Process Control - Chapter 7JU
Process Control - Chapter 7JU
Process Controllers
Fall 2022
1
Process Controllers
Find the transfer function that relates the output y with input u :
Solution:
Steady-state Eq.:
Deviated variables:
Regulatory control: (Manipulate the system input to counteract the effects of disturbances)
o Constant set point:
o Set point deviated variable:
0 Note that:
Small letter : actual variable
Capital letter: deviated variable
where is called Bias or nominal value of controller output signal which is usually adjusted, during calibration,
to be half of the span of the range of the controller signal output.
According to Instrumental Society of America (ISA), Controller output signal has the
following standard ranges:
Pneumatic signal: 3 – 15 psi Zero = 3 psi ; Span=12 psi
Electrical Signal: 4 - 20 mA Zero = 4 mA ; Span=16 mA
Electrical Signal: 0–10 VDC Zero = 0 VDC ; Span=10 VDC
The on-off control is the simplest form of a controller, which switches ON when the error is
positive and switches OFF when the error is zero or negative.
An on-off controller doesn’t have intermediate states but only fully ON or fully OFF states.
δ = tolerance
The controller gain can be adjusted ( “ tuned ” ) to make the manipulated variable changes as
sensitive as desired to the deviations between set-point and controlled variable
The sign of can be chosen to make the controller output u increase or decrease as the error
increases
The bias is the value of the controller output which, in manual mode, causes the measured
process variable to maintain steady state at the design level of operation [e(t) = 0] when the
process disturbances are at their expected values
The bias value is assigned at the controller design level, and remains fixed once the controller is
put in automatic
When error (offset) has zero value, the controller output signal reaches its steady state Bias value
Action of controller: as absolute error increases, the controller output signal must increase to give
large change in manipulated variable, X(t).
Direct acting controller (Kc < 0): choose negative Kc value to increase the controller output signal as the
measured controlled variables increases above the set point.
Reverse acting controller (Kc 0): choose positive Kc value to increase the controller output signal as the
measured controlled variables decreases below the set point.
There conceptually simple easy to tune (a single parameter is needed, Kc ; the bias is determined from steady
state information).
As error changes, p(t) will change immediately (fast corrective action in very simple form).
Introducing very high values of Kc will lead to oscillatory response or even unstable
situation.
Proportional Controller Transfer Function:
Effect of Kc on the controlled variable response under step change in disturbance variable
Example: How is the response of proportional controller to unit step change in e(t)?
The P controller cannot remove offset because the only way to change the controller bias during
non-nominal operations is to cause e(t) = 0.
The rationale behind a PI controller is to set the “ actual ” bias different from , thus letting the error
be zero.
The integral mode will change the bias value to eliminate the steady state error (offset).
The action is not immediate until the integral becomes significant.
The integral mode tends the system to be more oscillatory or even unstable.
Note that until e(t) = 0, the manipulated input keeps on changing because of the presence of the
integral term.
The change in p(t) will stop only when e(t) = 0
Net result: the integral action can eliminate offset.
Reset Time:
The bias value will be reset every by the amount of action taken by the P control. This is called
“reset time”
Integral action Kc / I
Effect of integral time and gain Kc of PI controller on the response of controlled deviated
variable Y(t):
As Kc increases or decreases: less offset, the response will be faster, more overshooting,
less oscillation.
Y. Mubarak Process Control 30
Summary for PI control
Advantages:
Steady state offset can be eliminated the process response can be considerably speeded up with
respect to open-loop
Pitfalls:
The process response becomes oscillatory; bad tuning may even lead to instability
(Same as P controller)
i. If the error if increasing very rapidly, a large deviation from the set-point may arise in a short time.
The rationale behind derivative action is to anticipate the future behavior of the error signal by
considering its rate of change
34
4. Proportional Integral Derivative (PID) controller:
Disadvantages
If there is noise in the process variable, noise will be amplified by the derivative. If the
measurement is noisy, use the measurement after smoothing out (filtering).
The derivative requires information on error in the future: impossible use
approximation of derivative
Three parameters to tune (Kc, and . It is quite complicated for three tuning parameters.
PID controller Transfer Function :
Effect of derivative time of PID controller on the response of controlled deviated variable Y(t):
Example: How is the response of PID controller to unit step change in e(t)
(Same as PI controller)
Parallel form of
PID controller
Transfer function:
Any transfer function which has only zeros is not realizable, realizability requires less zeros than poles
Compare:
In this form,
Basically, the controller gain, Kc, is dimensional quantity. Its physical unit is the ratio of the unit of
controller output signal (mA, psig) to the unit of the controlled variable ( oC, m, Pa, gpm, mol/L, …etc).
Kc can be dimensionless quantity if the set point and measured controlled variable are transmitting to a
signal as that of controller output: