more cool air is allowed to enter the zone. ii. VARIABLE AIR VOLUME SYSTEMS
  • 9. VAV system.Floor plan of a VAV system.VAV control box.
  • 10. At the first the terminal reheat system looks just like the V.A.V system but in fact it is very different. This system has terminal reheat boxes in which electric strip heaters or hot water coils reheat air previously cooled.All others zones will reheat the cold air to the desired temperature.iii. TERMINAL REHEAT SYSTEMTerminal reheat system.
  • 11. In this system, every zone receives air at the required temperature through a separate duct.These ducts are supplied by a special multizone air handling unit that custom mixes hot and cold air for each zone. This is accomplished by motorized dampers located in the air handling unit but controlled by thermostats in each zone. Depending on the temperature, the ratio of hot and cold air varies but the total amount of air is constant. iv. MULTIZONE SYSTEM
  • 12. The multizone unit is supplied with hot water, chilled water and a small amount of fresh air.Each multizone unit can handle about 8 zones.Because moderate air temperatures are created by mixing hot and cold air, this system also wasteful of energy.Disadvantage this system are costs relatively high while the thermal control is relatively poor.
  • 13. Like the multizone system, the double duct system mixes hot and cold air to achieve the required air temperature.Instead of mixing the air at a central air handling unit, mixing boxes are dispersed throughout the building.The double duct system creates a high level of thermal comfort and allows for great zoning flexibility, it is very expensive, requires much building space and its wasteful of energy.v. DOUBLE DUCT SYSTEMDouble duct system.
  • 14. To reduce the size of the ducts, a high-velocity version of this systemHigh-velocity air systems (6000 feet/minute) consume more fan power than normal velocity systems(2000 feet/minute).Because of these problem and because V.A.V system are a good alternative, dual duct systems are not used much anymore.
  • 15. These system supply both airand water to each zone of a building.It greatly decreases the size of the equipment because of the immense heart-carrying capacity of water as opposed to air.Air is supplied mainly because of the need for ventilation.There are 2 system in air-water system categories.i. Induction System ii. Fan- coil with supplementary airBut in this topic is cover induction system onlyAIR-WATER SYSTEM
  • 16. A small quantity of high-velocity air is supplied to each zone to supply the required fresh air and to induce room air to circulate.Most induction terminal units are found under windows where they can effectively neutralize the heat gain. As the high-velocity air shoots into the room it induces a large amount of room air to circulates.This combination of room air and fresh air, then passes over heating or cooling coils.INDUCTION SYSTEM
  • 17. Local thermostats regulate the temperature by controlling the flow of either hot or cold water through the coils.It takes a lot of fan power to circulate air at high velocity throughout a building.Because of the high cost of energy and the expense of high-velocity ductwork, the use of induction systems is limited.Induction system.
  • 18. Induction system. Induction unit with cooling or heating coils
  • 19. These systems supply no air.There are 2 system in all-water system categories.i. Fan-coil System ii. Water Loop Heat Pump SystemBut in this topic is cover Fan-coil system only.ALL-WATER SYSTEM
  • 20. The fan-coil unit basically consists of a fan and a coil within water circulates. The units are in the form of cabinets for placement under windows.The fan blows room air across coils containing either hot or cold water.Thermostatically controlled valves regulate the flow of water through the coils. A 4 pipe system, which is has 2 pipes for hot water supply and return and another 2 pipes for cold water supply and return.FAN-COIL SYSTEM
  • 21. Condensation on the cooling coils must be collected in a pan and drained away.When the fan-coil unit is on an outside wall, it is possible to have an outdoor air intake connected to the unit.A three-speed fan switch allows occupants of the zone to have some control over the temperature.Fan-coil units are most appropriate for air conditioning buildings with small zones (eg. Apartments, condominiums, motels, hotels, hospitals and schools).Fan coil units also located above windows, in small closets or in the dropped ceiling above a bathroom.
  • 22. Fan Coil System.Schematic diagram of an under window FCU ( 4 pipe system).
  • 23. FCU placed in a small closet.FCU placed above a dropped ceiling.