Módulo Multifunción KBDA IODA
Módulo Multifunción KBDA IODA
RoHS
See Safety Warning, on page 4.
Table Page
1 Terminal Block TB1 Wire and Tightening Torque Specifications..................................... 14
2 Functions, Features, and Terminal Assignment.............................................................. 14
3 Multi-Function Input Terminal, Function No., and Code Assignment .............................. 15
4 Preset Frequency Selection............................................................................................ 15
5 Unidirectional Preset Frequency Selection with 2-Wire Start/Stop Programming............ 17
6 Unidirectional Preset Frequency Selection with 3-Wire Start/Stop Programming............ 18
7 Bidirectional Preset Frequency Selection Programming ................................................. 19
8 Unidirectional Up/Down Frequency Control Programming.............................................. 21
9 Bidirectional Up/Down Frequency Control Programming ................................................ 22
10 Accel/Decel "2" Programming......................................................................................... 23
11 Forward/Stop-Reverse/Stop Programming ..................................................................... 24
12 External Fault Programming ........................................................................................... 25
13 Reset Programming........................................................................................................ 26
14 Analog Input "1" Electrical Ratings ................................................................................. 28
15 Analog Input "1" Signal Voltage Following Programming................................................ 29
16 Analog Input "2" Electrical Ratings ................................................................................. 30
17 Analog Input "2" Signal Current Following Programming ................................................ 30
18 Analog Outputs "1" and "2" Electrical Ratings................................................................. 31
19 Analog Outputs "1" and "2" Programming....................................................................... 32
20 Remote Unidirectional Main Speed Potentiometer Programming ................................... 34
21 Remote Bidirectional Main Speed Potentiometer Programming ..................................... 34
22 Remote Main speed Potentiometer Operation with Forward/Reverse Programming ...... 35
23 Multi-Function Output Relay Contacts Programming ...................................................... 37
24 Multi-Function Open Collector Output Programming ...................................................... 38
25 Multi-Function Open Collector Outputs Electrical Ratings............................................... 38
26 Digital Readout Codes.................................................................................................... 40
27 Status Indicator LED....................................................................................................... 43
2
TABLE OF CONTENTS (CONTINUED)
Figure Page
1 IODA Layout..................................................................................................................... 6
2 KBDA Layout.................................................................................................................... 7
3 Exploded View of KBDA and IODA Assembly .................................................................. 8
4 Preparing the Drive for Installation of the IODA ................................................................ 9
5 Installing the IODA PC Board onto the Mounting Base..................................................... 9
6 Installing the IODA into the Drive.................................................................................... 10
7 Installing the Ribbon Cable into the IODA CON1............................................................ 10
8 IODA Installed into Model KBDA-24D............................................................................. 11
9 IODA Installed into Models KBDA-27D, 29, 45, 48 ......................................................... 12
10 Terminal Block TB1 Layout............................................................................................. 13
11 Unidirectional Preset Frequency Selection with 2-Wire Start/Stop Connections ............. 17
12 Unidirectional Preset Frequency Selection with 3-Wire Start/Stop Connections ............. 17
13 Bidirectional Preset Frequency Selection Connections................................................... 18
14 Unidirectional Up/Down Frequency Control with 2-Wire Start/Stop Connections ............ 20
15 Bidirectional Up/Down Frequency Control Connections ................................................. 22
16 Accel/Decel "2" Connections .......................................................................................... 23
17 Forward/Stop-Reverse/Stop Connections....................................................................... 24
18 External Fault Connections............................................................................................. 25
19 Reset Connections ......................................................................................................... 26
20 Analog Input "1" and "2" Signal Gain and Offset with Positive Slope .............................. 27
21 Analog Input "1" and "2" Signal Gain and Offset with Negative Slope............................. 28
22 Analog Input "1" Signal Voltage Following Connections ................................................. 29
23 Analog Input "2" Signal Current Following Connections.................................................. 30
24 Analog Outputs "1" and "2" Gain .................................................................................... 31
25 Analog Outputs "1" and "2" Connection .......................................................................... 32
26 Remote Unidirectional Main Speed Potentiometer Connections..................................... 33
27 Remote Bidirectional Main Speed Potentiometer Connections....................................... 34
28 Remote Main Speed Potentiometer with Forward/Reverse Connections........................ 35
29 Multi-Function Output Relay Contacts Connections........................................................ 36
30 Multi-Function Open Collector Output Connections ........................................................ 38
31 Typical Application for Open Collector Output ................................................................ 39
3
ITEMS INCLUDED IN THIS PACKAGE
● IODA Input/Output Multi-Function Board.
● Small Mounting Base (for Model KBDA-24D only).
● Large Mounting Base (for Models KBDA-27D, 29, 45, 48).
● One 6-32 X ½" and one 6-32 X 1" Socket Head Cap Screw (for Small Mounting Base).
● Two 6-32 X 1½ " Socket Head Cap Screws (for Large Mounting Base).
● 7/64" Allen key.
● IODA Input/Output Multi-Function Board Installation and Operation Manual.
● 4" Heat Shrink Tubing (used to enclose IODA wires when using the optional AC line filter).
● CE Approved Product Information Card.
● Warranty Registration Card.
1 SAFETY WARNING
Definition of Safety Warning Symbols
The IODA contains electronic Start/Stop circuits, which can be used to start and stop
the drive. However, these circuits are never to be used as safety disconnects since
they are not fail-safe. Use only the AC line for this purpose.
Be sure to read this manual in its entirety and follow all instructions carefully before
proceeding with the installation and operation. Fire and/or electrocution can result
due to improper use of this product.
4
2 INTRODUCTION
Thank you for purchasing the IODA Input/Output Multi-Function Board.
KB Electronics, Inc. is committed to providing total customer satisfaction by producing
quality products that are easy to install and operate.
The IODA Input/Output Multi-Function Board provides a variety of functions which
include preset frequency, up/down frequency control, signal isolation, isolated output
voltage for controlling auxiliary devices, output relay contacts, and open collector
outputs. The IODA mounts on the drive's PC board with 2 snap-ins (located on the
bottom of the mounting base) and 2 screws (provided). All of the IODA inputs and
outputs are isolated from the AC line.
The IODA has a green power on LED (PWR) and a red status LED (STATUS), which
are used to provide operational information of the IODA. See Table 27, on page 43,
for a description of the status LED. See Figure 1, on page 6, for the IODA layout. See
Figure 10, on page 13, for Terminal Block TB1 Layout. See Table 1, on page 14, for
Terminal Block TB1 Wire and Tightening Torque Specifications. See Table 2, on page
14, for the Functions, Features, and Terminal Assignment. See Sections 4.1 – 4.6, on
pages 15 – 26, describing the use of the IODA Multi-Function Input Terminals for
remote operations. See Sections 4.7 – 4.11, on pages 26 – 39, for other functions and
features of the IODA.
STANDARD FEATURES
▪ Signal Input Isolation: Provides isolation between signal sources and the drive.
▪ Potentiometer Operation: A 5 kΩ potentiometer can be used to in lieu of the
Keypad or the Built-In Potentiometer. The Main Speed Potentiometer can be
connected for forward, reverse, or bidirectional motor speed control.
▪ Multi-Function Input Terminals: Used for a variety of functions, which include
Preset Frequency; Up/Down Frequency Command; Forward/Stop and Reverse/Stop
Command; External Fault; Reset; 2-Wire and 3-Wire Start/Stop.
▪ Multi-Function Output Relays: Two Multi-Function Output Relays are provided,
which can be programmed for Run, Fault, Target Frequency, Frequency Threshold
Level, I2t or I•t Fault, Load Loss, External Fault, and Motor Overload.
▪ Multi-Function Open Collector Outputs: Two Multi-Function Output Relays are
provided, which can be programmed for Run, Fault, Target Frequency, Frequency
Threshold Level, I2t or I•t Fault, Load Loss, External Fault, and Motor Overload.
▪ Isolated Signal Output: Two isolated analog signal outputs are provided, which can
be used to monitor Motor Frequency, set Frequency, Motor Voltage Bus Voltage,
and Motor Current. Analog Output 1 provides a 0 – 5 Volt DC signal output. Analog
Output 2 can be programmed for 0 – 5 Volt DC, 4 – 20 mA DC, or for 0 – 20 mA DC.
▪ Selectable Jumpers: For voltage or current signal selection.
▪ Multi-Turn Trimpots: For fine adjustment and attenuation of signal inputs.
▪ LEDs: The green power on LED (PWR) indicates that power is applied to the IODA
from the drive. The red status LED (STATUS) provides indication of the IODA
operation.
▪ Barrier Terminal: All connections to the IODA are made via the barrier terminal
block. All terminal block connections of the IODA are isolated from the AC line.
▪ Easy Installation: Uses a snap-in base and two screws (provided) for mounting and
a ribbon cable for wiring to the drive.
5
FIGURE 1
IODA LAYOUT
*The IODA kit contains 2 mounting bases. Use the small base for Model KBDA-24D and the
large base for Models KBDA-27D, 29, 45, 48.
6
FIGURE 2
KBDA LAYOUT
*Model KBDA-24D shown. Layout of Models KBDA-27D, 29, 45, 48 varies slightly.
3 INSTALLATION INSTRUCTIONS
The IODA is designed to be installed onto the KBDA PC board with a mounting base
and screws provided. The ribbon cable in the KBDA contains a connector which is to
be plugged into the mating connector on the IODA. See Figures 8 and 9, on pages 11
and 12, showing the IODA installed onto the KBDA PC board.
See Figure 3, on page 8, for the exploded view of the KBDA and IODA assembly.
7
FIGURE 3
EXPLODED VIEW OF KBDA AND IODA ASSEMBLY (KBDA-24D SHOWN)
8
3.1 PREPARING THE DRIVE FOR INSTALLATION OF THE IODA
Use the Allen Key (supplied) to remove the two socket head cap screws located
at the top corners of the KBDA PC board. See Figure 4.
FIGURE 4
PREPARING THE DRIVE FOR INSTALLATION OF THE IODA*
*Model KBDA-24D shown. Layout of Models KBDA-27D, 29, 45, 48 varies slightly.
Note: To prevent damage to components press only on the PC board, not on any
components.
FIGURE 5
INSTALLING THE IODA PC BOARD ONTO THE MOUNTING BASE
9
3.4 INSTALLING THE IODA INTO THE DRIVE
Place the IODA in the area where it is to be installed. Be sure the ribbon cable is
routed underneath the mounting base. Align the two snap-ins of the mounting
base with the two holes on the KBDA PC board and press firmly until the
mounting base is secured onto the KBDA PC board. See Figure 6.
Use the 6-32 X ½" and 6-32 X 1" screws for the small Mounting Base (see Figure
8, on page 11). Use the two 6-32 X 1½" screws for the large Mounting Base (see
Figure 9, on page 12). Use the Allen Key (supplied) to tighten the screws. Do
not over tighten.
Note: To facilitate the connection of the ribbon cable onto the IODA, it is
recommended that the fold of the ribbon cable be positioned in the area where
the IODA and mounting base will be located, as shown in Figure 6.
FIGURE 6
INSTALLING THE IODA INTO THE DRIVE
*Model KBDA-24D shown. Layout of Models KBDA-27D, 29, 45, 48 varies slightly.
10
3.6 IODA INSTALLED INTO THE DRIVE
After completing the installation, the IODA mounted in Model KBDA -24D will
resemble Figure 8 and the IODA mounted in Models KBDA-27D, 29, 45, 48 will
resemble Figure 9, on page 12.
FIGURE 8
IODA INSTALLED INTO MODEL KBDA-24D
11
FIGURE 9
IODA INSTALLED INTO MODELS KBDA-27D*, 29, 45, 48
12
4 ELECTRICAL CONNECTIONS
See Sections 4.1 – 4.11, on pages 15 – 38, for the electrical connections to the IODA.
See Figure 10, below, for Terminal Block TB1 Layout. Common Terminals "8", "12",
"14", "16", "18", "20", and "22" (shown shaded) are all internally connected and can be
used with the Multi-Function Input Terminals "1" – "7", Signal Inputs 1 and 2, and
Signal Outputs 1 and 2.
See Table 1, on page 14, for Terminal Block TB1 Wire and Tightening Torque
Specifications. See Table 2, on page 14, for Terminal Block TB1 Functions, Features
and Terminal Assignments.
FIGURE 10
TERMINAL BLOCK TB1 LAYOUT
Common Terminals "8", "12", "14", "16", "18", "20", and "22" are all internally connected and
are shown shaded.
13
TABLE 1
TERMINAL BLOCK TB1 WIRE AND TIGHTENING TORQUE SPECIFICATIONS
Maximum Wire Size (Cu) Recommended Tightening Torque
AWG mm2 lbs-in kg-cm
16 1.3 6 7
TABLE 2
FUNCTIONS, FEATURES, AND TERMINAL ASSIGNMENT
Terminal Assignment
Multi- Relay
Multi-Function Input Terminals1 Power Function Analog Analog Outputs
(Digital Inputs) Supply2 Outputs2 Outputs2 Inputs2 3
1–7 8 11 15 19 23
0000: Preset Frequency Operation1 Common Open Analog Analog RY1
Collector 1 Output 1 Input 1 N.O.
0001: Preset Frequency Operation1
Multi-Function Input Terminal Codes (Function Group 7) 9 12 16 20 24
+5 Volts Common Common Common RY1
0002: Preset Frequency Operation1
Common
16
FIGURE 11
UNIDIRECTIONAL PRESET FREQUENCY SELECTION
WITH 2-WIRE START/STOP CONNECTIONS
Note: Use Function Nos. 7.07 – 7.13 to program the desired Preset Frequencies.
TABLE 5
UNIDIRECTIONAL PRESET FREQUENCY SELECTION
WITH 2-WIRE START/STOP PROGRAMMING
Function No. Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
3.00: Stored Set Frequency 00.00 Hz
7.00: Multi-Function Input Terminal 1 0000: Preset Frequency Operation*
7.01: Multi-Function Input Terminal 2 0001: Preset Frequency Operation*
7.02: Multi-Function Input Terminal 3 0002: Preset Frequency Operation*
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
*Factory setting.
FIGURE 12
UNIDIRECTIONAL PRESET FREQUENCY SELECTION
WITH 3-WIRE START/STOP CONNECTIONS
Note: Use Function Nos. 7.07 – 7.13 to program the desired Preset Frequencies.
17
TABLE 6
UNIDIRECTIONAL PRESET FREQUENCY SELECTION
WITH 3-WIRE START/STOP PROGRAMMING
Function No. Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
3.00: Stored Set Frequency 00.00 Hz
7.00: Multi-Function Input Terminal 1 0000: Preset Frequency Operation*
7.01: Multi-Function Input Terminal 2 0001: Preset Frequency Operation*
7.02: Multi-Function Input Terminal 3 0002: Preset Frequency Operation*
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
7.05: Multi-Function Input Terminal 6 0011: N.C. Stop
*Factory setting.
FIGURE 13
BIDIRECTIONAL PRESET FREQUENCY SELECTION CONNECTIONS
Note: Use Function Nos. 7.07 – 7.13 to program the desired Preset Frequencies.
18
TABLE 7
BIDIRECTIONAL PRESET FREQUENCY SELECTION PROGRAMMING
Function No. Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
3.00: Stored Set Frequency 00.00 Hz
7.00: Multi-Function Input Terminal 1 0000: Preset Frequency Operation*
7.01: Multi-Function Input Terminal 2 0001: Preset Frequency Operation*
7.02: Multi-Function Input Terminal 3 0002: Preset Frequency Operation*
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
7.05: Multi-Function Input Terminal 6 0006: Forward/Stop Command
7.06: Multi-Function Input Terminal 7 0007: Reverse/Stop Command
*Factory setting.
Notes: 1. The drive is factory set for Unidirectional (Forward) Operation. For
Bidirectional Operation, use two Multi-Function Inputs for Forward/Stop and
Reverse/Stop, as described in Section 4.2.2, on page 21. 2. If a Multi-Function
Input Terminal is programmed for Reverse/Stop Command ("0007"), when
activated, the drive will remain "locked" in Reverse Operation until two Multi-
Function Input Terminals are programmed for Forward/Stop Command ("0006")
and Reverse/Stop Command ("0007").
19
Note: Use a maintained switch or contact for Start/Stop. If a Start/Stop
Switch or Contact is not used, a jumper must be installed between
Terminals "5" and "8".
FIGURE 14
UNIDIRECTIONAL UP/DOWN FREQUENCY CONTROL
WITH 2-WIRE START/STOP CONNECTIONS
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is not
required.
20
TABLE 8
UNIDIRECTIONAL UP/DOWN FREQUENCY CONTROL PROGRAMMING
Function No. Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0005: Up/Down Using MFITs
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
7.05: Multi-Function Input Terminal 6 0003: Up Frequency Command*
7.06: Multi-Function Input Terminal 7 0004: Down Frequency Command.
7.14: Up/Down Frequency Control Mode 0000: Free-Running 0001: Incremental
7.15: Increment of Up/Down Frequency** 0.01 – 30.00 Hz: Set to Desired Frequency
*Factory setting.
**Use with Function No. 7.14 code "0001" only.
TABLE 9
BIDIRECTIONAL UP/DOWN FREQUENCY CONTROL PROGRAMMING
Function No. Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0005: Up/Down Using MFITs
7.02: Multi-Function Input Terminal 3 0006: Forward/Stop Command
7.03: Multi-Function Input Terminal 4 0007: Reverse/Stop Command
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
7.05: Multi-Function Input Terminal 6 0003: Up Frequency Command*
7.06: Multi-Function Input Terminal 7 0004: Down Frequency Command*
7.14: Up/Down Frequency Control Mode 0000: Free-Running 0001: Incremental
7.15: Increment of Up/Down Frequency** 0.01 – 30.00 Hz: Set to Desired Frequency
*Factory setting.
**Use with Function No. 7.14 code "0001" only.
22
FIGURE 16
ACCEL/DECEL "2" CONENCTIONS
TABLE 10
ACCEL/DECEL "2" PROGRAMMING
Function No. Code/Range
7.05: Multi-Function Input Terminal 6 0005: Accel/Decel 2
7.16: Accel/Decel 2 Time 0.3 – 180.0: Set to Desired Time*
*Factory set to 1.5 seconds.
4.4 FORWARD/STOP-REVERSE/STOP
Remote Forward/Stop and Reverse/Stop operation can be performed by
connecting switches or contacts to the Multi-Function Input Terminals. See
Figure 17, on page 24, for connections. See Table 11, on page 24, for drive
programming.
Operation: When the Forward/Stop Switch or Contact is closed, the drive will run
in the forward direction. When the Forward/Stop Switch or Contact is opened,
the drive will stop. When the Reverse/Stop Switch or Contact is closed, the drive
will run in the reverse direction. When the Reverse/Stop Switch or Contact is
opened, the drive will stop.
23
FIGURE 17
FORWARD/STOP-REVERSE/STOP CONNECTIONS
TABLE 11
FORWARD/STOP-REVERSE/STOP PROGRAMMING
Function No. Code
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
7.02: Multi-Function Input Terminal 3 0006: Forward/Stop Command
7.03: Multi-Function Input Terminal 4 0007: Reverse/Stop Command
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
*Factory setting.
24
APPLICATION NOTES FOR AUTO/MANUAL START MODE (FUNCTION NO. 1.05)
After the Extenal Fault has been Cleared:
1. If the drive is set for Manual Start Mode ("0000" (factory setting)), Manual Start
with Ride-Through ("0001"), or Auto Start After Undervoltage Fault Clears
("0002"), it will have to be manually restarted after the external fault has been
cleared. Use the Reset Key on the Keypad or the external Reset Switch or
Contact to restart the drive.
2. If the drive is set for Auto Start All Faults (Except Short circuit Fault) ("0003"), it will
automatically restart after the external fault has been cleared, for the number of
restart attempts set in Function No. 1.07 (factory set to 3). After which, the drive
will have to be restarted using the Reset Key on the Keypad or the external Reset
Switch or Contact.
3. If the drive is set for Auto Start All Faults (Except 12t, I•t, and Short Circuit Faults)
("0004"), it will automatically restart after the external fault has been cleared.
FIGURE 18
EXTERNAL FAULT CONNECTIONS
*Optional.
TABLE 12
EXTERNAL FAULT PROGRAMMING
Function No. Code
7.03: Multi-Function Input Terminal 4 0009: Reset*
0008: External Fault (N.O. Contact)
7.04: Multi-Function Input Terminal 5
0012: External Fault (N.C. Contact)
*Factory setting.
25
4.6 RESET
It is advisable to connect a momentary normally open switch or contact to Multi-
Function Input Terminal "4". This allows the drive to be restarted after a fault has
been cleared. See Figure 19 for connections. See Table 13 for drive
programming.
Connect the Reset Switch or Contact to Multi-Function Input Terminal "4", which
is factory set to Reset ("0009"). Terminal "4" has been arbitrarily chosen for
Reset. Connect the common of the switch or contact to any available common
terminal ("8", "12", "14", "16", "18", "20", "22").
Operation: When a fault has been cleared, momentarily activate the Reset
switch or Contact to reset the drive.
FIGURE 19
RESET CONNECTIONS
TABLE 13
RESET PROGRAMMING
Function No. Code
7.03: Multi-Function Input Terminal 4 0009: Reset*
*Factory setting.
Analog Input 1 is used for a DC voltage signal which has a positive or negative
slope and is unidirectional or bidirectional. Analog Input 2 is used for a DC
voltage, current, or PWM signal with a positive or negative slope and is
unidirectional.
26
Local/Remote Operation: When using the IODA with signal following or
remote start/stop, it is desirable to program the drive for Local/Remote
Operation. In this mode, the drive frequency setting can be toggled between a
process signal and the keypad using the JOG-LCL/REM Key. The following
functions can be switched between "remote" and "local" (Keypad) operation:
Start/Stop, Forward/Reverse, Analog Signal Inputs 1 and 2, and Up/Down
Frequency Control.
Note: To stop the drive using the Keypad, when in Remote Operation, first
press the JOG-LCL/REM Key and then the Stop Key.
Operation with a Positive Slope Signal: When the signal input is increased,
the drive output frequency will increase. When the signal input is decreased, the
drive output frequency will decrease. See Figure 20.
Operation with a Negative Slope Signal: When the signal input is increased,
the drive output frequency will decrease. When the signal input is decreased, the
drive output frequency will increase. See Figure 21, on page 28.
FIGURE 20
ANALOG INPUT "1" AND "2" SIGNAL GAIN AND OFFSET WITH POSITIVE SLOPE
(LOW-TO-HIGH SIGNAL) (FUNCTION NO. 9.01 OR 9.06 SET TO "0000")
27
FIGURE 21
ANALOG INPUT "1" AND "2" SIGNAL GAIN AND OFFSET WITH NEGATIVE SLOPE
(HIGH-TO-LOW SIGNAL) (FUNCTION NO. 9.01 OR 9.06 SET TO "0001")
Connect the signal input to Terminal "19" and the common to Terminal "20".
Connect the Start (Jumper) to Terminal "5", which is factory set for N.O. Start
("0010") and to any available common terminal ("8", "12", "14", "16", "18" "20",
"22"). See Figure 22, on page 29, for connections. See Table 15, on page 29,
for drive programming.
MAX1 Trimpot: If the Analog Input 1 signal is higher than 5 Volts, use Trimpot
MAX1 to attenuate it. Apply the maximum signal input and set the drive for full
speed output and observe the display. Rotate Trimpot MAX1 counter clockwise
until the drive output frequency begins to drop. Then, rotate Trimpot MAX1
clockwise until the display returns to the maximum output frequency.
Set the signal Slope and Type and adjust the Gain, Offset, and Response Time
as desired. See Figure 20, on page 27, and Figure 21, above.
TABLE 14
ANALOG INPUT "1" ELECTRICAL RATINGS
Parameter Specification Factory setting
Voltage Range (Volts DC) 0 – ±2.5 thru 0 – ±25 0–5
MAX1 Scaling Trimpot Range (Volts DC) 0 – 24 5
28
FIGURE 22
ANALOG INPUT "1" SIGNAL VOLTAGE FOLLOWING CONNECTIONS
TABLE 15
ANALOG INPUT "1" SIGNAL VOLTAGE FOLLOWING PROGRAMMING
Function No. Code/Range
2.00: Frequency Control 0002: Analog Signal 1
9.00: Analog Input 1 Gain 0 – 500: Set to the Desired Gain
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
0000: Positive
9.01: Analog Input 1 Slope
0001: Negative
9.02: Analog Input 1 Offset 0 – 100: Set to the Desired Offset
0000: Unidirectional
9.03: Analog Input 1 Type
0001: Bidirectional
9.04: Analog Input 1 Response Time (mSec) 2 – 100: Set to the Desired Time
*Factory setting.
FIGURE 23
ANALOG INPUT "2" SIGNAL CURRENT FOLLOWING CONNECTIONS
TABLE 17
ANALOG INPUT "2" SIGNAL CURRENT FOLLOWING PROGRAMMING
Function No. Code/Range
2.00: Frequency Control 0003: Analog Signal 2
9.05: Analog Input 2 Gain 0 – 500: Set to the Desired Gain
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
0000: Positive
9.06: Analog Input 2 Slope
0001: Negative
9.07: Analog Input 2 Offset 0 – 100: Set to the Desired Offset
9.08: Analog Input 2 Type 0000: Analog Voltage or Current
9.09: Analog Input 2 Response Time (mSec) 2 – 100: Set to the Desired Time
*Factory setting.
30
4.8 ANALOG SIGNAL OUTPUT
Two analog signal outputs are provided, which will linearly follow the parameter
programmed in Analog output 1 Mode (Function No. 8.06) and Analog Output 2
Mode (Function No. 8.08). They can be used to monitor Motor Frequency, Set
Frequency, Motor Voltage, Bus Voltage, and Motor Current. See Figure 24 for
Analog Output 1 and 2 Gain settings (factory set to 100%). See Table 18 for
Analog Outputs 1 and 2 electrical ratings. See Figure 25, on page 32, for
connections. See Table 19, on page 32, for drive programming.
FIGURE 24
ANALOG OUTPUTS "1" AND "2" GAIN
TABLE 18
ANALOG OUTPUTS "1" AND "2" ELECTRICAL RATINGS
Parameter Specification Factory setting
Analog Outputs 1 and 2 Voltage Range (Volts DC) 0–5 0–5
Analog Output 2 Current Range (mA DC) 0 – 20, 4 – 20 –
Analog Output 2 Impedance for Current Mode (Ω) 150 –
31
FIGURE 25
ANALOG OUTPUTS "1" AND "2" CONNECTIONS
TABLE 19
ANALOG OUTPUTS "1" AND "2" PROGRAMMING
Function No. Code/Range
0000: Motor Frequency
0001: Set Frequency
8.06: Analog Output 1 Mode 0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
8.07: Analog Output 1 Gain 0 – 200: Set to the Desired Gain
0000: Motor Frequency
0001: Set Frequency
8.08: Analog Output 2 Mode 0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
0000: 0 – 5 Volts DC
8.09: Analog Output 2 Type 0001: 0 – 20 mA DC
0002: 4 – 20 mA DC
8.10: Analog Output 2 Gain 0 – 200: Set to the Desired Gain
Voltage Signal Output: Set both Jumpers J2 and J3 to the "VOLT" position
(factory setting).
Current Signal Output: Set both Jumpers J2 and J3 to the "CUR" position.
32
4.9 REMOTE MAIN SPEED POTENTIOMETER
A remote Main Speed Potentiometer (5 kΩ) can be used in lieu of the Keypad or
the Built-In Potentiometer on the drive to control motor speed. The potentiometer
can be connected for Unidirectional Operation, Bidirectional Operation with
center off, or Bidirectional Operation with Forward/Reverse Switches or Contacts.
UNIDIRECTIONAL OPERATION WITH 2-WIRE START/STOP USING
ANALOG INPUT 1:
Connect the potentiometer to Terminals "9" (+5 Volts), "19" (Analog Input 1), and
"16" (Common) (Terminals "8", "12", "14", "18" or "22" can also be used for
common). Connect the Start/Stop Switch or Contact to Terminal "5", which is
factory set for N.O. Start ("0010"), and to any available common terminal
("8", "12", "14", "16", "18" "20", "22"). See Figure 26 for connections. See Table
20, on page 34, for drive programming.
Operation: When the Start/Stop Switch or Contact is closed, the drive will be in
the Run Mode. Rotate the Main Speed Potentiometer clockwise to increase
motor speed. Rotate the Main speed Potentiometer counterclockwise to
decrease motor speed. When the Start /Stop Switch or Contact is opened, the
drive will be in the Stop Mode.
UNIDIRECTIONAL OPERATION WITH 2-WIRE START/STOP USING
ANALOG INPUT 2:
Connect the potentiometer to Terminals "9" (+5 Volts), "21" (Analog Input 2), and
"14" (Common) (Terminals "8", "12", "16", "18" or "22" can also be used for
Common). Connect the Start/Stop Switch or Contact to Terminal "5", which is
factory set for N.O. Start ("0010"), and to any available common terminal
("8", "12", "14", "16", "18" "20", "22").
Operation: When the Start/Stop Switch or Contact is closed, the drive will be in
the Run Mode. Rotate the Main Speed Potentiometer clockwise to increase
motor speed. Rotate the Main speed Potentiometer counterclockwise to
decrease motor speed. When the Start /Stop Switch or Contact is opened, the
drive will be in the Stop Mode.
FIGURE 26
REMOTE UNIDIRECTIONAL MAIN SPEED POTENTIOMETER CONNECTIONS
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is not
required.
33
TABLE 20
REMOTE UNIDIRECTIONAL MAIN SPEED POTENTIOMETER PROGRAMMING
Function No. Code
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0002: Analog Signal 1
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
*Factory setting.
BIDIRECTIONAL OPERATION WITH START/STOP
(Use Analog Input "1" Only)
Connect the Main Speed Potentiometer to Terminals "9" (+5 Volts), "19" (Analog
Input 1), and "10" (-5 Volts). Connect the Start/Stop Switch or Contact to
Terminal "5", which is factory set for N.O. Start ("0010"), and to any available
common terminal ("8", "12", "14", "16", "18" "20", "22"). See Figure 27 for
connections. See Table 21 for drive programming.
Operation: Close the Start/Stop Switch or contact to start the drive. At 50%
rotation, the Main Speed Potentiometer is set for zero speed. Rotating the Main
Speed Potentiometer clockwise will increase motor frequency in the forward
direction. Rotating the Main Speed Potentiometer counterclockwise will increase
motor frequency in the reverse direction. Open the Start/Stop Switch or Contact
to stop the drive.
FIGURE 27
REMOTE BIDIRECTIONAL MAIN SPEED POTENTIOMETER CONNECTIONS
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch or Contact is not
required.
TABLE 21
REMOTE BIDIRECTIONAL MAIN SPEED POTENTIOMETER PROGRAMMING
Function No. Code
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0002: Analog Signal 1
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
9.03: Analog Input 1 Type 0001: Bidirectional
*Factory setting.
34
BIDIRECTIONAL OPERATION WITH FORWARD/REVERSE:
Connect the Main Speed Potentiometer to Terminals "9" (+5 Volts), "19" (Analog
Input 1), and "8" (Common) (Terminals "12", "14", "16", "18" or "22" can also be
used for Common). Connect the Forward Switch or Contact to a Multi-Function
Input Terminal "1" – "7". Connect the Reverse Switch or Contact to a Multi-
Function Input Terminal "1" – "7". Connect the Start (Jumper) to Terminal "5",
which is factory set for N.O. Start ("0010"), and to any available common terminal
("8", "12", "14", "16", "18" "20", "22"). See Figure 28 for connections. See Table
22 for drive programming.
FIGURE 28
REMOTE MAIN SPEED POTENTIOMETER
WITH FORWARD/REVERSE CONNECTIONS
TABLE 22
REMOTE MAIN SPEED POTENTIOMETER
WITH FORWARD/REVERSE PROGRAMMING
Function No. Code
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control 0002: Analog Signal 1
7.00: Multi-Function Input Terminal 1 0006: Forward/Stop Command
7.01: Multi-Function Input Terminal 2 0007: Reverse/Stop Command
7.04: Multi-Function Input Terminal 5 0010: N.O. Start*
*Factory setting.
35
4.10 MULTI-FUNCTION OUTPUT RELAYS
Two Multi-Function Output Relays are provided, which can be programmed for
Run, Fault, Target Frequency, Frequency Threshold Level (> 8.04 – 8.05),
Frequency Threshold Level (< 8.04 + 8.05), I2t or I•t Fault, Load Loss, External
Fault, and Motor Overload. The maximum allowable contact load current is 1
Amp. See Figure 29 for connections. See Table 23, on page 37, for drive
programming.
Note: If the drive "stops", due to an External Fault Trip ("EF–t"), which indicates
that a Multi-Function Input Terminal (Function Nos. 7.00 – 7.06 set to "0008") has
closed, the Multi-Function Output Relay Contacts will change state (when
Function No. 8.00 or 8.01 is set to "0007").
FIGURE 29
MULTI-FUNCTION OUTPUT RELAY CONTACTS CONNECTIONS
36
TABLE 23
MULTI-FUNCTION OUTPUT RELAY CONTACTS PROGRAMMING
Function No. Code
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
8.00: Multi-Function Output Relay 1 0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I2t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
8.01: Multi-Function Output Relay 2 0004: Frequency Threshold Level (< 8.04 + 8.05)
0005: I2t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
37
FIGURE 30
MULTI-FUNCTION OPEN COLLECTOR OUTPUT CONNECTIONS
TABLE 24
MULTI-FUNCTION OPEN COLLECTOR OUTPUT PROGRAMMING
Function No. Code
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
8.02: Multi-Function Open Collector 0004: Frequency Threshold Level (< 8.04 + 8.05)
Output 1 0005: I2t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
0000: Run
0001: Fault
0002: Target Frequency
0003: Frequency Threshold Level (> 8.04 – 8.05)
8.03: Multi-Function Open Collector 0004: Frequency Threshold Level (< 8.04 + 8.05)
Output 2 0005: I2t or I•t Fault
0006: Load Loss
0007: External Fault
0008: Motor Overload
TABLE 25
MULTI-FUNCTION OPEN COLLECTOR OUTPUTS ELECTRICAL RATINGS
Parameter Specification Factory setting
Maximum Voltage (Volts DC) 24 –
Maximum Load Current (mA DC) 60 0 – 20
Minimum External Resistance (Ω) 400 –
38
FIGURE 31
TYPICAL APPLICATION FOR OPEN COLLECTOR OUTPUT
5 OPERATION
After the drive has been properly setup and all connections completed, the start-up
procedure can begin. If the AC power has been properly brought to the drive, the
PWR LED will illuminate green. The red STATUS LED will indicate the drive's status,
as described in Section 7, on page 43. See Table 26, on page 40, for the Digital
Readout Codes. See the KBDA Installation and Operation Manual for other Digital
Readout Codes of the drive.
Local/Remote Operation: When using the IODA with signal following, it may be
appropriate to program the drive for Local/Remote Operation. In this mode, the drive
frequency setting can be toggled between a process signal and the keypad using the
JOG-LCL/REM Key. Set Jog-Local/Remote (Function No. 2.02) to Jog Disabled;
Local/Remote Enabled ("0002") to change the JOG-LCL/REM Key from Jog Operation
to Local/Remote Operation.
IODA Faults: External Fault Trip ("EF–t") indicates that a Multi-Function Input Terminal
(Function Nos. 7.00 – 7.06 set to "0008") has closed (and will change the state of the
Multi-Function Output Relay Contacts and the Multi-Function Open collectors (when
Function No. 8.00 to 8.03 is set to "0007")). Current Source Trip ("CS–t") indicates that
the current signal output (from the IODA) has been opened. Communication Error
("Err4") indicates that communication between the drive and the IODA has failed.
39
TABLE 26
DIGITAL READOUT CODES
Display Description
40
FUNCTION GROUP 7
MULTI-FUNCTION INPUT TERMINALS
Function Factory Actual
No. Description Range/Code Setting Setting
Multi-Function Input 0000: Preset Frequency Operation2
7.00 * 0000
Terminal 11 0001: Preset Frequency Operation2
0002: Preset Frequency Operation2
Multi-Function Input
7.01 * 0003: Up Frequency Command3 0001
Terminal 21
(See 7.14)
Multi-Function Input 0004: Down Frequency Command3
7.02 * 0002
Terminal 31 (See 7.14)
0005: Accel/Decel 2 (See 7.16)
Multi-Function Input 0006: Forward/Stop Command4
7.03 * 0009
Terminal 41 0007: Reverse/Stop Command4
Multi-Function Input 0008: External Fault (N.O. Contact)
7.04 * 0010
Terminal 51 0009: Reset
0010: N.O. Start4
Multi-Function Input (2-Wire or 3-Wire Start/Stop)
7.05 * 0003
Terminal 61 0011: N.C. Stop4
Multi-Function Input (3-Wire Start/Stop)
7.06 * 0004
Terminal 71 0012: External Fault (N.C. Contact)
7.07 Preset Frequency 1 (Hz) 0.00 – 240.0 5.00
7.08 Preset Frequency 2 (Hz) 0.00 – 240.0 10.00
7.09 Preset Frequency 3 (Hz) 0.00 – 240.0 20.00
7.10 Preset Frequency 4 (Hz) 0.00 – 240.0 25.00
7.11 Preset Frequency 5 (Hz) 0.00 – 240.0 30.00
7.12 Preset Frequency 6 (Hz) 0.00 – 240.0 35.00
7.13 Preset Frequency 7 (Hz) 0.00 – 240.0 40.00
0000: Free-Running5
Up/Down Frequency
7.14 0001: Incremental Change 0000
Control Mode
(See 7.15)
Increment of Up/Down
7.15 0.01 – 30.00 1.00
Frequency (Hz)
Accel/Decel 2 Time
7.16 0.3 – 180.0 1.5
(Seconds)
Note: 1. Each of the 7 Multi-Function Inputs can be programmed for any of the respective
function codes ("0000" – "0011"). 2. Preset Frequencies 1 – 7 are obtained by selecting a
specific combination of 3 Multi-Function Input Terminals. The specific frequencies are
programmed in Function Nos. 7.07 – 7.13. 3. For Up/Down Frequency Commands (codes
"0003" and "0004"), Frequency Control (Function No. 2.00) must be set to Up/Down Using
MFITs (code "0005"). 4. For Forward/Reverse Stop Commands (codes "0006" and "0007")
and N.O. Start / N.C. Stop (codes "0010" and "0011"), Run/Stop-Forward/Reverse Control
(Function No. 1.00) must be set to External Contacts (code "0001"). 5. The rate of change of
the "UP" Control for frequency setting, using external contacts, is proportional to the Accel
Time setting (Function No. 3.03). The incremental rate of change of the "DOWN" Control for
frequency setting, using external contacts, is proportional to the Decel Time Setting
(Function No. 3.04).
*Functions which can only be changed while the drive is in Stop Mode.
41
FUNCTION GROUP 8
MULTI-FUNCTION OUTPUT RELAYS AND OUTPUT SIGNAL OPERATION
Function Factory Actual
No. Description Range/Code Setting Setting
Multi-Function Output 0000: Run
8.00 * Relay 1 0001: Fault1 0000
(Terminals 23 – 25) 0002: Target Frequency
Multi-Function Output (8.04 ± 8.05)
8.01 * Relay 2 0003: Frequency Threshold Level 0001
(Terminals 26 – 28) (> 8.04 – 8.05)2
Multi-Function Open 0004: Frequency Threshold Level
8.02 * Collector Output 1 (< 8.04 + 8.05)3 0002
(Terminals 11, 12) 0005: I2t or I•t Fault
0006: Load Loss (See 5.03)
Multi-Function Open
8.03 * Collector Output 2 0007: External Fault 0004
(Terminals 13, 14) 0008: Motor Overload4
Frequency Set Point
8.04 0.00 – 240.0 0.00
(Hz)
Frequency Bandwidth
8.05 0.00 – 30. 00 1.00
(± Hz)
0000: Motor Frequency
Analog Output 1 Mode 0001: Set Frequency
8.06 (Terms. 15, 16) 0002: Motor Voltage 0000
(0 – 5 VDC) 0003: Bus Voltage
0004: Motor Current
Analog Output 1 Gain
8.07 0 – 200 100
(%)
0000: Motor Frequency
Analog Output 2 Mode 0001: Set Frequency
8.08 (Terms. 17, 18) 0002: Motor Voltage 0000
(See 8.09) 0003: Bus Voltage
0004: Motor Current
0000: 0 – 5 VDC
8.09 Analog Output 2 Type (5) 0001: 0 – 20 mA DC 0000
0002: 4 – 20 mA DC
Analog Output 2 Gain
8.10 0 – 200 100
(%)
Notes: 1. The Output Relay contacts will change state due to all Faults and Recovered
Faults. 2. The relay will activate above the setting in Function No. 8.04 and deactivate below
the setting in Function No. 8.04 minus the setting in Function No. 8.05. 3. The relay will
activate below the setting in Function No. 8.04 and deactivate above the setting in Function
No. 8.04 plus the setting in Function No. 8.05. 4. The Output Relay will change state when
the I2t or I•t Timer starts. 5. Analog Output 2 Type: For 0 – 5 VDC (code "0000"), set
Jumpers J2 and J3, on the IODA, to the "VOLT" position (factory setting). For 0 – 20 mA DC
(code "0001") or 4 – 20 mA DC (code "0002"), set Jumpers J2 and J3, on the IODA, to the
"CUR" position.
*Functions which can only be changed while the drive is in Stop Mode.
42
FUNCTION GROUP 9
ANALOG INPUT SIGNAL OPERATION
Function Factory Actual
No. Description Range/Code Setting Setting
1
9.00 Analog Input 1 Gain (%) 0 – 500 100
0000: Positive
9.01 Analog Input 1 Slope1 0000
0001: Negative
Analog Input 1 Offset
9.02 0 – 100 0
(%)1
0000: Unidirectional
9.03 Analog Input 1 Type1 0000
0001: Bidirectional
Analog Input 1
9.04 2 – 100 2
Response Time (mSec)1
9.05 Analog Input 2 Gain (%)2 0 – 500 100
0000: Positive
9.06 Analog Input 2 Slope2 0000
0001: Negative
Analog Input 2 Offset
9.07 0 – 100 0
(%)2
2 0000: Analog Voltage or Current3
9.08 Analog Input 2 Type 0000
0001: PWM4
Analog Input 2
9.09 2 – 100 2
Response Time (mSec)2
Notes: 1. For Analog Input 1 (Function Nos. 9.00 – 9.04), Frequency Control (Function No.
2.00) must be set to Analog Signal 1 (code "0002"). 2. For Analog Input 2 (Function Nos.
9.05 – 9.09), Frequency Control (Function No. 2.00) must be set to Analog Signal 2 (code
"0003). 3. For Current Signal Input, set Jumper J1, on the IODA, to the "CUR" position.
4. 0.15 – 1 kHz (0 – 100% duty cycle).
7 DIAGNOSTIC LEDs
The IODA has two PC board mounted LEDs to provide operational status. The green
power on LED (PWR) indicates that power is applied to the IODA from the drive. The
red status LED (STATUS) provides indication of the IODA operation, as described in
Table 27.
TABLE 27
STATUS INDICATOR LED
Condition Red STATUS LED
Normal Operation Not Illuminated
1
Communication Error Flashes 1 Second On and 1 Second Off
2
Current Source Trip Illuminated
Notes: 1. When a Communication Error occurs, the drive's 4-Digit Display will show "Err4".
2. When a Current Source Trip occurs, the drive's 4-Digit Display will show "CS-t".
43
LIMITED WARRANTY
For a period of 18 months from the date of original purchase, KB Electronics, Inc. will repair
or replace without charge, devices which our examination proves to be defective in material
or workmanship. This warranty is valid if the unit has not been tampered with by
unauthorized persons, misused, abused, or improperly installed and has been used in
accordance with the instructions and/or ratings supplied. The foregoing is in lieu of any
other warranty or guarantee, expressed or implied. KB Electronics, Inc. is not responsible
for any expense, including installation and removal, inconvenience, or consequential
damage, including injury to any person, caused by items of our manufacture or sale. Some
states do not allow certain exclusions or limitations found in this warranty and therefore
they may not apply to you. In any event, the total liability of KB Electronics, Inc. under any
circumstance, shall not exceed the full purchase price of this product. (rev 2/2000)