6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13
This document provides examples for calculating current, wire size, circuit breaker size, and conduit size for electrical circuits. The first example is for a 15KW, single phase, 230V furnace load. It shows calculating the current at 65.2A, using #4 gauge wire rated for 85A, sizing the circuit breaker at the next higher 90A rating, and requiring 1" conduit. The second example is for a 9-fixture, 4-tube fluorescent lighting circuit calculating the load current at 15.6A, and using #14 gauge wire.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
36 views
6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13
This document provides examples for calculating current, wire size, circuit breaker size, and conduit size for electrical circuits. The first example is for a 15KW, single phase, 230V furnace load. It shows calculating the current at 65.2A, using #4 gauge wire rated for 85A, sizing the circuit breaker at the next higher 90A rating, and requiring 1" conduit. The second example is for a 9-fixture, 4-tube fluorescent lighting circuit calculating the load current at 15.6A, and using #14 gauge wire.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
MCP Breakers for Motors 125% or next larger size
Standard breaker sizes are listed Page 70-74, 240-6 NEC
Conduit Sizing 1. After circuits have been derated to get proper wire size use Table 3A if wires are all same size. Use Page 70-57"9, or Tables 4 and 5 if wires are all different size. Ground wires should be run with all branch circuits. Example: Load Furnace 15 KW, I phase, 230V, find current, KVA, wire size, circuit breaker size, conduit size. I = _KW= 15KW= 65.2 Amp KV .23KV KW = KVA, P.F. = 1.0 KVA = 15 Wire Size Wire Size = Load = ampacity = 65.2 Amp = 81.5 Amp .8 Use NEC 310-16, 75C, THW, wire #4 wire has 85 amps Use #4 2 #4 and, 1 #4 ground Circuit Breaker Sizing
CB = Load = 65.2 Amp = 81.5 Amp .8 .8 Next higher CB size is 90 Amp. NEC 240-6 and 240-3 exception 1, conduit-size, 3 #4 in conduit Table 3A = 1" conduit which allows 3 #4 maximum in a 1" conduit Example: Load: Lighting circuit 9-4 tube 4', 50VA/tube 115V fluorescent circuits. find I, circuit breaker, wire. (9 fixtures) (4 tubes/fixture) (50V A/tube) = 1800 VA = 1.8 KVA I = KVA = 1.8 KVA = 15.6 Amp KV .115 KV
Wire Size = Load = 15.6A = 19.5 amps. .8 .8 6/14/02 Chapter 3: NEC CODE Rules and Design Practice 2/13