6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13

This document provides examples for calculating current, wire size, circuit breaker size, and conduit size for electrical circuits. The first example is for a 15KW, single phase, 230V furnace load. It shows calculating the current at 65.2A, using #4 gauge wire rated for 85A, sizing the circuit breaker at the next higher 90A rating, and requiring 1" conduit. The second example is for a 9-fixture, 4-tube fluorescent lighting circuit calculating the load current at 15.6A, and using #14 gauge wire.

Uploaded by

man98_greyhoundz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views

6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13

This document provides examples for calculating current, wire size, circuit breaker size, and conduit size for electrical circuits. The first example is for a 15KW, single phase, 230V furnace load. It shows calculating the current at 65.2A, using #4 gauge wire rated for 85A, sizing the circuit breaker at the next higher 90A rating, and requiring 1" conduit. The second example is for a 9-fixture, 4-tube fluorescent lighting circuit calculating the load current at 15.6A, and using #14 gauge wire.

Uploaded by

man98_greyhoundz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

MCP Breakers for Motors 125% or next larger size

Standard breaker sizes are listed Page 70-74, 240-6 NEC


Conduit Sizing
1. After circuits have been derated to get proper wire size use Table 3A if wires are all
same size. Use Page 70-57"9, or Tables 4 and 5 if wires are all different size. Ground
wires should be run with all branch circuits.
Example:
Load Furnace 15 KW, I phase, 230V, find current, KVA, wire size, circuit breaker size,
conduit size.
I = _KW= 15KW= 65.2 Amp
KV .23KV
KW = KVA, P.F. = 1.0 KVA = 15
Wire Size
Wire Size = Load = ampacity = 65.2 Amp = 81.5 Amp
.8
Use NEC 310-16, 75C, THW, wire
#4 wire has 85 amps Use #4 2 #4 and, 1 #4
ground Circuit Breaker Sizing

CB = Load = 65.2 Amp = 81.5 Amp
.8 .8
Next higher CB size is 90 Amp.
NEC 240-6 and 240-3 exception 1, conduit-size, 3 #4 in conduit Table 3A =
1" conduit which allows 3 #4 maximum in a 1" conduit
Example:
Load: Lighting circuit 9-4 tube 4', 50VA/tube 115V fluorescent circuits. find I, circuit
breaker, wire.
(9 fixtures) (4 tubes/fixture) (50V A/tube) = 1800 VA = 1.8 KVA
I = KVA = 1.8 KVA = 15.6 Amp
KV .115 KV

Wire Size = Load = 15.6A = 19.5 amps.
.8 .8
6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13